3.3 Single-Phase, Three-Phase, and Voltage Systems

Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Orientation and Source Control

1.1 ICC R17, T17, G17, and Jurisdiction Variance 1.2 Current Format, Cost, Time, and Passing Score 1.3 Licensing Board vs. Exam Provider 1.4 Official References, Open-Book Rules, and Calculators 1.5 Domain Weights and Study Map 1.6 Using the Practice Bank, Error Log, and NEC Index

2 Chapter 2: NEC Navigation, Definitions, and Code Strategy

2.1 NEC Book Structure and Article Map 2.2 Article 100 Definitions and Exam Language 2.3 Index, Table, and Annex Navigation 2.4 Shall, Shall Not, Permitted, and Informational Notes 2.5 Using Code References Without Overlooking Context 2.6 State Amendments and Code Edition Control 2.7 NEC Navigation Case Lab

3 Chapter 3: Electrical Theory and Calculation Foundations

3.1 Ohm's Law, Power, and Basic Units 3.2 Series, Parallel, and Circuit Behavior 3.3 Single-Phase, Three-Phase, and Voltage Systems 3.4 Continuous Loads, Demand, and 125 Percent Rules 3.5 Voltage Drop and Practical Calculation Setup 3.6 Load Calculation Workflow 3.7 Calculation Foundation Case Lab

4 Chapter 4: Services, Service Equipment, and Grounding/Bonding

4.1 Service Point, Service Conductors, and Disconnects 4.2 Service Load Calculation and Sizing 4.3 Service Equipment, Panelboards, and Switchboards 4.4 Grounding Electrode System and GEC 4.5 Bonding, Main Bonding Jumpers, and Effective Fault Path 4.6 Transformers and Separately Derived Systems 4.7 Services and Grounding Case Lab

5 Chapter 5: Feeders, Branch Circuits, and Conductor Sizing

5.1 Feeder vs. Branch Circuit Boundaries 5.2 Branch Circuit Ratings and Required Outlets 5.3 Conductor Ampacity, Temperature, and Terminal Ratings 5.4 Adjustment, Correction, and More Than Three Conductors 5.5 Overcurrent Protection and Small-Conductor Rules 5.6 GFCI, AFCI, Equipment Grounding, and Dwelling Circuits 5.7 Feeders and Branch Circuits Case Lab

6 Chapter 6: Wiring Methods, Raceways, Boxes, and Cables

6.1 Raceway Selection and Installation Logic 6.2 Underground Wiring, Wet Locations, and Protection 6.3 Boxes, Enclosures, and Conduit Bodies 6.4 Box Fill, Conductor Counting, and Device Yokes 6.5 Cabinets, Panelboards, and Switchboards 6.6 Flexible Cords, Cables, and Temporary Wiring 6.7 Wiring Methods Case Lab

7 Chapter 7: Equipment, Devices, Luminaires, and Controls

7.1 Receptacles, Switches, and Device Selection 7.2 Luminaires, Lampholders, and Lighting Outlets 7.3 Appliances and Utilization Equipment 7.4 Heating, Cooling, and HVAC Electrical Connections 7.5 Disconnects, Controllers, and Switching Devices 7.6 Equipment Grounding, Bonding, and Listing Markings 7.7 Equipment and Devices Case Lab

8 Chapter 8: Motors, Generators, Transformers, and Special Equipment

8.1 Motor Circuit Anatomy and Article 430 Navigation 8.2 Motor Conductors, Overload, and Short-Circuit Protection 8.3 Motor Controllers, Disconnects, and Nameplates 8.4 Generators, Transfer Equipment, and Optional Standby 8.5 Transformer Sizing, Protection, and Grounding 8.6 Emergency Systems, Fire Alarms, and Signaling Overview 8.7 Motors and Generators Case Lab

9 Chapter 9: Special Occupancies, Renewables, and Safety

9.1 Hazardous Classified Locations 9.2 Healthcare, Marinas, RV Parks, and Mobile Home Parks 9.3 Pools, Spas, and Similar Installations 9.4 Solar PV, Energy Storage, and Renewable Systems 9.5 Temporary Power, Emergency Systems, and Special Conditions 9.6 OSHA Subpart K and Safe Work Practice Context 9.7 Special Occupancies Case Lab

10 Chapter 10: Open-Book Exam Workflow and Mixed Code Labs

10.1 Four-Hour Pacing and Question Triage 10.2 Look-Up vs. Know-From-Memory Decisions 10.3 Mixed Calculation Lab 10.4 Mixed Code Navigation Lab 10.5 Diagnostic Report and Error Log Remediation 10.6 High-Weight Domain Remediation Plan 10.7 Full Exam Simulation Playbook

11 Chapter 11: Final Review, Test Day, and License Planning

11.1 Final Two-Week Study Plan 11.2 Reference Book, Tabs, and Allowed Materials Checklist 11.3 Pearson VUE, PRONTO, and Test-Day Rules 11.4 After the Exam: Results, Retakes, and Challenges 11.5 License Application, Work Hours, and Jurisdiction Next Steps 11.6 After Journeyman: Master, Contractor, and Continuing Education

3.3 Single-Phase, Three-Phase, and Voltage Systems

Key Takeaways Explain This Topic AI

Single-phase and three-phase systems use different current formulas, especially when converting VA or kVA to amperes.

Three-phase current calculations normally use the square root of 3 multiplier because line relationships differ from single-phase circuits.

Nominal voltage systems must be read carefully; 120/240, 120/208, 277/480, and 240-volt delta systems lead to different load connections.

Exam traps often come from using line-to-neutral voltage when line-to-line voltage is required, or forgetting the 1.732 factor for three-phase.

Last updated: May 2026

Read the system before choosing the formula

Many wrong exam answers are produced before the first calculator entry. The candidate sees kVA and voltage, grabs a familiar formula, and ignores whether the system is single-phase or three-phase. The NEC uses many system types, and the question may state the system directly: 120/240-volt single-phase, 120/208-volt three-phase, 277/480-volt three-phase, or another nominal system.

The first discipline is to identify what voltage the load actually uses. A 120-volt receptacle load is line-to-neutral on a grounded system. A 240-volt water heater on a dwelling service is line-to-line. A 208-volt three-phase load uses line-to-line voltage. A 277-volt lighting load on a 480Y/277-volt system uses line-to-neutral voltage. The label on the system tells you the available voltages, not always the voltage of every load.

Single-phase formulas

For a single-phase two-wire load:

  • VA = E x I
  • I = VA / E

For a single-phase 3-wire service or feeder, the same apparent-power relationship works when total VA and line-to-line voltage are used for a balanced two-line load calculation. For many NEC load calculations, you total the VA and divide by the service or feeder voltage that supplies the load.

Example: a single-phase 240-volt load is 12 kVA. Current is 12,000 / 240 = 50 A.

Example: a 120-volt load is 1,800 VA. Current is 1,800 / 120 = 15 A.

The trap is mixing the voltage. If the 12 kVA load is truly 240 volts, dividing by 120 gives 100 A, which doubles the correct line current. If the load is truly 120 volts, dividing by 240 gives half the correct current. Read the load connection, not just the service label.

Three-phase formulas

For balanced three-phase apparent power:

  • VA = 1.732 x Eline x Iline
  • Iline = VA / (1.732 x Eline)

The number 1.732 is the approximate square root of 3. It appears because three-phase line quantities are separated by 120 electrical degrees. On the exam, use 1.732 unless the question or calculator gives a square-root function and you prefer using sqrt(3). Do not use 3 in place of 1.732 for line current calculations.

Example: a 45 kVA three-phase load is supplied at 208 volts. What is the line current?

Convert kVA to VA: 45 kVA = 45,000 VA.

I = 45,000 / (1.732 x 208) = 45,000 / 360.256 = 124.9 A.

The practical answer is about 125 A before any code sizing rule is applied. A common distractor is 216 A, which comes from 45,000 / 208 and ignores the three-phase factor.

Common voltage systems

  • System description Common available voltages Typical use
  • 120/240 V single-phase, 3-wire 120 V line-to-neutral, 240 V line-to-line Dwellings and small services

120/208 V three-phase, 4-wire wye 120 V line-to-neutral, 208 V line-to-line Commercial receptacles and small three-phase loads

277/480 V three-phase, 4-wire wye 277 V line-to-neutral, 480 V line-to-line Commercial lighting and larger motors

240 V delta variants 240 V line-to-line, sometimes special grounded conductor relationships Older or specialized installations

Do not assume every three-phase system has a neutral. Do not assume every 240-volt system is single-phase. Do not assume a high-leg delta allows ordinary 120-volt loads from every phase to neutral. When a question asks about a special system, the NEC rules and definitions become important; when it asks for current from kVA, the formula still depends on phase and voltage.

Line-to-line and line-to-neutral

A slash in a voltage rating usually shows line-to-neutral and line-to-line values on a grounded system. In 120/208 V, 120 is line-to-neutral and 208 is line-to-line. In 277/480 V, 277 is line-to-neutral and 480 is line-to-line. A three-phase motor rated 480 V uses line-to-line voltage. A lighting load rated 277 V uses line-to-neutral voltage.

Example: A 9,600 VA 277-volt lighting load draws I = 9,600 / 277 = 34.7 A. Do not divide by 480 because the luminaires are connected line-to-neutral. Example: A 30 kVA 480-volt three-phase load draws I = 30,000 / (1.732 x 480) = 36.1 A. Do not divide by 277 because the load is connected line-to-line across the three-phase system.

Balanced and unbalanced loads

The simple three-phase formula assumes a balanced load. NEC service and feeder calculations often total VA by category and then apply demand factors, neutral rules, or special load rules. A real panel may be unbalanced phase to phase. The exam will usually provide enough information to know whether it wants a balanced three-phase formula or a code load calculation workflow.

If a question gives separate phase currents or line-to-neutral loads, do not force everything into one balanced formula unless it tells you to. Add VA on each phase or follow the stated method. The word balanced is a strong signal that the standard three-phase formula is appropriate.

Calculator and rounding discipline

Write the denominator as one expression: 1.732 x voltage. Then divide VA by that denominator. Avoid entering 45 x 1000 / 1.732 x 208 without parentheses on a basic calculator, because left-to-right entry may multiply by 208 after dividing. Use this sequence: 45,000, divide, open or mentally compute 1.732 x 208, equals. On a four-function calculator, compute the denominator first, write it down, then divide.

Carry one decimal place unless the answer choices are far apart. NEC conductor and overcurrent sizing may require moving to the next standard size or using an ampacity table after the theoretical current is found. Do not round down a load current before applying a 125 percent rule or a table selection.

Exam traps

The largest trap is the missing 1.732. The second is using the wrong voltage from a slash-rated system. The third is treating kVA as amperes. The fourth is applying a motor horsepower conversion when the NEC directs you to motor full-load current tables. The fifth is confusing calculated current with permitted overcurrent protection. Theory gives the current; the NEC determines the installation requirement.