8.2 Fuel Gas Pipe Sizing & Pressure Drop
Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Code Enforcement, & Safety
1.1 Administration, Permits, and Inspections 1.2 General Regulations & Building Integrity 1.3 Material Standards & Piping Joining Methods 1.4 Plumbing Math & Water Calculations 1.5 Isometric Drawings & Blueprint Reading
2 Chapter 2: Plumbing Fixtures, Appliances, & Water Heaters
Plumbing Fixtures & Minimum Standards Water Heaters & Safety Devices Special Fixtures & Healthcare Plumbing Fixture Installation & Connection Rules Water Conservation & Flow Rates
3 Chapter 3: Water Supply & Distribution Systems
Water Service Piping & Main Sizing Water Supply Sizing & WSFU Calculations Backflow Prevention & Cross-Connection Control Water Pressure Boosters & Reducing Valves Hot Water Distribution & Recirculation Disinfection & Potable Water Quality
4 Chapter 4: Sanitary Drainage Systems & DFU Sizing
4.1 Sanitary Drainage Fundamentals & DFU 4.2 Drainage Pipe Sizing & Minimum Slopes 4.3 Building Drains, Sewers, & Cleanouts 4.4 Sumps, Ejectors, & Sewage Pumps 4.5 Special Wastes & Chemical Drainage 4.6 Indirect & Special Waste Piping
5 Chapter 5: Plumbing Venting Systems
5.1 Venting Principles & Vent Stack Sizing 5.2 Individual, Common, & Wet Venting 5.3 Circuit, Loop, & Island Venting 5.4 Air Admittance Valves & Combination Vents 5.5 Vent Terminals & Roof Penetrations
6 Chapter 6: Traps, Interceptors, & Separators
6.1 Trap Requirements & Hydraulic Seals 6.2 Trap Seal Protection & Primers 6.3 Grease Interceptors & Hydromechanical Traps 6.4 Oil, Sand, & Flammable Liquid Separators 6.5 Backwater Valves & Flood Protection
7 Chapter 7: Storm Drainage & Exterior Systems
7.1 Storm Drainage Sizing & Roof Drains 7.2 Subsoil Drainage & Sump Systems 7.3 Combined & Separated Sewer Connections 7.4 Rainwater Harvesting & Non-Potable Systems
8 Chapter 8: Fuel Gas Piping & Appliance Venting
8.1 Fuel Gas Piping Materials & Joints 8.2 Fuel Gas Pipe Sizing & Pressure Drop 8.3 Gas Pipe Inspection, Testing, & Purging 8.4 Appliance Venting & Draft Hoods 8.5 Combustion Air & Appliance Location
8.2 Fuel Gas Pipe Sizing & Pressure Drop
Key Takeaways Explain This Topic AI
Appliance fuel demand in Cubic Feet per Hour (CFH) is calculated by dividing total appliance BTU/hr input by the gas heating value (1,000 BTU/cu ft for Natural Gas; 2,500 BTU/cu ft for LP Gas).
The Longest Length Method sizes every piping segment in the system based on the total distance from the meter to the single most remote appliance outlet.
Standard low-pressure natural gas systems are sized using code capacity tables based on an allowable pressure drop of 0.5 inches of water column (125 Pa).
Natural Gas has a specific gravity of 0.60 (lighter than air), whereas LP Gas (Propane) has a specific gravity of 1.50 (heavier than air), requiring capacity conversion factors when referencing standard tables.
The Branch Length Method allows individual branch lines to be sized based on the distance from the gas meter to that specific appliance outlet, rather than the most remote appliance.
Last updated: August 2026
- Fuel Gas Pipe Sizing & Pressure Drop
- 1. Gas Volumetric Flow Rate & BTU Calculations
Sizing a fuel gas piping distribution system requires converting the thermal heat input ratings of all connected gas appliances into a volumetric flow rate expressed in Cubic Feet per Hour (CFH) . The volumetric demand dictates the pipe internal diameter necessary to deliver gas without excessive pressure drop.
Thermal Heating Values of Fuel Gases
A British Thermal Unit (BTU) is defined as the quantity of heat required to raise the temperature of 1 pound of liquid water by 1 ∘ F 1^\circ\text{F} 1 ∘ F . Fuel gases vary in energy density:
Natural Gas (Nominal): 1 , 000 BTU per cubic foot ( 37.3 MJ/m 3 ) 1,000 \text{ BTU per cubic foot } (37.3 \text{ MJ/m}^3) 1 , 000 BTU per cubic foot ( 37.3 MJ/m 3 )
Liquid Petroleum (Propane) Gas: 2 , 500 BTU per cubic foot ( 93.1 MJ/m 3 ) 2,500 \text{ BTU per cubic foot } (93.1 \text{ MJ/m}^3) 2 , 500 BTU per cubic foot ( 93.1 MJ/m 3 )
Commercial Butane Gas: 3 , 200 BTU per cubic foot ( 119.2 MJ/m 3 ) 3,200 \text{ BTU per cubic foot } (119.2 \text{ MJ/m}^3) 3 , 200 BTU per cubic foot ( 119.2 MJ/m 3 )
The CFH Demand Formula Volumetric Flow Rate (CFH) = Total Appliance Input Rating (BTU/hr) Gas Heating Value (BTU/cu ft) \text{Volumetric Flow Rate (CFH)} = \frac{\text{Total Appliance Input Rating (BTU/hr)}}{\text{Gas Heating Value (BTU/cu ft)}} Volumetric Flow Rate (CFH) = Gas Heating Value (BTU/cu ft) Total Appliance Input Rating (BTU/hr) ┌────────────────────────────────────────────────────────────────────────────────────────┐
- │ SAMPLE APPLIANCE CFH DEMAND CONVERSION TABLE │
- ├─────────────────────────────┬──────────────────┬───────────────────┬───────────────────┤
- │ Appliance Description │ BTU/hr Input │ Natural Gas (CFH) │ Propane Gas (CFH) │
- │ │ Rating │ (BTU / 1,000) │ (BTU / 2,500) │
- ├─────────────────────────────┼──────────────────┼───────────────────┼───────────────────┤
- │ Central Heating Furnace │ 100,000 BTU/hr │ 100 CFH │ 40 CFH │
- │ Storage Water Heater │ 40,000 BTU/hr │ 40 CFH │ 16 CFH │
- │ Tankless Water Heater │ 199,000 BTU/hr │ 199 CFH │ 79.6 CFH │
- │ Residential Kitchen Range │ 65,000 BTU/hr │ 65 CFH │ 26 CFH │
- │ Clothes Dryer │ 35,000 BTU/hr │ 35 CFH │ 14 CFH │
- ├─────────────────────────────┼──────────────────┼───────────────────┼───────────────────┤
- │ TOTAL COMBINED LOAD │ 439,000 BTU/hr │ 439 CFH │ 175.6 CFH │
- └─────────────────────────────┴──────────────────┴───────────────────┴───────────────────┘
- 2. Gas Pressure Fundamentals & Pressure Drop Thresholds
Fuel gas distribution pressures are measured in Pounds per Square Inch (psi) or Inches of Water Column (in. w.c.) . 1 psi = 27.7 inches of water column ( in. w.c. ) 1 \text{ psi} = 27.7 \text{ inches of water column } (\text{in. w.c.}) 1 psi = 27.7 inches of water column ( in. w.c. ) 0.5 psi ≈ 14.0 inches of water column ( in. w.c. ) 0.5 \text{ psi} \approx 14.0 \text{ inches of water column } (\text{in. w.c.}) 0.5 psi ≈ 14.0 inches of water column ( in. w.c. )
Low-Pressure Natural Gas Systems
Standard residential and commercial interior gas piping downstream of the utility meter regulator operates at a low supply pressure of 6 to 7 in. w.c. ( 0.22 – 0.25 psi 0.22\text{--}0.25\text{ psi} 0.22 – 0.25 psi ). Model codes base standard pipe sizing tables on an allowable system pressure drop of 0.5 in. w.c. ( 125 Pa 125\text{ Pa} 125 Pa ). This ensures that the minimum manifold pressure delivered to appliance control valves does not drop below 3.5 to 5.0 in. w.c. during peak simultaneous demand.
Medium-Pressure Gas Systems (2 psi / 5 psi)
In larger commercial buildings or modern residential installations, medium-pressure systems operate at 2.0 psi ( 55.4 in. w.c. 55.4\text{ in. w.c.} 55.4 in. w.c. ). A Line Pressure Regulator (MPR) certified to ANSI Z21.80 is installed immediately upstream of each appliance to reduce pressure from 2.0 psi down to 7.0 in. w.c. Sizing tables for 2.0 psi systems permit an allowable pressure drop of 1.0 psi , drastically reducing required pipe diameters.
3. The Longest Length Method (Step-by-Step Code Algorithm)
The Longest Length Method is the primary procedure mandated by IFGC Section 402 and NFPA 54 Section 6.2 for sizing gas piping. Under this method, every pipe segment in the entire piping layout is sized using the single column in the code capacity table corresponding to the total distance from the gas supply point to the single most remote appliance outlet . METER (Supply Point)
- │
- │ Segment A (Trunk Line: 439 CFH)
- ▼
- ┌──────┴──────────────────────┐
- │ │
- Segment B (199 CFH) Segment C (240 CFH)
- Tankless Heater (50 ft) │
- ▼
- ┌──────┴──────────────┐
- │ │
- Segment D (100 CFH) Segment E (140 CFH)
Furnace (70 ft) Furthest Outlet:
- Range (90 ft)
- Step-by-Step Sizing Procedure
Determine Longest Length: Measure the total pipe length from the meter to the furthest appliance. In the schematic above, the distance to the Range is 90 feet (the longest length in the system).
Select Code Table Column: Locate the Schedule 40 Metallic Pipe Capacity Table for Natural Gas — IFGC Table 402.4(2) / NFPA 54 Table 6.2(a), inlet pressure less than 2 psi, 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. drop, G = 0.60 G=0.60 G = 0.60 . Round 90 feet up to the 100-foot length row. Critical Rule: you must use the 100-foot row for ALL pipe segments (A, B, C, D, and E). The capacities on that row are:
- Nominal pipe size 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in
- Capacity at 100 ft (CFH) 50 105 197 404 606 1,170
Size Main Trunk Segment A: Segment A carries the total load of all appliances ( 439 CFH 439\text{ CFH} 439 CFH ). On the 100-foot row, locate a capacity ≥ 439 CFH \ge 439\text{ CFH} ≥ 439 CFH . A 1-1/4 inch pipe carries 404 CFH 404\text{ CFH} 404 CFH (insufficient), while a 1-1/2 inch pipe carries 606 CFH 606\text{ CFH} 606 CFH . Select 1-1/2 inch steel pipe.
Size Branch Segment B (Tankless): Segment B carries 199 CFH 199\text{ CFH} 199 CFH . On the SAME 100-foot row, a 1-inch pipe carries only 197 CFH 197\text{ CFH} 197 CFH — two CFH short. Select 1-1/4 inch pipe ( 404 CFH 404\text{ CFH} 404 CFH ). This is exactly why a 199,000 BTU/hr tankless heater so often forces an upsize on a long run.
Size Segment C: Segment C carries the combined load of the remaining appliances ( 240 CFH 240\text{ CFH} 240 CFH ). On the 100-foot row, 1-inch carries 197 CFH 197\text{ CFH} 197 CFH (insufficient), so select 1-1/4 inch pipe.
Size Branch Segment D (Furnace): Segment D carries 100 CFH 100\text{ CFH} 100 CFH . On the 100-foot row, a 3/4-inch pipe carries 105 CFH 105\text{ CFH} 105 CFH . Select 3/4-inch pipe.
Size Branch Segment E (Range): Segment E carries 140 CFH 140\text{ CFH} 140 CFH . On the 100-foot row, 3/4-inch carries 105 CFH 105\text{ CFH} 105 CFH (insufficient), so a 1-inch pipe at 197 CFH 197\text{ CFH} 197 CFH is required.
Why the longest-length method costs pipe. Segments B, C and E are all physically much shorter than 90 feet, but the method forces every one of them onto the 100-foot row. The Branch Length Method in the next part relaxes exactly this penalty.
4. The Branch Length Method
The Branch Length Method is an alternative sizing procedure permitted by code. Under this method:
The main distribution trunk is sized using the longest distance from the meter to the furthest appliance outlet.
Individual branch lines are sized using the distance from the meter to that specific branch outlet .
This method allows smaller pipe sizes on short branch runs near the meter, optimizing installation cost.
5. Specific Gravity Adjustments (Natural Gas vs. Propane)
Specific Gravity ( G G G ) is the ratio of the density of a gas to the density of dry air ( G air = 1.00 G_{\text{air}} = 1.00 G air = 1.00 ).
- Natural Gas: G = 0.60 G = 0.60 G = 0.60 (Lighter than air; floats upward)
- Propane (LP) Gas: G = 1.50 G = 1.50 G = 1.50 (Heavier than air; sinks and pools in low areas)
Flow capacity through a pipe varies inversely with the square root of specific gravity: Multiplier Factor = 0.60 G new = 0.60 1.50 = 0.40 ≈ 0.632 \text{Multiplier Factor} = \sqrt{\frac{0.60}{G_{\text{new}}}}=\sqrt{\frac{0.60}{1.50}}=\sqrt{0.40} \approx 0.632 Multiplier Factor = G new 0.60 = 1.50 0.60 = 0.40 ≈ 0.632
To use a standard Natural Gas capacity table for Propane gas, multiply the natural gas table capacity values by 0.632 . A pipe that carries 100 CFH 100\text{ CFH} 100 CFH of natural gas will carry only 63.2 CFH 63.2\text{ CFH} 63.2 CFH of propane at the same pressure drop.