10.1 Roof Drainage Design: Primary Drains, Secondary Overflow Scuppers & Sizing Calculations
Louisiana Residential Roofing Contractor Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Louisiana Licensing Law & Act 422 Regulatory Framework
1.1 Act 422 (2025): The Residential Roofing Classification, the $7,500 Threshold & Licensing Requirements 1.2 Act 239 (2025) Roof Permits & Inspections, Permit-Related Violations & Louisiana's Construction Code 1.3 LSLBC Enforcement: Violations, Cease-and-Desist Orders, Civil Fines & Criminal Penalties
2 Chapter 2: Louisiana Business Law, Contracts & Liens
2.1 Louisiana Private Works Act (La. R.S. 9:4801 et seq.): Privileges, Notices of Contract & Termination, and Lien Deadlines 2.2 Residential Roofing Contracts: Required Contents (R.S. 37:2159) & Property-Insurance Claim Rules (R.S. 37:2159.1) 2.3 Contractor Insurance (Liability & Workers' Compensation), the Statutory Employer Rule & Business Records
3 Chapter 3: Roofing Estimating, Plan Reading & Mathematics
3.1 Architectural Roof Plans, Symbols, Dimensions & Structural Pitch Calculations 3.2 Surface Area Calculations, Roofing Squares, Pitch Multipliers & Slope Formulas 3.3 Material Takeoff, Wastage Factors (Hips, Valleys, Rakes), and Jobsite Cost Estimating
4 Chapter 4: Roof Deck Preparation, Substrates & Re-Roofing Codes
4.1 Roof Deck Substrates (Plywood, OSB, Wood Board) & Structural Inspection Criteria 4.2 Reroofing Rules (IBC 1512 / IRC R908): Roof Replacement vs. Roof Recover, the Two-Layer Limit & Tear-Off Triggers 4.3 Deck Fastening, Nail Patterns, Damaged Sheathing Replacement & Clean Substrate Preparation
5 Chapter 5: Hurricane-Resistant Roofing, Wind Codes & FORTIFIED Standards
5.1 Louisiana Wind Speeds, Exposure, Wind-Borne Debris Regions & Roof Uplift Zones (IBC Chapter 16 / ASCE 7) 5.2 High-Wind Underlayment Rules (IBC Table 1507.1.1) & Sealed Roof Deck Options (Taped Seams, Two Layers, Full Self-Adhered) 5.3 IBHS FORTIFIED Roof (2025 Standard), the Louisiana Fortify Homes Program & Louisiana FORTIFIED Incentives 5.4 High-Wind Fastening Protocols: 6-Nail Shingle Patterns, Ring-Shank Nails & ASTM D3161/D7158 Wind Ratings
6 Chapter 6: Asphalt Shingles & Steep-Slope Assemblies
6.1 Asphalt Shingle Types (3-Tab vs. Laminated Architectural), ASTM Classifications & Thermal Behavior 6.2 Underlayment Specifications: Felt vs. Synthetic Underlayments & Self-Adhering High-Temperature Membranes 6.3 Shingle Application Mechanics: Starter Courses, Offsets, Fastener Placement & Wind Sealant Activation 6.4 Valley Construction Assemblies (Open Metal, Woven, Closed-Cut) & Ridge / Hip Cap Installations
7 Chapter 7: Metal, Tile, Slate & Wood Steep-Slope Systems
7.1 Metal Roof Panels & Metal Roof Shingles: Standing Seam, Exposed Fasteners, Minimum Slopes & Thermal Movement 7.2 Concrete & Clay Tile Roof Systems: Battens, Direct-to-Deck, Wind Uplift Resistance & Foam/Mortar Adhesion 7.3 Natural Slate & Synthetic Tile Roofing: Installation Fundamentals, Headlap & Fastening 7.4 Wood Shingles & Wood Shakes (IBC 1507.8–1507.9): Grades, Slopes, Sheathing, Exposure, Spacing & Fasteners
8 Chapter 8: Low-Slope Membranes & Built-Up Roofing (BUR)
8.1 Built-Up Roofing (BUR) Systems: Asphalt vs. Coal Tar Pitch, Organic/Glass Felts & Surfacings 8.2 Polymer-Modified Bitumen Systems: SBS vs. APP, Torched, Hot-Mopped, Cold-Adhesive & Self-Adhered Sheets 8.3 Single-Ply Roofing Membranes: TPO, PVC, and EPDM (Attachment Methods, Seam Welding & Ballast) 8.4 Low-Slope Rigid Insulation, Cover Boards, Vapor Retarders & Thermal Barriers
9 Chapter 9: Flashing, Penetrations & Roof Ventilation
9.1 Edge Metal & Drip Edge: Code Rules (IBC 1507.2.8.3 / IRC R905.2.8.5), FORTIFIED Upgrades & ES-1 Edge Securement 9.2 Step Flashing, Counterflashing, Chimney Crickets & Reglet Details 9.3 Plumbing Vents, Mechanical Exhausts, Skylight Curbs & Roof Penetration Seals 9.4 Attic Ventilation: Net Free Ventilating Area (1/150 vs. 1/300 Rule, IBC 1202.2 / IRC R806), Balanced Airflow & Unvented Attics
10 Chapter 10: Roof Drainage, Maintenance & Emergency Repairs
10.1 Roof Drainage Design: Primary Drains, Secondary Overflow Scuppers & Sizing Calculations 10.2 Gutters, Downspouts, Splash Blocks & Stormwater Runoff Management 10.3 Post-Storm Emergency Tarping, Temporary Shoring, Moisture Assessment & Insurance Scope Documentation
11 Chapter 11: OSHA Safety, Fall Protection & Jobsite Environmental Controls
11.1 OSHA 29 CFR 1926 Subpart M: Fall Protection Systems (Guardrails, Safety Nets, PFAS, Warning Lines & Monitors) 11.2 Ladder & Scaffolding Safety (29 CFR 1926 Subpart L & X, 4:1 Extension Rule, Tie-Off & Pitch) 11.3 PPE, Tool Safety, Hot Kettle/Torch Safety & Hazardous Material Communication (Lead, Asbestos, Silica) 11.4 Heat Illness Prevention & Louisiana High-Humidity Environmental Field Controls
10.1 Roof Drainage Design: Primary Drains, Secondary Overflow Scuppers & Sizing Calculations
Key Takeaways Explain This Topic AI
Louisiana uses the 2021 IPC, whose Chapter 11 sizes roof drains and storm piping from the 100-year, 1-hour rainfall rate on its maps or approved local data.
IPC Equation 11-1 converts rain to flow: gallons per minute equals 0.0104 times rainfall (in/hr) times roof area (sq ft), about area times rate divided by 96.
Secondary drains or scuppers are required where parapets or other perimeter construction would trap water if the primary drains clog (IBC 1502.2, IPC 1108.1).
Overflow scuppers must be at least 4 inches in every opening dimension (IBC 1502.3); for dwellings, IRC R903.4.1 sets the inlet 2 inches above the roof's low point.
Each inch of ponded water weighs about 5.2 psf, so a blocked drain can overload a roof designed only for the 20 psf minimum roof live load.
Last updated: September 2026
Roof Drainage Design: Primary Drains, Secondary Overflow Scuppers & Sizing Calculations
Low-slope commercial and residential roofing assemblies must do more than simply resist rainwater penetration—they must actively collect, channel, and evacuate vast volumetric quantities of storm runoff. Unlike steep-slope roofs that shed precipitation almost instantaneously via gravity, low-slope roofs (typically pitched between 1/4:12 and 1:12) rely on controlled sheet flow toward designated primary internal drains or exterior perimeter outlets. In Louisiana, where tropical depressions, squall lines, and hurricanes routinely produce torrential precipitation rates exceeding 4 to 5 inches per hour, undersized or improperly engineered roof drainage systems represent an immediate structural hazard. The Louisiana State Uniform Construction Code (LSUCC) adopts the 2021 International Plumbing Code (IPC) , whose Chapter 11 sizes storm drainage, and the 2021 IBC , whose Section 1502 requires secondary (emergency overflow) drainage. Roofing contractors must understand both, because they install the drains, sumps, and scuppers.
1. Fluid Mechanics & Hydraulic Fundamentals of Low-Slope Roof Drainage
Rainwater falling onto a low-slope roof behaves according to open-channel fluid mechanics. As precipitation gathers across the waterproofing membrane, it forms a thin sheet that flows down the engineered slope toward the lowest elevation of the roof deck. However, once water approaches an interior roof drain, its hydraulic behavior transforms from shallow sheet flow into a radial drawdown depression known as a hydraulic cone: PRIMARY ROOF DRAIN ASSEMBLY & HYDRAULIC DRAWDOWN CONE
- Cast-Iron Dome Strainer (Vortex Suppressor)
- ┌───┬───┬───┐
- ┌────┘ │ └───┐
- Sheet Flow Inflow │ [ ] │ [ ] │ Sheet Flow Inflow
- ──────────────────> ───────┴────────┴───────┴─────── <──────────────────
- ╲ ╱
- ╲ Drawdown Vortex Cone ╱
- ======================█ █====================== <── Roof Membrane
- ──────────────────────█ █────────────────────── <── Rigid Insulation
- ======================█═════════════════════════█====================== <── Structural Deck
- │ Clamping Ring & Pan │
- │ ┌─────────────────────┐ │
- │ │ DECK SUMP PAN │ │ <── Depressed 1/2" to 1-1/2"
- │ └─────────────────────┘ │
- │ │
- │ Vertical Conductor │
- │ (Annular Gravity │
- │ Downflow) │
- ▼ ▼
- A. Hydraulic Head and Vortex Suppression
When water flows into an open vertical pipe, it naturally forms a spiraling vortex (analogous to water draining from a bathtub). This vortex pulls a core of ambient air into the center of the vertical conductor pipe. The air core takes up part of the pipe, reducing how much water it can carry and letting water back up on the roof.
To reduce vortex formation, roof drains are fitted with cast-iron or polymer dome strainers with vertical vanes:
Vortex Baffling: The vanes make water enter radially instead of swirling, which reduces air intake and increases flow.
Strainer Area: Drain manufacturers make the strainer's open area much larger than the outlet pipe, so partly blocked slots still let water through.
Code Rules: IPC 1102.6 requires roof drains to conform to ASME A112.3.1 or A112.6.4, and to be tested and rated for flow. IPC 1105.1 requires installation per the manufacturer's instructions and states that the roofing membrane must not obstruct the drain's inside opening. IPC 1105.2 requires the drain's published flow rate at the expected water head to be used in sizing.
B. Sump Pans and Deck Depressions
Gravity flow velocity is directly proportional to hydraulic head—the vertical distance between the surface of the ponded water and the drain inlet. If a roof drain flange is installed directly on top of the insulation layer, the thickness of the drain body and membrane flashing rings creates a 1/2-inch to 3/4-inch raised lip. This lip creates permanent "bird baths"—stagnant rings of water around the drain that accelerate membrane degradation.
To achieve positive drainage:
Primary drains are commonly set in a deck sump pan (a recessed metal pan) or a tapered insulation sump, often about 36 by 36 to 48 by 48 inches .
The sump depresses the drain bowl 1/2 inch to 1-1/2 inches below the primary roof plane. This depression speeds water into the bowl and prevents a ring of standing water around the drain.
C. Clamping Rings and Underdeck Anchoring
The interface between the roof drain bowl and the waterproofing membrane is a high-stress transition subject to severe mechanical vibration, water pressure, and thermal movement:
Clamping Ring Flange: The roofing membrane (BUR plies, modified bitumen, or single-ply TPO/EPDM/PVC) is cut flush with the drain bowl throat. A heavy cast-iron clamping collar is set over the membrane and bolted into the drain body using 3/8-inch or 1/2-inch stainless steel machine bolts. The clamping ring exerts hundreds of pounds of uniform radial compression, pinching the membrane against the drain lip to create a permanent hydrostatic seal without relying on topical caulking.
Underdeck Clamps: Beneath the structural roof deck, an underdeck clamp assembly mechanically anchors the drain bowl to the underside of the steel, concrete, or wood decking. Without an underdeck clamp, thermal expansion and contraction of long vertical plumbing stacks will push the drain bowl upward through the roof deck, dislodging the clamping ring and tearing the roof membrane.
2. Regulatory Framework: IPC Chapter 11 & Louisiana Design Rainfall Rates
Low-slope roof drainage across Louisiana is governed by Chapter 11 of the 2021 International Plumbing Code (IPC) , adopted in the LSUCC, together with IBC Section 1502.
A. The 100-Year, 1-Hour Storm Event Standard
IPC 1106.1 bases the size of conductors, leaders, and storm drains on the 100-year hourly rainfall rate shown in IPC Figures 1106.1(1) through 1106.1(5), or on rates from approved local weather data . A 100-year storm event is a severe meteorological occurrence that has a 1% statistical probability of occurring in any given year, sustained continuously over a 60-minute duration.
Louisiana's Gulf climate gives it some of the highest hourly rainfall rates in the country. NOAA Atlas 14 point estimates for the 100-year, 60-minute rainfall (NOAA Precipitation Frequency Data Server, checked 2026-09-27) show how much they vary across the state:
- Location 100-Year, 60-Minute Rainfall (NOAA Atlas 14 point estimate)
- Shreveport about 4.0 inches
- Monroe about 4.0 inches
- Baton Rouge about 4.4 inches
- Lafayette about 4.5 inches
- Alexandria about 4.7 inches
- Lake Charles about 4.8 inches
- New Orleans about 5.4 inches
- Houma about 5.6 inches
Use the rate the code official or the design professional approves for the site. The estimates vary block to block, and the IPC maps are coarser than NOAA's point data.
B. The Hydraulic Flow Equation ( Q Q Q )
IPC 1106.2.1 converts rainfall to flow with Equation 11-1 : Q = 0.0104 × R × A Q = 0.0104 \times R \times A Q = 0.0104 × R × A
Where:
Q Q Q = flow in gallons per minute (gpm) .
R R R = rainfall intensity in inches per hour .
A A A = horizontally projected roof area in square feet .
Because 0.0104 is almost exactly 1/96, the trade shortcut is Q = A × R ÷ 96 . Either form gives nearly the same answer.
Step-by-Step Calculation Example: A low-slope roof measures 120 feet by 150 feet (18,000 sq ft). The approved design rainfall rate is 5.0 inches per hour. Calculate the peak flow: Q = 0.0104 × 5.0 × 18,000 = 936 gpm Q = 0.0104 \times 5.0 \times 18{,}000 = 936 \text{ gpm} Q = 0.0104 × 5.0 × 18 , 000 = 936 gpm (The shortcut gives 18,000 × 5.0 ÷ 96 = 937.5 gpm.) The drains and piping serving this roof must carry about 936 gallons per minute.
C. Accounting for Intercepted Vertical Wall Runoff
When a roof is abutted by a higher wall, penthouse, or stair tower, wind drives rain against the wall and it runs down onto the roof. IPC 1106.4 requires one-half of the area of any vertical wall that diverts rainwater to the roof to be added to the projected roof area when sizing roof drains, conductors, leaders, and horizontal storm piping.
Example: A 40-foot-long, 12-foot-high penthouse wall (480 sq ft) drains onto a 5,000 sq ft roof area. Design area = 5,000 + (480 ÷ 2) = 5,240 sq ft .
3. Primary Interior Roof Drain Pipe Sizing
Roof drainage piping carries water in two ways: vertical downflow and horizontal flow. The 2021 IPC sizes both by flow rate in gpm . IPC 1106.2 requires the calculated flow to be checked against the roof drain manufacturer's published flow rate , and the flow in the piping must not exceed Table 1106.2 . Vertical leaders that serve gutters or drains must not exceed Table 1106.3 .
A. Storm Drain Pipe Capacity (IPC Table 1106.2)
Pipe Size (inches) Vertical Drain (gpm) Horizontal at 1/8 in/ft (gpm) Horizontal at 1/4 in/ft (gpm) Horizontal at 1/2 in/ft (gpm)
- 2 34 22 31 44
- 3 87 55 79 111
- 4 180 115 163 231
- 5 311 165 234 331
- 6 538 344 487 689
- 8 1,117 714 1,010 1,429
- 10 2,050 1,311 1,855 2,623
- B. Vertical Leader Capacity (IPC Table 1106.3)
- Leader Size (inches) Capacity (gpm) Roof Area at 5.0 in/hr (A = Q × 96 ÷ 5.0)
- 2 round, 2 × 2, or 1-1/2 × 2-1/2 30 about 576 sq ft
- 2-1/2 round or 2-1/2 × 2-1/2 54 about 1,037 sq ft
- 3 round, 2 × 4, or 2-1/2 × 3 92 about 1,766 sq ft
- 4 round, 3 × 4-1/4, or 3-1/2 × 4 192 about 3,686 sq ft
- 5 round, 4 × 5, or 4-1/2 × 4-1/2 360 about 6,912 sq ft
- 6 round, 5 × 6, or 5-1/2 × 5-1/2 563 about 10,810 sq ft
How to Use the Tables: (1) Find the flow with Equation 11-1. (2) Choose a drain whose published flow rate at the expected head is at least that flow. (3) Pick the smallest pipe whose table capacity is at least the flow, for the pipe's direction and slope. Example: 625 gpm in a horizontal drain at 1/4 inch per foot needs an 8-inch pipe (1,010 gpm), because a 6-inch pipe carries only 487 gpm.
4. Primary vs. Secondary (Emergency Overflow) Drainage Mandates
Building codes require secondary (emergency overflow) roof drainage wherever a clogged drain would let water build up on the roof. PRIMARY DRAINAGE VS. SECONDARY OVERFLOW SCUPPER GEOMETRY
- Parapet Wall
- ┌────────────┐
- │ │
- │ │
- │ ┌──────┐ │ <── OPEN SECONDARY OVERFLOW SCUPPER
- │ │ │ │ (Min. 4" x 4" opening, weir flow)
- │ │ │ │
- │ └──┬───┘ │
- │ │ │
- │ │ Inlet set above the roof low point
- │ ▼ │
- │ ──────── │ <── Finished Roof Membrane Plane
- │ │
- │ ┌────────┐ │
- └─┴─┐ ┌─┴─┘
- │ │
- │ │ <── PRIMARY INTERIOR ROOF DRAIN
- │ │ (Sumpted 1/2" to 1-1/2" below roof plane)
- │ │
- ▼ ▼
- To Internal Storm Sewer
- A. When Secondary Drainage Is Required (IBC 1502.2, IPC 1108.1, IRC R903.4.1)
The three codes use the same trigger: where roof drains are required , secondary (emergency overflow) drains or scuppers must be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason . Parapets are the usual example. If the primary drains clog with leaves or debris, the secondary system keeps water from rising past the depth the structure was designed for.
Reroofing note: IBC 1512.1 does not require a reroof to add secondary drains where the roof has positive drainage, but existing secondary drains or scuppers may not be removed unless replaced with compliant ones.
B. Independence from the Primary System
Separate discharge (IPC 1108.2): the secondary system's end point of discharge must be separate from the primary system . Where primary and secondary drains come as one assembly, each must have an independent inlet and outlet (IPC 1108.1). For dwellings, IRC R903.4.1 states that overflow drains shall not be connected to roof drain lines .
Why: if both systems shared a pipe, one downstream blockage would disable both.
Visible discharge (IPC 1108.2): discharge must be above grade, in a location that would normally be observed by occupants or maintenance staff. Water pouring from an overflow outlet is the warning that the primary drains are clogged.
No credit for primary flow: secondary drains are sized for the full design rainfall, and the flow through the primary system is not considered (IPC 1108.3, IBC 1502.3).
C. Inlet Elevation
Dwellings (IRC R903.4.1): overflow drains the same size as the roof drains have their inlet 2 inches above the low point of the roof ; or overflow scuppers three times the size of the roof drains , with an opening at least 4 inches high , are installed in the parapet with the inlet 2 inches above the low point of the roof served.
Other buildings (IBC 1502.3, IPC 1106.5): the quantity, size, location, and inlet elevation of scuppers must keep ponding water from exceeding the depth the roof was designed for under IBC 1611.1. Designers commonly set overflow inlets about 2 inches above the low point, and seldom more than about 4 inches, as the structural design allows.
Setting the inlet too low causes overflow in ordinary rains. Setting it too high lets deep, heavy water build up before overflow starts.
5. Secondary Scupper Engineering & Francis Weir Hydraulics
Where roof perimeters are bounded by parapet walls, contractors frequently install secondary overflow scuppers —rectangular penetrations through the parapet wall that discharge directly to the exterior building perimeter.
A. Open vs. Closed Scuppers
Open Scuppers: Open at the top of the parapet wall, extending to the parapet coping. An open scupper acts as a classic open-channel rectangular weir. Because there is no top header, floating leaves and debris can float cleanly through without wedging or creating an obstruction.
Closed Scuppers: A rectangular opening framed through the wall with a solid top. When water reaches the top, flow changes from weir flow to orifice flow, and debris can jam the opening.
B. Minimum Code Dimensions
IBC 1502.3: scuppers used for secondary drainage must not have an opening dimension of less than 4 inches .
IPC 1106.5 and 1108.3: scupper openings must be at least 4 inches high , with a width at least equal to the circumference of the roof drain required for the area served .
IRC R903.4.1: overflow scuppers are three times the size of the roof drains , at least 4 inches high .
Small openings clog easily with leaves and debris, which is why the codes set these minimums.
C. Sizing via the Francis Weir Formula
Designers often check an open scupper's capacity with the Francis weir formula for a rectangular weir. It is an engineering method, not a code formula: Q cfs = 3.33 × L × H 1.5 Q_{\text{cfs}} = 3.33 \times L \times H^{1.5} Q cfs = 3.33 × L × H 1.5
Where:
Q cfs Q_{\text{cfs}} Q cfs = Water discharge in cubic feet per second (cfs) ( 1.0 cfs = 448.83 GPM 1.0 \text{ cfs} = 448.83 \text{ GPM} 1.0 cfs = 448.83 GPM ).
L L L = Length (width) of the scupper opening in feet .
H H H = Hydraulic head (depth of water above the scupper invert) in feet .
Converting the equation directly into Gallons Per Minute (GPM): Q GPM = 1 , 495 × L × H 1.5 Q_{\text{GPM}} = 1,495 \times L \times H^{1.5} Q GPM = 1 , 495 × L × H 1.5
Secondary Overflow Scupper Capacity Matrix (GPM & Drainage Area)
Scupper Width (L) Head (H) Above Invert Flow Capacity (Q) in GPM Max Drainage Area @ 4.0 in/hr Max Drainage Area @ 5.4 in/hr (New Orleans area)
- 6 Inches (0.50 ft) 2 Inches (0.167 ft) 51 GPM 1,224 sq ft 907 sq ft
- 6 Inches (0.50 ft) 3 Inches (0.250 ft) 93 GPM 2,232 sq ft 1,653 sq ft
- 12 Inches (1.00 ft) 2 Inches (0.167 ft) 102 GPM 2,448 sq ft 1,813 sq ft
- 12 Inches (1.00 ft) 3 Inches (0.250 ft) 187 GPM 4,488 sq ft 3,324 sq ft
- 18 Inches (1.50 ft) 3 Inches (0.250 ft) 280 GPM 6,720 sq ft 4,978 sq ft
- 24 Inches (2.00 ft) 3 Inches (0.250 ft) 374 GPM 8,976 sq ft 6,649 sq ft
- 24 Inches (2.00 ft) 4 Inches (0.333 ft) 575 GPM 13,800 sq ft 10,222 sq ft
Drainage area = Q × 96 ÷ rainfall rate. Compare the result with the IPC minimums above; the scupper must satisfy both.
6. Hydrostatic Dead Load & Progressive Structural Ponding Instability
Roof drainage failure is not merely a waterproofing problem—it is a critical structural life-safety emergency. Water is extraordinarily heavy, and flat roofs are structural planes designed with finite dead- and live-load limits. PROGRESSIVE PONDING INSTABILITY: THE COLLAPSE LOOP
- ┌────────────────────────────────────────────────────────┐
- │ Primary Interior Drains Clog (Leaves, Debris, Ballast) │
- └───────────────────────────┬────────────────────────────┘
- │
- ▼
- ┌────────────────────────────────────────────────────────┐
- │ Water Rises: Adds 5.2 lbs/sq ft Dead Load Per Inch │
- └───────────────────────────┬────────────────────────────┘
- │
- ▼
- ┌────────────────────────────────────────────────────────┐
- │ Structural Steel Joists / Wood Trusses Deflect Down │
- └───────────────────────────┬────────────────────────────┘
- │
- ▼
- ┌────────────────────────────────────────────────────────┐
- │ Mid-Span Deflection Lowers Elevation: Deepens Low Spot │
- └───────────────────────────┬────────────────────────────┘
- │
- ▼
- ┌────────────────────────────────────────────────────────┐
- │ More Water Rushes from High Areas into Deepening Sag │
- └───────────────────────────┬────────────────────────────┘
- │ (The Uncontrolled Feedback Loop)
- ▼
- ┌────────────────────────────────────────────────────────┐
- │ Joist Yielding, Web Buckling & CATASTROPHIC COLLAPSE │
- └────────────────────────────────────────────────────────┘
- A. Hydrostatic Weight Calculation
The physical density of liquid water is 62.4 pounds per cubic foot ( 62.4 lbs/ft 3 62.4 \text{ lbs/ft}^3 62.4 lbs/ft 3 ) : Weight of 1 inch of water over 1 sq ft = 62.4 lbs/ft 3 12 inches = 5.20 lbs/sq ft (psf) \text{Weight of 1 inch of water over 1 sq ft} = \frac{62.4 \text{ lbs/ft}^3}{12 \text{ inches}} = 5.20 \text{ lbs/sq ft (psf)} Weight of 1 inch of water over 1 sq ft = 12 inches 62.4 lbs/ft 3 = 5.20 lbs/sq ft (psf)
As standing water deepens, hydrostatic load escalates rapidly:
- 1 Inch Depth: 5.2 psf 5.2 \text{ psf} 5.2 psf
- 2 Inches Depth: 10.4 psf 10.4 \text{ psf} 10.4 psf
- 3 Inches Depth: 15.6 psf 15.6 \text{ psf} 15.6 psf
- 4 Inches Depth: 20.8 psf 20.8 \text{ psf} 20.8 psf (more than the 20 psf minimum roof live load)
- 6 Inches Depth: 31.2 psf 31.2 \text{ psf} 31.2 psf
- 12 Inches Depth (1 Foot): 62.4 psf 62.4 \text{ psf} 62.4 psf
- B. The Mechanics of Progressive Ponding Instability
IBC Section 1611 sets the rain load , R = 5.2(ds + dh), where ds is the depth of water up to the secondary drain inlet with the primary drains blocked and dh is the extra depth above that inlet at design flow. IBC 1611.2 requires susceptible roof bays to be checked for ponding instability under ASCE 7:
Many light roofs are framed for the 20 psf minimum roof live load plus the rain load the designer calculated from the secondary drain height.
If primary drains clog and overflow scuppers are placed too high (e.g., 6 inches above the deck) or undersized, water rises past 4 inches, exerting more than 20.8 psf across the structural bay.
The joists deflect downward at mid-span. This downward deflection creates an artificial structural bowl.
Rainwater from adjacent, stiffer bays flows down the deflection slope into the sagging center, deepening the pool.
The added water increases the load, which causes further deflection, attracting still more water.
This self-feeding ponding instability can continue until members yield or buckle and the roof bay collapses.