Study guide

5.4 Non-Potable and Reclaimed Water Strategies

LEED AP Building Design + Construction BD+C

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction & Exam Overview

1.1 Current Exam Facts 1.2 How to Use This Guide

2 Chapter 2: Integrative Process

2.1 Integrative Process Philosophy and Workflow 2.2 Integrative Process Credit (IP) 2.3 Prerequisites and Project Setup 2.4 Certification Levels and Scorecard

3 Chapter 3: Location & Transportation + Surroundings

3.1 LEED for Neighborhood Development Location 3.2 Sensitive Land Protection & High Priority Site 3.3 Surrounding Density and Diverse Uses 3.4 Access to Quality Transit 3.5 Bicycle Facilities, Reduced Parking, Green Vehicles 3.6 Building Surroundings and Joint Use

4 Chapter 4: Sustainable Sites (SS)

4.1 SS Prerequisite: Construction Activity Pollution Prevention 4.2 Site Assessment and Site Development 4.3 Open Space and Rainwater Management 4.4 Heat Island Reduction 4.5 Light Pollution Reduction

5 Chapter 5: Water Efficiency (WE)

5.1 WE Prerequisites 5.2 Outdoor and Indoor Water Use Reduction Credits 5.3 Cooling Tower Water Use, Process Water, and Metering 5.4 Non-Potable and Reclaimed Water Strategies

6 Chapter 6: Energy & Atmosphere (EA)

6.1 EA Prerequisites 6.2 Optimize Energy Performance 6.3 Enhanced Commissioning 6.4 Advanced Energy Metering and Grid Harmonization 6.5 Renewable Energy and Carbon Offsets 6.6 ASHRAE 90.1-2016 Fundamentals

7 Chapter 7: Materials & Resources (MR)

7.1 MR Prerequisites 7.2 Building Life-Cycle Impact Reduction (BLIR) 7.3 Building Product Disclosure and Optimization (BPDO) 7.4 Construction and Demolition Waste Management 7.5 PBT Source Reduction and Furniture Material

8 Chapter 8: Indoor Environmental Quality (EQ)

8.1 EQ Prerequisites 8.2 Enhanced IAQ Strategies and Low-Emitting Materials 8.3 Construction IAQ Management and Assessment 8.4 Thermal Comfort 8.5 Interior Lighting and Daylight 8.6 Quality Views and Acoustic Performance

9 Chapter 9: Innovation, Regional Priority & Project Types

9.1 Innovation Credits 9.2 Regional Priority Credits 9.3 BD+C Project Types and Scope 9.4 Project Registration, Documentation, and Certification Process 9.5 Last-Minute Exam Tips

5.4 Non-Potable and Reclaimed Water Strategies

Key Takeaways Explain This Topic AI

Rainwater harvesting captures roof runoff into cisterns (with first-flush diverters and screens) and can supply irrigation, toilet flushing, cooling tower makeup, and — with disinfection — non-potable indoor uses.

Graywater systems collect lightly used water from lavatories, showers, and clothes washers for reuse in toilet flushing or subsurface irrigation, but cannot include kitchen, dishwasher, or toilet sources.

Blackwater treatment (membrane bioreactors, constructed wetlands) and condensate recovery from HVAC equipment expand non-potable supply beyond rainwater and graywater, often supporting cooling tower makeup or large irrigation loads.

Municipal reclaimed water (purple-pipe) is a high-value zero-additional-treatment option where utilities provide it; LEED treats it as non-potable for the 20% cooling tower threshold and the 100% outdoor reduction.

Plumbing code compliance varies by state — many jurisdictions follow the IPC, UPC, or amendments that prohibit graywater for indoor use or require purple-pipe labeling, backflow prevention, and color-dyed water; verify local rules before specifying systems.

Last updated: May 2026

The Strategy Layer Above Fixtures and Cycles

Fixture swaps and cycles of concentration get a project to the prerequisite floor and the early credit points. To reach 2 points outdoor , 5-6 points indoor , and the second cooling tower point , projects typically replace some potable demand with non-potable water sources .

  • The Five Non-Potable Sources
  • 1. Rainwater Harvesting

Roof runoff is collected, screened, and stored in cisterns or tanks. Typical system components:

First-flush diverter — sheds the first volume of rainfall (usually 0.05-0.1 in) carrying roof contaminants away from the cistern.

Leaf screen and filter before the inlet.

Storage cistern sized by water budget calculations (use vs. supply curves across the year).

Pump and pressure tank for distribution.

Backup potable connection with backflow preventer for dry periods.

For indoor use: filtration plus disinfection (UV, chlorine, or ozone) to meet local non-potable water quality standards.

Typical end uses: irrigation, toilet flushing, cooling tower makeup, vehicle wash water .

2. Graywater

Graywater is lightly used wastewater from:

  • Bathtubs, showers, lavatories
  • Clothes washers

It does not include : kitchen sinks, dishwashers, or toilet/urinal effluent (those are blackwater ). Graywater systems require:

Diversion plumbing — separate drain lines from blackwater.

Surge tank to hold incoming graywater.

Filtration (typically sand or membrane) to remove hair, lint, soap residue.

Disinfection for indoor reuse.

Purple-pipe distribution and signage to prevent cross-connection.

Typical end uses: toilet flushing, subsurface drip irrigation .

3. Blackwater Reuse and On-Site Treatment

Blackwater treatment systems take all building wastewater (graywater + toilet/kitchen) and treat it to a reuse standard. Approaches include:

System How it works

Membrane bioreactor (MBR) Combines biological treatment with microfiltration membranes; produces high-quality non-potable effluent suitable for cooling and flushing.

Constructed wetland Mimics natural wetland processes — wastewater flows through gravel beds planted with wetland species (cattails, bulrush) that uptake nutrients while microbes break down organics. Higher footprint, lower energy.

Recirculating sand filter Aerobic biological treatment through layered sand beds; common for small to mid-sized projects.

Living Building Challenge projects often pair these with composting toilets to fully close the water loop.

4. Condensate Recovery

When warm humid air contacts cold cooling coils in HVAC equipment, water condenses out — sometimes thousands of gallons per day in large or humid-climate buildings. Condensate is essentially distilled water (low dissolved solids) and is ideal for cooling tower makeup because it raises achievable cycles of concentration.

Key design points:

Slope condensate pans and lines to a collection sump .

Plumb to cooling tower basin or non-potable holding tank.

Add overflow to the storm drain for excess.

5. Municipal Reclaimed Water

Where utilities offer it, purple-pipe reclaimed water is treated wastewater delivered to building sites for non-potable uses. Because the utility has already treated it to a state-regulated reuse standard, the project's only requirements are:

Backflow prevention at the building connection.

Purple-pipe identification and signage.

No cross-connection with potable plumbing.

Reclaimed water counts toward the 100% outdoor reduction (Option 2, 2 points) and toward the 20% non-potable makeup for the cooling tower 2-point option.

Comparing Sources

  • Source Best Use Treatment Needed Code Sensitivity
  • Rainwater Irrigation, flushing, cooling Filter + disinfection for indoor Low for outdoor; moderate indoor
  • Graywater Flushing, subsurface irrigation Filter + disinfection High — banned indoors in some states
  • Blackwater (treated) Flushing, cooling, irrigation Advanced (MBR, wetland) High — permit-intensive
  • Condensate Cooling tower makeup, flushing Minimal Low
  • Reclaimed water Irrigation, flushing, cooling None (utility delivers) Low if utility offers it
  • Code, Health, and Verification Considerations

State plumbing codes vary widely. Some states (e.g., Texas, Arizona, California) have explicit graywater statutes; others restrict graywater to subsurface irrigation only; some prohibit indoor reuse entirely.

International Plumbing Code (IPC) Chapter 13 and Uniform Plumbing Code (UPC) Chapter 16 address non-potable water systems — required treatment, signage, dyeing, and backflow prevention.

EPA WaterSense labels apply not just to fixtures but also to irrigation controllers and irrigation professionals — specify WaterSense-certified components to claim higher irrigation efficiencies.

All non-potable systems require backflow preventers at the potable interface and clear labeling (purple pipe, signage) at every accessible component.

Verification at LEED documentation requires system schematics, water-budget calculations, permits, and treatment-system specifications — auditors look for evidence the system actually delivers the claimed gallons.

Pulling It All Together

A high-performing LEED BD+C project usually layers strategies: Low-flow WaterSense fixtures + dual-flush + waterless urinals

  • > meet 35-45% indoor reduction
  • Graywater or rainwater for toilet flushing
  • > push to 50% indoor reduction (6 pts)
  • Rainwater/condensate for cooling tower makeup at >20%
  • > earn 2nd cooling tower point
  • Reclaimed water or 100% non-potable irrigation
  • > earn 2 outdoor points
  • Sub-meters on irrigation, hot water, cooling tower, fixtures
  • > earn metering point

That full stack adds up to roughly 9-11 of the 11 WE points while staying inside common code constraints.