11.1 DFU Values & Load Calculations

Massachusetts Journeyman Plumber Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Massachusetts Licensing, Permits & Exam Process

1.1 Board, M.G.L. c. 142 & License Hierarchy 1.2 Permits, Inspections & Product Acceptance 1.3 Education, Experience, PSI Process & Excavation Safety

2 Fuel Gas Code, Materials & Pipe Sizing

2.1 248 CMR 4.00/5.00, Materials & Components 2.2 Gas Pipe Sizing & Demand 2.3 Underground Gas Installation

3 CSST, Regulators, Testing & Purging

3.1 CSST Installation 3.2 Gas Piping Regulators 3.3 Inspection, Testing & Purging

4 Combustion Air, Appliances & Large Equipment

4.1 Combustion Air 4.2 Specific Equipment, Testing & Adjustment 4.3 Gas Equipment over 400,000 BTU

5 Appliance Venting Categories, Draft & Chimneys

5.1 Positive vs Non-Positive Venting 5.2 Natural Draft Venting 5.3 Chimneys

6 Gas Vent Sizing & Part II Gas Practical

6.1 Gas Vent Sizing & Materials 6.2 Part II Practical Gas Piping 6.3 Part II Practical Gas Venting

7 Traps, Cleanouts & Joints

7.1 Trap Design, Seals & Prohibited Traps 7.2 Cleanout Locations, Sizing & Clearances 7.3 Joints, Connections & Prohibited Practices

8 Fixtures, Valves & Water Heaters

8.1 Fixtures, Equipment & Clearances 8.2 Piping, Valves & Controls 8.3 Water Heaters, T&P & M.G.L. c. 142

9 Water Supply, Backflow & Temperatures

9.1 Water Supply Materials, WSFU & Sizing 9.2 Backflow Prevention & Cross-Connection 9.3 Water Temperatures, Scald Control & Thermal Expansion

10 Hangers, DWV Materials & Storm Drainage

10.1 Hangers, Anchors & Pipe Protection 10.2 DWV Piping Materials 10.3 Storm Drainage

11 Sanitary Drainage Sizing

11.1 DFU Values & Load Calculations 11.2 Building Drains & Building Sewers 11.3 Horizontal Branches, Stacks & Offsets

12 Indirect Waste, Special Waste & Plumbing Vent Principles

12.1 Indirect Waste 12.2 Special Waste 12.3 Plumbing Vent Sizing Principles

13 Plumbing Vent Types & Terminations

13.1 Individual, Common & Dual Vents 13.2 Wet, Circuit, Loop & Stack Venting 13.3 Vent Terminations & Special Venting

14 Interceptors, Separators & Holding Tanks

14.1 Grease Interceptors 14.2 Holding Tanks 14.3 Gasoline, Oil & Sand Separators

15 Part II Trade Calculations

15.1 Head, Pressure & Volume 15.2 Pipe Offsets 15.3 Slope, Fall & Grade

16 Part II Isometric Analysis

16.1 Isometric Symbols & Reading Order 16.2 DWV Isometric Takeoff 16.3 Fixture, Vent & Gas Isometric Plan Analysis

11.1 DFU Values & Load Calculations

Key Takeaways Explain This Topic AI

248 CMR 10.15 Table 1 (12/8/2023) assigns drainage fixture units: tank-type toilet 4, valve-operated toilet 6, lavatory with 1-1/4 inch outlet 1, residential kitchen sink 2, residential shower stall 2, bathtub or tub-and-shower unit 2.

Massachusetts sizes sanitary piping from those Table 1 values plus 10.15(2)(b), not from International Plumbing Code fixture-unit tables or a printed bathroom-group shortcut.

Continuous or semi-continuous flow from a waste pump, sewage ejector, or similar sewage-discharging device is 2 DFU per gallon per minute, except ejector pumps installed to 10.15(9) Table 5 with a maximum of 20 GPM.

Unlisted fixtures take the Table 1 size-row values: 1-1/4 inch or less = 1 DFU, 1-1/2 inches = 2, 2 inches = 3, 2-1/2 inches = 4, 3 inches = 5, 4 inches = 6.

Add every fixture that will actually discharge, including future rough-ins required by 10.15(5), before you open Table 2 or Table 3.

Last updated: September 2026

11.1 DFU Values & Load Calculations

Quick Answer: Compute Massachusetts sanitary load from 248 CMR 10.15 Table 1 (effective 12/8/2023 ). A tank-type toilet is 4 DFU . A valve-operated toilet is 6 DFU . A lavatory with a 1-1/4 inch outlet is 1 . A residential kitchen sink (with or without disposer) is 2 . A residential shower stall is 2 . A bathtub or tub-and-shower unit is 2 . Add every fixture, then add 2 DFU per gpm for a sewage pump unless the pump is a 10.15(9) Table 5 ejector at a maximum of 20 GPM . Do not import IPC fixture-unit tables onto this closed-book exam.

The PSI Candidate Information Bulletin dated October 3, 2025 lists Drain, Waste & Vent — Sanitary inside the plumbing written cluster. This section is the load half of that sanitary work: how many drainage fixture units sit on the pipe before you pick a diameter. Independent ExamFinch teaching follows 248 CMR 10.15 as posted on Cornell LII and the Mass.gov 12/8/2023 Uniform State Plumbing Code PDF. It is not a Board publication and it does not claim official approval.

248 CMR 10.03 defines a fixture unit as one cubic foot of water drained in a 1-1/4 inch pipe over one minute, and one cubic foot as 7.5 gallons . That definition explains the unit. It does not let you invent loads. 248 CMR 10.15(2)(a) says waste-discharge calculations are computed in drainage fixture units from Table 1: Fixture Unit Values for Various Plumbing Fixtures and from 10.15(2)(b) . 10.15(3) then sends those totals to Tables 1, 2, and 3 for pipe size. Chapter 11.2 and 11.3 pick the pipe. This section gets the number right.

Table 1 is Massachusetts, not an IPC appendix

Open Cornell 248 CMR 10.15 and the UpCodes fixture-unit table and copy the printed values. Do not “remember IPC Chapter 7” and hope the numbers match. Massachusetts does not print a single bathroom-group DFU row in Table 1. Add the water closet, the lavatory, and the tub or shower as separate lines. A tank closet is 4 in both many IPC private rows and in Table 1; a flush-valve closet is 6 in Table 1 with no private-versus-public split . A residential dishwasher is 1 DFU , not a second kitchen-sink 2. A residential laundry connection is 3 DFU .

248 CMR 10.15 Table 1 — Fixture Unit Values for Various Plumbing Fixtures (12/8/2023):

  • Type of fixture or group of fixtures Fixture unit value
  • Bathtub or tub & shower unit 2
  • Bidet 2
  • Dental chair unit or cuspidor 1
  • Dental lavatory 1
  • Drinking fountain / water station 1
  • Dishwasher, commercial 6
  • Dishwasher, residential 1
  • Floor/trench drain, 2-inch 4
  • Floor/trench drain, 3-inch 5
  • Floor/trench drain, 4-inch 6
  • Kitchen sink, residential (with or without disposer) 2
  • Lavatory with 1-1/4 inch outlet 1
  • Laundry connection, residential 3
  • Laundry / utility sink 2
  • Shower stall, residential 2
  • Showers (group) per head 2
  • Surgeon’s sink 3
  • Flushing-rim sink with valve 6
  • Service sink with trap standard 3
  • Service sink with P-trap 2
  • Commercial pot, scullery, etc. (each section) — see Note 1 4
  • Shampoo sink 2
  • Toilet, tank type 4
  • Toilet, valve operated 6
  • Urinal, pedestal, siphon-jet blowout 6
  • Urinal, wall lip 4
  • Urinal, waterless 1
  • Wash sink (circular or multiple), each 20 inches of usable length 1

Sizes for fixtures not listed above: 1-1/4 inch or less 1 ; 1-1/2 inches 2 ; 2 inches 3 ; 2-1/2 inches 4 ; 3 inches 5 ; 4 inches 6 .

Note 1 sends grease-interceptor sizing to 248 CMR 10.15(1)(b)2.d. / the 10.09 interceptor rules — do not substitute interceptor gallons for Table 1 DFU. Note 2 sends continuous flow to 10.15(2)(b) . Note 3 says floor-drain pipe size follows floor area under 248 CMR 10.10(10)(a) ; Table 1 still gives the DFU once that diameter is known.

A tub-and-shower unit is 2 , not 2 for the tub plus 2 for the head. A separate residential stall shower in the same dwelling is another 2 . Group showers are 2 per head . Count 20 inches of a circular or multiple wash sink as 1 DFU , the same 20-inch module 10.10 uses for fixture count.

Worked example 1 — Springfield one-family

Fixtures actually installed (no future bath):

  • Fixture Table 1 DFU
  • One tank-type toilet 4
  • One lavatory, 1-1/4 inch outlet 1
  • One bathtub with shower head (tub & shower unit) 2
  • One residential kitchen sink with disposer 2
  • One residential dishwasher 1
  • One residential laundry connection 3
  • House total 13

That 13 DFU is the sanitary load you take to Table 2 for the building drain and to Table 3 for a one- or two-interval stack. It is not an IPC “bathroom group of 5” plus a kitchen. If the owner also wants a separate stall shower , add 2 and the house becomes 15 DFU . If a second tank toilet is roughed for a future bath, 10.15(5) says those future drains count in the final size — add 4 , do not wait until the second bath is trimmed.

Kitchen-sink independence is a later fitting rule ( 10.15(8)(c) ): the residential kitchen branch is not less than 1-1/2 inches and the sink shall not waste into a horizontal drain smaller than 3 inches that already receives a flat-bottom fixture. That is pipe arrangement, not a second DFU number. The load for that sink remains 2 .

Worked example 2 — Worcester public restroom (flush valves)

  • Fixture Count DFU each Subtotal
  • Valve-operated toilets 4 6 24
  • Lavatories, 1-1/4 inch outlet 4 1 4
  • Wall-lip urinals 2 4 8
  • Branch total 36

36 DFU already exceeds the 3-inch horizontal branch cap of 34 DFU in Table 2 (and that 3-inch row is also not more than four water closets ). The branch is 4 inches (Table 2 horizontal-branch column 160 DFU ). If someone quotes “flushometer water closet = 4 DFU because it is a public IPC row,” the total becomes a fake 28 and a 3-inch branch looks legal. Table 1 says 6 . Use 6 .

A waterless urinal is 1 DFU , not 4. Do not “upgrade” it to a wall-lip value. Pedestal / siphon-jet / blowout urinals are 6 .

Continuous flow, ejectors, and unlisted outlets

248 CMR 10.15(2)(b): fixture-unit values for continuous or semi-continuous flow into a building sanitary drainage system from a waste pump, sewage ejector pump, or similar device that discharges sewage waste are computed on the basis of two fixture units for each gallon per minute of flow .

Exception: ejector pumps installed in compliance with 10.15(9) Table 5 with a maximum of 20 GPM . That exception is the ordinary single-family sewage ejector: 10.15(9)(b)1. requires a full-size discharge and a minimum 20 GPM pump when the sump receives toilets and other fixtures, and Table 5’s first row is 1 toilet → 20 GPM . Do not add 2 × 20 = 40 DFU on top of the fixtures when that Table 5 / 20 GPM exception applies. A 75 GPM pump serving two or three toilets is not the 20 GPM exception; 2 × 75 = 150 DFU hits the gravity drain that receives the force main unless a Massachusetts PE designs a different 10.15(9) installation.

Scenario. A basement fixture pump rated 12 GPM discharges sewage to the overhead building drain and is not a Table 5 20 GPM ejector. Add 24 DFU to whatever gravity load already sits on that drain. That 24 can be larger than the two basement fixtures the pump serves. Size the receiving gravity pipe for the pump number, not for a “small bathroom.”

Unlisted fixtures: use the outlet-size rows at the bottom of Table 1, not a guess from IPC Table 709.1. A 2-inch custom receptor is 3 DFU . A 3-inch receptor is 5 DFU .

Load calculation is addition, then tables. Wrong Table 1 values make every downstream diameter wrong. 216 DFU on a 4-inch drain is a Table 2 slope question in the next section, not a Table 1 value.

  • Official resources
  • 248 CMR 10.15 Sanitary Drainage System (Cornell) — Table 1, 10.15(2)(b) continuous flow, Table 5 exception
  • Fixture Unit Values for Various Plumbing Fixtures (UpCodes) — HTML Table 1
  • 248 CMR 10.03 Definitions (Cornell) — fixture unit, 7.5 gallons
  • 248 CMR 10.00 Uniform State Plumbing Code (Mass.gov, effective 12/8/2023) — official PDF tables

Loading diagram... Massachusetts DFU load path (248 CMR 10.15)