Study guide
2.2 Ohms Law, Power Factor, and Three-Phase Review
Master Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Master Exam Orientation and Source Control
1.1 ICC R16, T16, G16, and Jurisdiction Variance 1.2 Current Format, Cost, Time, and Passing Score 1.3 Master License Scope vs. Exam Provider 1.4 Official References, Open-Book Rules, and Calculators 1.5 Domain Weights and Master-Level Study Map 1.6 Using the Practice Bank, Error Log, and Code Index
2 Chapter 2: Master-Level Electrical Theory, Plans, and Calculations
2.1 Plan Reading, Specifications, and Supervisory Review 2.2 Ohms Law, Power Factor, and Three-Phase Review 2.3 Fault Current, Available Fault Current, and Equipment Ratings 2.4 Demand Loads, Continuous Loads, and Calculation Setup 2.5 Voltage Drop and Design Judgment 2.6 Coordination, Selectivity, and Master-Level Decision-Making 2.7 Theory, Plans, and Calculation Case Lab
3 Chapter 3: Services, Service Equipment, and Main Distribution
3.1 Service Point, Service Conductors, and Utility Boundaries 3.2 Service Load Calculations and Demand-Factor Workflow 3.3 Service Disconnects, Overcurrent Protection, and Grouping 3.4 Service Equipment Ratings, Clearances, and Working Space 3.5 Transformers and Separately Derived System Decisions 3.6 Temporary Services and Construction Power 3.7 Services and Main Distribution Case Lab
4 Chapter 4: Grounding, Bonding, and Fault-Current Paths
4.1 Grounding vs. Bonding and Exam Language 4.2 Grounding Electrode Systems and Grounding Electrode Conductors 4.3 Main Bonding Jumpers, System Bonding, and Equipment Bonding 4.4 Separately Derived Systems Grounding and Bonding 4.5 Fault-Current Paths, Clearing Time, and Equipment Ratings 4.6 Special Bonding Patterns: Pools, Services, and Metal Systems 4.7 Grounding and Bonding Case Lab
5 Chapter 5: Feeders, Branch Circuits, and Conductor Engineering
5.1 Feeder vs. Branch Boundaries and Load Flow 5.2 Conductor Ampacity, Temperature Ratings, and Terminal Limits 5.3 Adjustment, Correction, and Neutral Counting 5.4 Overcurrent Protection, Tap Conductors, and Next-Size Rules 5.5 Required Outlets, GFCI/AFCI, and Occupancy Patterns 5.6 Multiwire Branch Circuits, Shared Neutrals, and Voltage Drop 5.7 Feeders, Branch Circuits, and Conductor Case Lab
6 Chapter 6: Wiring Methods, Raceways, Box Fill, and Installation Judgment
6.1 Raceway Selection and Installation Conditions 6.2 Raceway Fill, Conductor Protection, and Bending Limits 6.3 Boxes, Enclosures, and Conduit Bodies 6.4 Box Fill: Device Yokes, Equipment Grounds, and Clamps 6.5 Underground, Wet, Corrosive, and Physical-Damage Locations 6.6 Cabinets, Panelboards, Switchboards, and Working Clearance 6.7 Wiring Methods Installation Case Lab
7 Chapter 7: Equipment, Devices, Controls, and Utilization Equipment
7.1 Luminaires, Receptacles, Switches, and Device Placement 7.2 Appliances, Utilization Equipment, and Nameplate Data 7.3 Heating, Cooling, and HVAC Equipment Branch-Circuit Decisions 7.4 Disconnects, Switches, Controllers, and Control-Circuit Logic 7.5 Panelboards, Switchboards, Cabinets, and Equipment Labeling 7.6 Working Space, Accessibility, and Maintenance Judgment 7.7 Equipment, Devices, and Controls Case Lab
8 Chapter 8: Motors, Generators, Transformers, and Power Systems
8.1 Motor Loads, Full-Load Current, and Nameplate Boundaries 8.2 Motor Conductors, Overloads, and Short-Circuit/Ground-Fault Protection 8.3 Motor Controllers, Disconnects, and Group Installations 8.4 Generators, Transfer Equipment, and Optional Standby Systems 8.5 Emergency, Legally Required, and Critical Power Distinctions 8.6 Transformer Primary, Secondary, and Grounding Decisions 8.7 Motors, Generators, and Power Systems Case Lab
9 Chapter 9: Special Occupancies, Emergency Systems, and Safety
9.1 Hazardous Classified Locations and Boundary Thinking 9.2 Healthcare, Places of Assembly, and Commercial Special Rules 9.3 Pools, Spas, Marinas, and Corrosive/Wet Environments 9.4 RV Parks, Mobile Homes, Data Centers, and Special Equipment 9.5 Emergency Systems, Signaling, and Fire Alarm Interfaces 9.6 OSHA Electrical Safety, Lockout, and Field Risk Control 9.7 Special Occupancies and Safety Case Lab
10 Chapter 10: Master Electrician Integrated Code and Calculation Labs
10.1 Residential Service Upgrade Integrated Lab 10.2 Small Commercial Tenant Improvement Integrated Lab 10.3 Motor Shop and Industrial Equipment Integrated Lab 10.4 Mixed-Occupancy Special Condition Integrated Lab 10.5 Generator, Transfer, and Emergency Load Integrated Lab 10.6 Plan Review, Redline, and Supervisory Correction Lab 10.7 Five-Hour Open-Book Simulation Strategy
11 Chapter 11: Final Review, Test Day, Licensing, and Business Next Steps
11.1 Final 30-Day Master Electrician Review Plan 11.2 Reference Tab, Index, and Open-Book Speed Drills 11.3 Test-Day Checklist: Pearson VUE, PRONTO, and Retake Rules 11.4 After the Score: Jurisdiction Application and License Next Steps 11.5 Business, Supervision, Permit, and Compliance Readiness 11.6 Master Electrician Final Mixed Review
2.2 Ohms Law, Power Factor, and Three-Phase Review
Key Takeaways Explain This Topic AI
Ohms law and power formulas must be matched to the circuit type, load type, and phase relationship shown in the problem.
Power factor changes real power, apparent power, conductor current, transformer loading, and generator sizing decisions.
Three-phase calculations require the square-root-of-three relationship for line quantities, but not every problem is a three-phase problem.
Master-level review includes recognizing when nameplate data, code multipliers, or equipment articles replace simple theory formulas.
Last updated: May 2026
Theory as a calculation language
Electrical theory is the language behind many master-level code questions. The exam may not ask, What is Ohms law? It may give a motor load, a transformer, a long feeder, a nonunity power factor, or a three-phase panel schedule and expect you to select the right setup. The field expectation is similar. A master electrician must know whether a measured current is reasonable, whether a transformer is overloaded, whether a neutral is being misunderstood, and whether the voltage and phase listed on the plan match the equipment being installed.
Start with the basic relationships. Ohms law is E = I x R, I = E / R, and R = E / I. Power in a resistive direct-current or unity-power-factor single-phase situation can be written as P = E x I, P = I^2 x R, or P = E^2 / R. For alternating-current systems, the difference between real power, apparent power, and reactive power matters. Real power is watts or kilowatts. Apparent power is volt-amperes or kilovolt-amperes. Reactive power is vars or kilovars. Power factor is real power divided by apparent power.
Formula selection table
Situation Common formula Notes
Single-phase apparent power VA = V x I Use line voltage and line current for the single-phase load.
Single-phase real power W = V x I x PF Applies where power factor is stated or implied by equipment.
Three-phase apparent power VA = 1.732 x Vline x Iline Use line-to-line voltage and line current.
Three-phase real power W = 1.732 x Vline x Iline x PF Add power factor only when calculating real power from current.
Current from three-phase kVA I = kVA x 1000 / (1.732 x Vline) Do not multiply by power factor when kVA is already apparent power.
Current from three-phase kW I = kW x 1000 / (1.732 x Vline x PF) Include power factor because kW is real power.
A common exam trap is using power factor twice. If a transformer is rated 75 kVA, the rating is apparent power. Current on a 480 volt three-phase secondary is 75,000 / (1.732 x 480), or about 90 amps. Do not divide by power factor unless the problem gives kilowatts and asks for current. Another trap is forgetting the 1.732 factor. A 30 kVA three-phase load at 208 volts draws about 83 amps. The same apparent power on a single-phase 208 volt load would draw about 144 amps.
Phase, voltage, and neutral discipline
A master electrician should separate line-to-line, line-to-neutral, and phase winding quantities. In a 120/208 volt three-phase, 4-wire wye system, 208 volts is line-to-line and 120 volts is line-to-neutral. A three-phase load connected across all phases uses the 208 volt line-to-line value in the three-phase formula. A single-pole 120 volt load uses 120 volts in the single-phase formula. A 240/120 volt single-phase service is not a three-phase system just because it has two ungrounded conductors and a neutral.
Plan review often exposes voltage mistakes. A rooftop unit nameplate may require 208/230 volt single-phase or 460 volt three-phase. A panel schedule may show a two-pole breaker in a three-phase panel, but the load may still be single-phase. A sign transformer, welder, elevator controller, or kitchen appliance may carry nameplate data that directs branch-circuit sizing. The master-level habit is to read the nameplate basis before forcing the load into a generic formula.
Power factor and design judgment
Power factor affects conductor current and source loading. Low power factor means more apparent power is required for the same real power. A 50 kW three-phase load at 480 volts and 0.80 power factor draws about 75 amps: 50,000 / (1.732 x 480 x 0.80). At unity power factor it would draw about 60 amps. The real work is the same, but the current and apparent power are not.
That difference matters for transformers, generators, voltage drop, and utility metering. A generator must be evaluated for both kW and kVA capability. A transformer is normally rated in kVA, so loads with poor power factor can consume capacity even when the real power seems modest. Conductors are heated by current, not by the name of the load. Protective devices respond to current and time-current behavior, not simply to kW.
Code interaction
Theory formulas do not override code rules. Motor branch circuits, transformer secondaries, continuous loads, neutral calculations, appliance nameplate instructions, and special equipment can require article-specific sizing steps. The formula tells you a base current. The NEC article tells you whether to multiply, round, protect, derate, adjust, or select a standard ampere rating. On the exam, read whether the question asks for calculated load, conductor ampacity, overcurrent protection, transformer current, or voltage drop. Each answer may start with the same theory but end in a different code section.
A strong workflow is: list known values, identify phase, decide whether the value is W, kW, VA, or kVA, decide whether power factor applies, compute current or power, then apply the specific code rule requested. Write units on every step. Most wrong theory answers come from a correct formula used with the wrong unit, the wrong voltage, or the wrong load type.