Study guide
8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies
Key Takeaways Explain This Topic AI
IPC 2018 Table 608.1 approves the double check backflow prevention assembly (ASSE 1015, AWWA C510) for backpressure or backsiphonage in sizes 3/8 inch through 16 inches, but at low hazard only.
A reduced pressure principle assembly (ASSE 1013, AWWA C511) protects high or low hazard against both backpressure and backsiphonage using two checks plus a differential relief valve that dumps the zone when it rises to within about 2 psi of inlet pressure.
IPC 2018 Section 608.14.2 requires the RP relief opening to discharge by air gap and be prevented from being submerged, which is the code basis for never installing an RP in a pit or vault.
USC 10th-edition field test minimums are 2.0 psid for the RP relief valve opening point, 5.0 psid for RP check valve No. 1, and 1.0 psid for each check on a double check, PVB or SVB assembly.
IPC 2018 Section 312.10.2 requires reduced pressure principle, double check, pressure vacuum breaker, spill-resistant and fire-protection detector assemblies to be tested at installation, immediately after repairs or relocation, and at least annually.
Last updated: July 2026
8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies
Quick Answer: A double check valve assembly (ASSE 1015) stops backsiphonage and backpressure but is approved for low hazard only ; a reduced pressure principle assembly (ASSE 1013) stops both directions at high hazard , and its relief opening must discharge through an air gap and must never be submerged.
Reading the Scenario: Backsiphonage or Backpressure?
Exam questions rarely name the mechanism. You have to read it out of the fact pattern.
Backsiphonage is backflow produced by negative (sub-atmospheric) gauge pressure in the supply piping - the supply pulls. Look for a water main break, heavy fire-flow draft from a nearby hydrant, an undersized or partly closed service, a shutdown with the risers drained, or a pump taking suction directly on the service.
Backpressure is backflow produced by a downstream pressure higher than the supply - the downstream system pushes. Look for a booster or transfer pump, a pressurized boiler or hydronic loop, compressed air or carbon dioxide injection, thermal expansion in a closed system, or plain elevation.
Elevation is the one you can compute. A column of water exerts 0.433 psi per vertical foot .
Worked example. A chemical mixing tank sits on the fourth floor, 42 feet above the potable connection, and is charged by a transfer pump that adds 30 psi.
- Static head = 42 ft x 0.433 psi/ft = 18.2 psi
- Total potential backpressure = 18.2 + 30 = 48.2 psi
- Street pressure at the connection = 45 psi
Because 48.2 psi exceeds 45 psi, a backpressure condition exists. That single comparison disqualifies every vacuum breaker on the market, no matter how high it is mounted. This connection needs an air gap or a reduced pressure principle assembly.
Degree of Hazard: Pollutant vs Contaminant
IPC 2018 Table 608.1 sorts every device by degree of hazard , and footnote a of that table sends you to the Chapter 2 definitions:
Pollution (low hazard, pollutant) - an impairment of the quality of the potable water that does not create a hazard to public health, but adversely and unreasonably affects the aesthetic qualities of the water for domestic use: taste, odor, color. Examples include food-grade dye, a plain fire sprinkler system with no additives, a heat exchanger using an essentially nontoxic transfer fluid, and a plain boiler make-up line.
Contamination (high hazard, contaminant) - an impairment that creates an actual hazard to public health through poisoning or through the spread of disease by sewage, industrial fluids or waste. Examples include boiler treatment chemicals, pesticide or fertilizer injection, mortuary and autopsy equipment, dental vacuum, car wash detergents, photo-processing chemicals and any sewage connection.
One rule follows from this and is worth memorizing whole: a low-hazard device may never be substituted for a high-hazard one, but a high-hazard assembly is always acceptable on a low-hazard connection. Upgrading is legal; downgrading is a violation.