9.3 Approved Gas Piping Materials, CSST & Bonding
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
9.3 Approved Gas Piping Materials, CSST & Bonding
Key Takeaways Explain This Topic AI
IFGC 2018 Section 310.2.2 requires the CSST bonding jumper to be not smaller than 6 AWG copper, and Section 310.2.3 limits its length to 75 feet.
Copper and copper alloy pipe and tubing are prohibited where the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (IFGC 403.4.3 and 403.5.3).
IFGC 404.17.1 restricts polyethylene gas pipe to outdoors underground only, at not more than 100 psig for natural gas and 30 psig for LP-gas.
A yellow insulated copper tracer wire of not less than 18 AWG, rated for direct burial, must be installed adjacent to underground nonmetallic gas piping (IFGC 404.17.3).
Cast-iron pipe is prohibited for fuel gas and steel, stainless steel and wrought-iron pipe must be not lighter than Schedule 10 (IFGC 403.4.1 and 403.4.2).
Last updated: July 2026
9.3 Approved Gas Piping Materials, CSST & Bonding
Quick Answer: A gas piping system containing any segment of non-arc-resistant (yellow) CSST must be bonded to the electrical service grounding electrode system with a jumper not smaller than 6 AWG copper and not longer than 75 feet , clamped to a rigid pipe, pipe fitting or CSST fitting — never to the corrugated tubing itself (IFGC 2018 Sections 310.2 through 310.2.5).
Chapter 4 of the IFGC 2018 answers two questions on almost every materials item: is this material approved at all , and is it approved in this location . Master the second half — aluminum indoors but never outdoors, plastic outdoors but never indoors, copper only in low-sulfur gas.
Approved Metallic Pipe (IFGC 403.4)
Cast-iron pipe is prohibited outright (403.4.1). No exceptions, no locations.
Steel, stainless steel and wrought-iron pipe must be not lighter than Schedule 10 , meet ASME B36.10M dimensional standards, and comply with ASTM A53/A53M, ASTM A106 or ASTM A312 (403.4.2). Black iron in Schedule 40 is the workhorse. Note the joint consequence in 403.10.1: Schedule 40 and heavier pipe may be threaded, flanged, brazed, welded or press-connected, but pipe lighter than Schedule 40 may only be press-connected, flanged, brazed or welded — you may not cut threads into it.
Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (scf) of gas, equal to 0.7 mg per 100 liters (403.4.3). Hydrogen sulfide (H₂S) attacks copper and forms flakes of copper sulfide that plug orifices and jam gas valves. Threaded copper, copper-alloy and aluminum-alloy pipe may never be used with gases corrosive to those materials.
Aluminum-alloy pipe must comply with ASTM B241 ( alloy 5456 is prohibited ), must be marked at each end of each length, must be coated where it contacts masonry, plaster or insulation, and may not be used in exterior locations or underground (403.4.4).
Approved Metallic Tubing (IFGC 403.5)
Tubing may never be used with gases corrosive to the tubing material. Steel tubing follows ASTM A254 and stainless tubing ASTM A268 or A269. Copper tubing must be Type K or Type L of ASTM B88 or ASTM B280 and carries the same 0.3-grains-per-100-scf hydrogen sulfide restriction (403.5.3). Aluminum-alloy tubing (403.5.4) is barred from exterior and underground locations just like the pipe. Corrugated stainless steel tubing (CSST) must be listed in accordance with ANSI LC 1/CSA 6.26 (403.5.5).
Plastic Pipe: Outdoors, Underground, Nowhere Else
Polyethylene (PE) pipe, tubing and fittings must conform to ASTM D2513 and be marked "Gas" and "ASTM D2513"; polyamide must conform to ASTM F2945 (403.6). PVC and CPVC are flatly prohibited for supplying fuel gas. The only PVC the code recognizes is ANSI/UL 651 pipe carrying a regulator vent to a remote termination, and even that shall not be installed indoors (403.6.3).
Section 404.17.1 controls installation: plastic pipe shall be installed outdoors underground only , shall not be used within or under any building or slab , and shall not operate above 100 psig for natural gas or 30 psig for LP-gas . Three exceptions matter:
It may terminate above ground outside a building in a premanufactured anodeless riser or service-head-adapter riser — a factory-made casing that carries the PE up out of the trench with no sacrificial anode required.
It may terminate with a wall head adapter inside a building where the PE is inserted into an approved indoor piping material.
It may run under an outdoor patio, walkway or driveway slab at the burial depth of 404.12.
Underground PE also needs a tracer : 404.17.3 requires a yellow insulated copper tracer wire not smaller than 18 AWG , insulated for direct burial, run adjacent to the nonmetallic pipe, with access provided or the wire terminating above ground at each end. Minimum burial is 12 inches (404.12), reduced to 8 inches for individual lines to outdoor lights, grills and similar appliances where approved and not subject to damage. Metallic-to-plastic connections made outdoors and underground require transition fittings conforming to ASTM D2513 Category I or ASTM F1973 (404.17.2). And 404.11.1 is a favorite one-liner: galvanizing is not adequate corrosion protection for underground gas piping.
Approved Materials and Where They May Be Used
- Material IFGC 2018 section Permitted locations Key limitation
- Cast iron 403.4.1 None Prohibited for fuel gas
Steel / stainless / wrought-iron pipe 403.4.2 Above ground, concealed, underground with corrosion protection Not lighter than Schedule 10; threads only on Sch. 40 and heavier
Copper and copper alloy pipe and tubing 403.4.3, 403.5.3 Above ground, exposed or concealed Prohibited if gas exceeds 0.3 grains H₂S per 100 scf; tubing must be Type K or L
Aluminum-alloy pipe and tubing 403.4.4, 403.5.4 Interior only; coated at masonry, plaster or insulation Never exterior or underground; alloy 5456 prohibited
CSST 403.5.5, 404.2 Concealed and exposed per its listing Listed to ANSI LC 1/CSA 6.26; sized and installed per manufacturer's instructions; bonded per 310.2
Polyethylene (PE) 403.6, 404.17 Outdoors underground only ≤ 100 psig natural gas, ≤ 30 psig LP; anodeless riser to come above grade; 18 AWG tracer wire