9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods

Maryland Journeyman Plumber Journey Plumber/Gas Fitter

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Maryland Licensing, Code Administration & the Exam

1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy

2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926

2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work

3 Chapter 3: Materials, Uses & Specifications

3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections

4 Chapter 4: Sanitary Drainage & Waste Piping

4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors

5 Chapter 5: Venting Systems

5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting

6 Chapter 6: Traps, Interceptors & Backwater Valves

6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators

7 Chapter 7: Water Supply & Distribution Systems

7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection

8 Chapter 8: Backflow Prevention & Cross-Connection Control

8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting

9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing

9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules

10 Chapter 10: Gas Piping Installation, Testing & Purging

10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response

11 Chapter 11: Gas Appliance Venting & Combustion Air

11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing

12 Chapter 12: Gas Appliance Installation & Service

12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety

13 Chapter 13: Plumbing Fixtures, Fittings & Appliances

13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements

14 Chapter 14: Plumbing Mathematics

14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions

9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods

Key Takeaways Explain This Topic AI

IFGC 2018 Section 402.4.1 sizes every section of a system from one table row: the developed length from the point of delivery to the most remote outlet, rounded up to the next tabulated length.

Natural gas is sized at 1,000 Btu/ft3, so a 100,000 Btu/h furnace demands 100 cfh; undiluted propane at 2,500 Btu/ft3 reduces that same furnace to 40 cfh of vapor.

IFGC Tables 402.4(1) through 402.4(24) list capacity in cubic feet per hour, while the undiluted propane Tables 402.4(25) through 402.4(37) list capacity in thousands of Btu per hour.

In IFGC Table 402.4(2) at the 100-foot row, Schedule 40 pipe carries 50 cfh at 1/2 inch, 104 cfh at 3/4 inch, 195 cfh at 1 inch and 400 cfh at 1-1/4 inch.

IFGC 402.2 requires sizing on the total connected load with all appliances at full capacity simultaneously; diversified loads may be used only where a diversity of load can be established.

Last updated: July 2026

9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods

Quick Answer: Under International Fuel Gas Code (IFGC) 2018 Section 402.4.1, the longest length method sizes every section of a gas piping system from a single table row - the developed length from the point of delivery to the most remote outlet, rounded up to the next tabulated length - and each section is then sized for its own load by picking the first pipe size whose tabulated capacity equals or exceeds that load.

Gas Appliances and Piping is 40 of the 100 scored questions on the Maryland Journey Plumber/Gas Fitter examination, and pipe sizing is the most arithmetic-heavy skill inside it. The exam is open book, so you are not memorizing capacities - you are being tested on whether you can find the right table and walk the right row under time pressure.

Step 1 - Convert input ratings to the units the table uses

Every appliance carries a nameplate input rating in British thermal units per hour (Btu/h). Divide that by the heating value of the gas to get a volumetric demand:

Demand (cubic feet per hour, cfh) = Input (Btu/h) / Heating value (Btu/ft3)

Natural gas is taken as 1,000 Btu/ft3 , so 1 cfh = 1,000 Btu/h. Undiluted propane is about 2,500 Btu/ft3 (2,516 Btu/ft3 at 60 degrees F).

  • Appliance Nameplate input Arithmetic Demand
  • Warm-air furnace 100,000 Btu/h 100,000 / 1,000 100 cfh
  • Storage water heater 40,000 Btu/h 40,000 / 1,000 40 cfh
  • Free-standing range 65,000 Btu/h 65,000 / 1,000 65 cfh
  • Clothes dryer 35,000 Btu/h 35,000 / 1,000 35 cfh
  • Total connected load 240,000 Btu/h 240,000 / 1,000 240 cfh

Where the appliances are not yet selected, IFGC Table 402.2 gives approximate inputs for typical appliances: 100,000 Btu/h for a single-family furnace or hydronic boiler, 50,000 Btu/h for a 50-gallon storage water heater, 65,000 Btu/h for a domestic range, 35,000 Btu/h for a clothes dryer, 80,000 Btu/h for a gas log, 2,500 Btu/h for a gas light. A nameplate always overrides the table, and the design must be re-verified once actual equipment is known.

Step 2 - Size for the total connected load, not a diversified load

IFGC 402.2 is blunt: the total connected hourly load is the basis for pipe sizing, assuming all appliances could operate at full capacity simultaneously . Diversity is the narrow exception - diversified loads may be used only where a diversity of load can be established . A gas system is therefore sized very differently from an electrical service, where demand factors are routine. Section 402.2 also requires the flow rate to be adjusted for altitude above 2,000 feet , which in Maryland reaches only parts of Garrett County.

The meter and the utility service regulator are supplied and sized by the serving gas utility; your job is to hand the utility a correct total connected load in cfh. IFGC 409.2 requires a shutoff valve on the supply side of every meter.

Step 3 - Identify the correct table before you read a single number

IFGC 402.3 allows three sizing routes: the code's tables and equations (402.4 and 402.5), the sizing tables in a listed piping system manufacturer's instructions, or other approved engineering methods. Tables 402.4(1) through 402.4(37) are keyed by four header lines, and misreading those headers is the most common sizing error on the exam:

Gas - natural, or undiluted propane

Inlet pressure - "less than 2 psi," 2.0 psi, 5.0 psi, or 11.0 in. w.c.

  • Pressure drop - 0.3 in. w.c., 0.5 in. w.c., 1.0 psi, 3.0 psi, or 3.5 psi
  • Specific gravity - 0.60 for natural gas, 1.50 for undiluted propane
  • Table Material Gas Inlet Drop Capacity units
  • 402.4(1) Schedule 40 metallic Natural < 2 psi 0.3 in. w.c. cfh
  • 402.4(2) Schedule 40 metallic Natural < 2 psi 0.5 in. w.c. cfh
  • 402.4(5) Schedule 40 metallic Natural 2.0 psi 1.0 psi cfh
  • 402.4(15) CSST Natural < 2 psi 0.5 in. w.c. cfh
  • 402.4(28) Schedule 40 metallic Propane 11.0 in. w.c. 0.5 in. w.c. 1,000 Btu/h

Burn this in: Tables 402.4(1) through 402.4(24) are read in cubic feet per hour; Tables 402.4(25) through 402.4(37) - the undiluted propane tables - are read in thousands of Btu per hour (IFGC Appendix A, Section A.3.1). Appendix A Table A.2.4 supplies specific-gravity multipliers when the delivered gas is not 0.60: a 0.50 gravity gas multiplies capacities by 1.10, a 1.50 gravity gas by 0.63.

The workhorse table for Maryland residential natural gas is Table 402.4(2) - Schedule 40 metallic pipe, natural gas, inlet less than 2 psi, 0.5 in. w.c. drop, 0.60 specific gravity, capacity in cfh:

Length (ft) 1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in.

  • 20 118 247 466 957 1,430 2,760
  • 40 81 170 320 657 985 1,900
  • 60 65 137 257 528 791 1,520
  • 80 56 117 220 452 677 1,300
  • 100 50 104 195 400 600 1,160
  • 125 44 92 173 355 532 1,020
  • 150 40 83 157 322 482 928
  • Step 4 - Measure the length and account for fittings

Measure the developed pipe length, then add an equivalent length allowance for fittings. IFGC Appendix A directs that an allowance from Table A.2.2 (Equivalent Lengths of Pipe Fittings and Valves) be considered for any run containing four or more fittings , and warns that only four elbows or tees can push a run into the next longer table row with a significant loss of capacity. ICC guidance offers a widely used shortcut: multiply the actual pipe length by 1.50 as an all-inclusive fitting allowance.

CSST is handled differently. Table 402.4(15) already includes losses for four 90-degree bends and two end fittings ; extra bends or fittings add L = 1.3n feet of equivalent tubing, where n is the number of additional fittings or bends.

Two rounding rules govern every lookup, and they run in the same direction:

Length rounds UP to the next tabulated row. An 88-foot developed length uses the 90-foot row.

Capacity rounds UP to the next larger figure in that row. Never select a pipe whose tabulated capacity is below the section load.

Step 5 - The three length methods (IFGC 402.4.1, 402.4.2, 402.4.3)

Longest length method (402.4.1) - the size of each section is determined using the longest length of piping from the point of delivery to the most remote outlet, together with the load of that section. One length, one row, whole system. Most conservative, and the default assumption on exam questions.

Branch length method (402.4.2) - sections on the longest run are still sized from the longest-run row, but each remaining branch is sized from the length measured from the point of delivery to the most remote outlet in that branch . Less conservative, which is why Appendix A stresses fitting allowances here.

Hybrid pressure method (402.4.3) - for 2 psi systems. Higher-pressure piping is sized from the longest length to the most remote line pressure regulator ; piping downstream of that regulator is sized from the regulator to the most remote outlet it serves.

Worked example - longest length method

A Maryland single-family home is served with natural gas at 0.5 psi or less through Schedule 40 steel pipe. Connected appliances: a 100,000 Btu/h furnace, a 40,000 Btu/h water heater, a 65,000 Btu/h range, and a 35,000 Btu/h dryer.

  • Section Serves Section load Measured length
  • A all four appliances 240 cfh 20 ft (meter to tee 1)
  • B range 65 cfh 12 ft off tee 1
  • C furnace + water heater + dryer 175 cfh 18 ft (tee 1 to tee 2)
  • D dryer 35 cfh 10 ft off tee 2
  • E furnace + water heater 140 cfh 14 ft (tee 2 to tee 3)
  • F water heater 40 cfh 8 ft off tee 3
  • G furnace 100 cfh 12 ft off tee 3

Longest run = A + C + E + G = 20 + 18 + 14 + 12 = 64 ft . Apply the all-inclusive fitting allowance: 64 x 1.50 = 96 ft . Round up to the next tabulated length: the 100-foot row of Table 402.4(2) sizes the entire system.

The 100-foot row reads 50 / 104 / 195 / 400 / 600 / 1,160. Walk it once per section:

Section Load First tabulated capacity at or above the load Size

A 240 cfh 400 cfh 1-1/4 in.

B 65 cfh 104 cfh 3/4 in.

C 175 cfh 195 cfh 1 in.

D 35 cfh 50 cfh 1/2 in.

E 140 cfh 195 cfh 1 in.

F 40 cfh 50 cfh 1/2 in.

G 100 cfh 104 cfh 3/4 in.

Section A fails at 1 inch because 195 cfh is less than the 240 cfh it must carry, so the next column - 1-1/4 inch at 400 cfh - is the answer. Section G passes at 3/4 inch by only 4 cfh, which is exactly why the fitting allowance matters.

The same job by the branch length method

Sections A, C, E and G lie on the longest run and do not change. Branch B, the range, is only 20 + 12 = 32 ft from the meter; 32 x 1.50 = 48 ft rounds up to the 50-foot row , where 1/2-inch pipe carries 72 cfh. Because 72 exceeds the 65 cfh range load, that branch drops from 3/4 inch to 1/2 inch . Branch D (48 x 1.50 = 72 ft, 80-foot row, 56 cfh) and branch F (60 x 1.50 = 90 ft, 90-foot row, 52 cfh) both stay at 1/2 inch.