Study guide
9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
Key Takeaways Explain This Topic AI
Maryland adopts NFPA 58 by reference at COMAR 09.20.01, and the State Board of Plumbing issues a separate Propane Gas Fitter Certificate valid statewide, including Baltimore County and WSSC, for a $25.00 initial application fee plus a $31.50 license fee.
Propane vapor has a specific gravity of 1.52 (1.50 in the IFGC tables), carries about 2,516 Btu/ft3 at 60 degrees F, and has a flammable range of 2.15 to 9.6 percent in air.
ASME propane tanks are filled by volume to about 80 percent of water capacity, so a 500-gallon tank holds roughly 400 gallons of propane; DOT cylinders are filled by weight to a 42 percent filling density.
NFPA 58 defines a first-stage regulator as reducing container pressure to 10 psig or less, and a second-stage regulator as delivering the pressure required at the point of delivery, normally 11 in. w.c.
NFPA 58 requires a regulator vent discharge at least 3 feet horizontally from any building opening below it and at least 5 feet in any direction from ignition sources, direct-vent openings and mechanical air intakes.
Last updated: July 2026
9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
Quick Answer: Maryland adopts NFPA 58, Liquefied Petroleum Gas Code , by reference at COMAR 09.20.01 , and IFGC 2018 Section 401.2 sends every liquefied petroleum gas (LP-gas) storage system to NFPA 58 and the International Fire Code. Propane vapor is about 1.52 times heavier than air , carries roughly 2,500 Btu/ft3 , is delivered to appliances at 11 in. w.c. , and containers are filled to a maximum of about 80 percent of their water capacity.
Why Maryland treats propane as its own credential
The Maryland State Board of Plumbing issues three overlapping gas credentials, and the exam expects you to know which one reaches where:
Credential Covers Where it is valid
Journey or Master Plumber/Gas Fitter Plumbing and gas fitting Statewide except Baltimore County and the WSSC service area (Montgomery and Prince George's Counties), which license and code separately
Natural Gas Fitter (apprentice, journey, master) Natural gas work by non-plumbers Same two exclusions
Propane Gas Fitter Certificate Propane gas services by non-plumbers The entire state , including Baltimore County and WSSC
The propane certificate is credential-based rather than examination-based. An applicant qualifies by holding a current National Propane Gas Association certified training completion for Distribution Systems Operations - documented in Basic Principles and Practices, Vapor Distribution, and Vapor Distribution System Installation - or a county or municipal gas fitter's license issued under a program in existence before July 1, 1995 , or equivalent qualifications accepted by the Board. The applicant must also carry $300,000 general liability and $100,000 property damage insurance. The Board's published fee schedule (Forms and Fees, updated 1 July 2025) sets the Propane Gas Fitter Certificate at a $25.00 initial application fee plus a $31.50 license fee .
The physical properties that drive every propane rule
- Property Value
- Vapor specific gravity (air = 1.0) 1.52 (IFGC sizing tables use 1.50)
- Heating value, vapor 2,516 Btu/ft3 at 60 degrees F (2,500 nominal)
- Heating value, liquid 91,547 Btu/gal ; 21,591 Btu/lb
- Weight of liquid 4.24 lb/gal at 60 degrees F
- Specific gravity of liquid 0.51 - lighter than water
- Boiling point -44 degrees F
- Flammable limits in air 2.15% to 9.6%
- Ignition temperature in air 920 to 1,020 degrees F
Two of these numbers generate most of the code. Propane vapor sinks , and its flammable range begins at only 2.15 percent, so a leak that natural gas would carry harmlessly upward instead pools in a crawl space, window well or stair pit and reaches an ignitable concentration with very little gas.
Containers: DOT cylinders versus ASME tanks
DOT cylinders are built, tested and stamped to U.S. Department of Transportation specifications in 49 CFR - the portable containers such as the 20-lb grill bottle, 100-lb stationary cylinders and forklift cylinders. ASME containers are built to the ASME Boiler and Pressure Vessel Code, Section VIII, and are the permanently installed 120, 250, 500 and 1,000 gallon tanks. NFPA 58 Section 5.2.1.1 requires containers to be designed, fabricated, tested and marked to DOT, FAA or ASME rules. Stationary DOT cylinders must be installed aboveground only, on a firm foundation of concrete, masonry or metal, secured against displacement and not in contact with soil.
Water capacity is not propane capacity
Water capacity is defined by NFPA 58 Section 3.3.90 as the amount of water at 60 degrees F required to fill a container. Every container is rated that way, and its usable propane content is always less:
ASME tanks are filled by volume to a maximum permitted filling limit of roughly 80 percent . A "500-gallon" tank is 500 gallons of water capacity and holds about 400 gallons of propane - approximately 400 x 91,547 = 36.6 million Btu , or about 152 hours of run time for the 240,000 Btu/h house sized in Section 9.4.
DOT cylinders are filled by weight to a filling density , defined in OSHA 29 CFR 1910.110(b)(12) as the percent ratio of the weight of the gas in a container to the weight of water the container will hold at 60 degrees F. For commercial propane at 0.504 to 0.510 specific gravity in an aboveground container of 1,200 gallons or less, that maximum is 42 percent . A 20-lb grill cylinder carries a stamped water capacity ("WC") near 47.6 lb, and 47.6 x 0.42 = 20 lb of propane.
Why the outage exists
That 20 percent vapor space - the outage - is not slack. Liquid propane has a far higher coefficient of thermal expansion than water, so a container filled liquid-full on a cold morning becomes hydraulically full as the day warms. With no vapor space left to compress, it relieves pressure by lifting its relief valve and discharging liquid , which flashes to roughly 270 times its volume of heavier-than-air flammable vapor at ground level.
Container appurtenances the exam names
- Appurtenance Function
- Service valve Main vapor (or liquid) withdrawal valve; the regulator connects here
Pressure relief valve Opens to prevent internal pressure rising above a set value; NFPA 58 Sections 6.7.2.4 and 6.7.2.5 require a rain cap that stays in place except during operation
Fixed maximum liquid level gauge The "outage gauge," "bleeder valve" or "spitter valve" - NFPA 58 Section 3.3.34.2 defines it as the fixed liquid level gauge indicating the level at the maximum permitted filling limit. This is the approved gauging device for filling
- Float (dial) gauge A convenience percentage indicator; not an approved gauging device for filling
- Filler valve The fill connection, fitted with a dust cap
- Excess-flow valve Closes when liquid or vapor passing through exceeds a prescribed flow rate
Overfilling prevention device (OPD) Float-actuated secondary shutoff required on DOT cylinders of 4 lb through 40 lb propane capacity in vapor service; identified by a triangular handwheel
NFPA 58 also requires every container inlet, outlet and valve other than pressure relief and gauging devices to be labeled vapor or liquid , and requires vapor-withdrawal containers to be equipped so liquid cannot be withdrawn accidentally. That is the practical line between vapor service - the regulator sees gas boiled off the top of the tank at a vaporization rate set by wetted surface area and ambient temperature, which is why an undersized tank frosts over and starves appliances in January - and liquid service , where a dip tube draws liquid for forklifts, motor fuel and vaporizers.