12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
Key Takeaways Explain This Topic AI
The IFGC 2018 Appendix D procedure (informational, not a code requirement) checks for spillage at the draft hood relief opening after 5 minutes of main burner operation, using smoke.
Air-free CO equals measured CO multiplied by 20.9 divided by (20.9 minus percent O2), so 100 ppm at 9 percent oxygen is 176 ppm air-free.
ANSI Z21 and the National Fuel Gas Code annex set 400 ppm air-free for central furnaces and boilers but only 200 ppm air-free for water heaters and room heaters.
OSHA's carbon monoxide PEL is 50 ppm as an 8-hour TWA (29 CFR 1910.1000 Table Z-1); NIOSH sets the IDLH at 1,200 ppm.
Typical manifold pressure is about 3.5 in. w.c. for natural gas and 10 to 11 in. w.c. for propane, but the appliance rating plate governs.
Last updated: July 2026
12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
Quick Answer: The safety-inspection sequence in IFGC 2018 Appendix D requires you to confirm that the main burner is burning properly with no floating, lifting or flashback , adjust the primary air shutter as required, and then test for spillage at the draft hood relief opening after 5 minutes of main burner operation using smoke (D.5.2). The match-or-candle wording belongs to the 2000-2015 editions; the 2018 text says smoke.
Everything in this section is diagnostic: the appliance is already installed, and your job is to prove it burns cleanly, drafts properly and cannot poison the occupants. Two numbers anchor the topic -- 400 ppm air-free carbon monoxide (CO) , the ANSI Z21 ceiling for a central furnace's flue gas, and 50 ppm , the OSHA permissible exposure limit for the air a worker breathes over 8 hours. They are not the same measurement.
Reading the Flame
Primary air is the air pre-mixed with gas inside the burner venturi, metered by the air shutter . Secondary air is the air drawn in around the flame at the burner ports and inside the combustion chamber. A correctly adjusted natural gas burner shows a soft blue flame with a well-defined inner cone ; a propane burner shows the same blue flame, on which slight yellow tips are normal for many appliances. Set the air shutter to the smallest opening that produces a stable inner cone with no yellow tipping.
Flame symptom What it means First things to check
Yellow tipping -- soft, blurred, luminous flame Too little primary air; incomplete combustion, soot and CO Air shutter closed too far, lint or dust blocking the shutter, blocked burner ports, oversized orifice
Lifting -- flame blows off the port and floats above it Mixture velocity exceeds burning velocity: too much primary air or excessive manifold pressure Air shutter open too far, overfired gas valve, undersized or eroded ports
Flashback -- flame burns back inside the burner with a roar Burning velocity exceeds mixture velocity Too much primary air at low input, wrong fuel gas for the orifice, damaged or clogged ports
Floating flame -- lazy, rolling flame filling the chamber Insufficient secondary air or a blocked vent Blocked flue, closed combustion air openings, depressurized appliance zone
A floating flame is the most dangerous of the four, because the cause is starved secondary air or a plugged vent -- exactly the conditions that push combustion products back into the building.
Orifices, Conversions and Manifold Pressure
Natural gas carries about 1,000 Btu per cubic foot ; propane carries about 2,500 Btu per cubic foot . To deliver the same input, a propane appliance passes less than half the gas volume , which is why a propane orifice is drilled substantially smaller and why a conversion always means changing orifices and the appliance regulator spring or setting. IFGC 301.7.1 allows a fuel conversion only where complete instructions come from the installation instructions, the serving gas supplier or the manufacturer.
Manifold pressure is the pressure the burners see downstream of the appliance regulator inside the combination gas valve. It is read with a manometer at the gas valve outlet tap while the appliance fires. Typical settings are about 3.5 inches water column (in. w.c.) for natural gas and 10 to 11 in. w.c. for propane , but the rating plate is the authority -- two-stage equipment carries separate low-fire and high-fire figures. Because 1 psi equals 27.7 in. w.c., 3.5 in. w.c. is only 3.5 / 27.7 = 0.126 psi ; a psi gauge will never resolve it.
Worked Example -- Clocking the Meter to Confirm Input
Shut off every other gas appliance including standing pilots, fire the unit at high fire until steady, and time one revolution of a test dial:
cfh = (3,600 x dial size) / seconds per revolution
A furnace nameplated at 100,000 Btu/h turns the 1-cubic-foot hand once in 32 seconds on natural gas at 1,000 Btu/ft3:
- 3,600 / 32 = 112.5 cfh
- 112.5 x 1,000 = 112,500 Btu/h
112,500 / 100,000 = 1.125 , so the unit is 12.5 percent overfired -- reduce manifold pressure to the plate value and re-clock.
The same 100,000 Btu/h appliance on propane should draw only 100,000 / 2,500 = 40 cfh .