Study guide
10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection
Key Takeaways Explain This Topic AI
IFGC 2018 Section 402.7 caps the maximum operating pressure of piping inside buildings at 5 psig unless one of seven listed conditions is met, such as welded joints or a ventilated chase.
IFGC 2018 Section 416.1 requires overpressure protection devices where the serving gas supplier delivers gas at greater than 2 psi to piping serving appliances designed for 14 inches w.c. or less.
Each overpressure protection device must limit pressure at every connected appliance to 2 psi or less upon failure of the line pressure regulator (IFGC 416.2.1), using a relief valve, monitoring regulator, series regulator or manually reset automatic shutoff device.
Clocking a meter uses CFH = (3,600 x dial size) / seconds; a 2-cubic-foot dial turning once in 36 seconds equals 200 CFH, or 206,000 Btu/h on 1,030 Btu per cubic foot gas.
Natural gas is delivered to appliances at about 7 inches w.c. and propane at about 11 inches w.c.; one psi equals 27.7 inches of water column, so a 2 psi house line is 55.4 inches w.c.
Last updated: July 2026
10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection
Quick Answer: Inside a building, IFGC 2018 Section 402.7 caps the maximum operating pressure at 5 psig unless one of seven listed conditions is met, and Section 416.1 requires overpressure protection devices wherever the serving gas supplier delivers gas at greater than 2 psi to piping serving appliances designed for 14 inches w.c. or less .
Gas Appliances and Piping is 40 of the 100 scored items on the Maryland Journey Plumber/Gas Fitter exam. Metering and pressure control sit right at the boundary between what the utility owns and what you are licensed to install, and PSI writes questions on exactly that boundary.
The Gas Service: Where the Utility Stops and Your Work Starts
Gas travels from a distribution main in the street, through a service line , to a service pressure regulator — a regulator installed by the serving gas supplier to reduce and limit service-line pressure to delivery pressure. Downstream of that regulator sits the meter set : the meter, its shutoff valve, the riser and the connection to the customer's house line.
IFGC 2018 Section 401.1 fixes the code's reach precisely: it applies from the point of delivery to the connections with the appliances . NFPA 54 defines the point of delivery as the outlet of the service meter assembly; where no meter is installed, the outlet of the service regulator or service shutoff valve; and for undiluted LP-gas, the outlet of the final pressure regulator . Everything upstream belongs to the utility or the propane supplier and is governed by federal pipeline rules (49 CFR Part 192), not by the IFGC.
Three meter-related code rules are heavily tested:
IFGC 409.2 — Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter.
IFGC 401.6 — Interconnections. Where two or more meters are installed on the same premises but supply separate consumers , the piping systems shall not be interconnected on the outlet side of the meters.
IFGC 401.7 — Piping meter identification. Piping from multiple-meter installations shall be permanently marked by the installer so the system supplied by each meter is readily identifiable. Section 409.3.3 adds a matching tag on each house-line shutoff valve.
Diaphragm Meters and How to Read the Index
A residential gas meter is a positive-displacement diaphragm meter . Two synthetic-rubber diaphragm chambers alternately fill and empty; slide valves switch the flow between them, and a tangent-and-crank linkage converts that reciprocating motion into rotation of the index . Every revolution therefore represents a fixed, known volume — which is why a meter can be used as a field measuring instrument, not just a billing device.
The index is the set of dials or the odometer wheel that records total consumption. On a dial index, the hands are typically marked 1,000, 10,000, 100,000 and 1,000,000 cubic feet, and adjacent dials rotate in opposite directions . Read left to right, and when a hand sits between two numbers, record the lower number. The utility converts cubic feet to CCF (hundreds of cubic feet) or therms for billing.
Below the index are the small test dials (also called proving or drive dials), typically 1/2, 1 or 2 cubic feet per revolution on residential meters and 5, 10 or 100 cubic feet on commercial meters. These are the dials you use to clock an appliance.
Worked Example — Clocking an Appliance
Shut off every other gas appliance including standing pilots, run the appliance being tested at high fire, and time one full revolution of a test dial. CFH = (3,600 x dial size in cubic feet) / seconds per revolution
A furnace turns the 2-cubic-foot test dial once in 36 seconds on gas with a heating value of 1,030 Btu per cubic foot: CFH = (3,600 x 2) / 36 = 7,200 / 36 = 200 CFH
Input = 200 CFH x 1,030 Btu/ft3 = 206,000 Btu/h
Compare that to the nameplate input. If the plate reads 200,000 Btu/h, the appliance is 3 percent over — acceptable. If it reads 150,000 Btu/h, the burner is badly overfired and the orifice or manifold pressure is wrong.
Elevated-pressure correction. A meter measures actual cubic feet at meter pressure. On a 2 psi meter you must multiply by a pressure factor: Factor = (gauge pressure + atmospheric) / base pressure = (2 + 14.7) / 14.73 = 1.134
Corrected flow = 200 CFH x 1.134 = 227 CFH
Skipping that correction under-reads a 2 psi meter by roughly 13 percent . No correction is needed on an ordinary 7 in. w.c. meter.
Meter Location, Access and Protection
Meter siting comes mainly from NFPA 54 Section 5.7 , which Maryland adopts at COMAR 09.20.01, plus each utility's own construction standard.
Requirement Rule
Ventilation and access Meters shall be located in ventilated spaces , readily accessible for examination, reading, replacement and maintenance
Physical damage Shall not be placed where subject to damage — adjacent to a driveway, under a fire escape, or in public passages and halls
Corrosion and vibration Shall not be placed where subject to excessive corrosion or vibration
Temperature Shall not be located where subject to extreme temperatures or sudden extreme changes in temperature
Support Shall be supported or connected to rigid piping so no strain is placed on the meter
Ignition sources Since the 2009 edition the 3-foot clearance applies to the line pressure regulator vent , not to the meter body
Vehicle exposure Utilities require bollards or relocation where a meter set is exposed to vehicle traffic
Indoor meters are permitted where the utility allows them, but they must still meet the ventilation, access and damage rules above, and any regulator serving them must be vented in accordance with IFGC 410.3.