10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping

Maryland Journeyman Plumber Journey Plumber/Gas Fitter

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Maryland Licensing, Code Administration & the Exam

1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy

2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926

2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work

3 Chapter 3: Materials, Uses & Specifications

3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections

4 Chapter 4: Sanitary Drainage & Waste Piping

4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors

5 Chapter 5: Venting Systems

5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting

6 Chapter 6: Traps, Interceptors & Backwater Valves

6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators

7 Chapter 7: Water Supply & Distribution Systems

7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection

8 Chapter 8: Backflow Prevention & Cross-Connection Control

8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting

9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing

9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules

10 Chapter 10: Gas Piping Installation, Testing & Purging

10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response

11 Chapter 11: Gas Appliance Venting & Combustion Air

11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing

12 Chapter 12: Gas Appliance Installation & Service

12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety

13 Chapter 13: Plumbing Fixtures, Fittings & Appliances

13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements

14 Chapter 14: Plumbing Mathematics

14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions

10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping

Key Takeaways Explain This Topic AI

IFGC 2018 Table 415.1 spaces steel gas pipe supports at 6 feet for 1/2 inch, 8 feet for 3/4 and 1 inch, and 10 feet for 1-1/4 inch and larger horizontal runs.

Vertical gas piping 1-1/4 inch and larger is supported at every floor level, and CSST support spacing follows the manufacturer's instructions, not Table 415.1.

IFGC 2018 Section 404.7.1 requires No. 16 gage (0.0575 inch) steel shield plates extending not less than 4 inches to each side of a framing member where piping is less than 1-1/2 inches from the membrane face; black and galvanized steel piping are exempt.

Underground gas piping is buried not less than 12 inches below grade (IFGC 2018 404.12), except individual lines to outdoor lights and grills, which may be 8 inches (404.12.1).

IFGC 2018 Section 404.5 limits concealed fittings to threaded elbows, tees and couplings, brazed fittings, welded fittings, and fittings listed to ANSI LC-1/CSA 6.26 or ANSI LC-4/CSA 6.32.

Last updated: July 2026

10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping

Quick Answer: IFGC 2018 Table 415.1 sets gas pipe support spacing at 6 feet for 1/2-inch steel pipe, 8 feet for 3/4-inch and 1-inch steel pipe, and 10 feet for 1-1/4-inch and larger horizontal steel pipe . Vertical steel pipe 1-1/4 inch and larger is supported at every floor level , and CSST spacing comes from the manufacturer's instructions, not from the table.

Gas Appliances and Piping is 40 of the 100 scored questions on the Maryland Journey Plumber/Gas Fitter exam — the largest domain by a wide margin — and the installation rules in IFGC (International Fuel Gas Code) 2018 Chapter 4 are where most of those points live. This section covers Sections 404, 407 and 415: how gas piping is held up, where it may never go, and what the rules become once the pipe disappears behind drywall.

Support: Materials, Anchoring and Table 415.1

Section 407.2 lists exactly what may carry the weight: metal pipe hooks, metal pipe straps, metal bands, metal brackets, metal hangers or building structural components , suitable for the size of piping and of adequate strength and quality. Three clauses inside that one paragraph generate exam questions:

Supports must be located at intervals that prevent or damp out excessive vibration .

Piping must be anchored to prevent undue strains on connected appliances — and it shall not be supported by other piping . Strapping a new 1/2-inch gas branch to an existing 2-inch water line is a violation no matter how solid that water line feels.

Hangers and supports shall conform to MSS SP-58 , must not interfere with free expansion and contraction of the pipe between anchors, and must be designed so they cannot be disengaged by movement of the pipe they carry.

Spacing itself is set by Section 415.1 and Table 415.1.

Table 415.1 — Support of Piping (IFGC 2018)

Steel pipe, nominal size (in.) Spacing of supports (ft) Tubing, smooth-wall (in. O.D.) Spacing of supports (ft)

  • 1/2 6 1/2 4
  • 3/4 or 1 8 5/8 or 3/4 6
  • 1-1/4 or larger (horizontal) 10 7/8 or 1 (horizontal) 8
  • 1-1/4 or larger (vertical) Every floor level 1 or larger (vertical) Every floor level

Three notes decide most questions built on this table:

The tubing column is outside diameter (O.D.), not nominal size. Copper tube runs 1/8 inch larger on the outside than its nominal size, so 1/2-inch nominal copper tube is 5/8-inch O.D. and is supported every 6 feet , not the 4 feet printed on the "1/2" row. That 1/2-inch O.D. row describes 3/8-inch nominal tube.

Vertical piping is not a distance. For both steel and tubing, vertical runs are supported at every floor level regardless of size.

CSST (corrugated stainless steel tubing) is deliberately absent. Section 415.1 sends CSST support spacing to the CSST manufacturer's instructions , which are typically far more frequent than 10 feet.

Worked Support Examples

A 34-foot horizontal run of 1-1/4-inch black steel : Table 415.1 caps spacing at 10 feet. 34 ÷ 10 = 3.4, so three spaces will not work (34 ÷ 3 = 11.33 feet, over the limit). Round the number of spaces up to 4: 34 ÷ 4 = 8.5 feet between supports , which is 5 support points including both ends.

A 30-foot horizontal run of 3/4-inch steel : the cap is 8 feet. 30 ÷ 8 = 3.75 → round up to 4 spaces → 30 ÷ 4 = 7.5 feet apart , again 5 support points.

A 1-1/2-inch steel riser serving three floors : the 10-foot figure never applies. The riser is supported at each of the three floor levels . Always round the number of spaces up , never the spacing, or you will land above the table maximum.