Study guide

10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors

Maryland Journeyman Plumber Journey Plumber/Gas Fitter

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Maryland Licensing, Code Administration & the Exam

1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy

2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926

2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work

3 Chapter 3: Materials, Uses & Specifications

3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections

4 Chapter 4: Sanitary Drainage & Waste Piping

4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors

5 Chapter 5: Venting Systems

5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting

6 Chapter 6: Traps, Interceptors & Backwater Valves

6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators

7 Chapter 7: Water Supply & Distribution Systems

7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection

8 Chapter 8: Backflow Prevention & Cross-Connection Control

8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting

9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing

9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules

10 Chapter 10: Gas Piping Installation, Testing & Purging

10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response

11 Chapter 11: Gas Appliance Venting & Combustion Air

11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing

12 Chapter 12: Gas Appliance Installation & Service

12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety

13 Chapter 13: Plumbing Fixtures, Fittings & Appliances

13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements

14 Chapter 14: Plumbing Mathematics

14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions

10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors

Key Takeaways Explain This Topic AI

IFGC 2018 Section 409.5.1 places the appliance shutoff valve in the same room as the appliance, within 6 feet of it, and upstream of the union, connector or quick-disconnect device it serves.

An appliance shutoff valve installed at a manifold must be within 50 feet of the appliance served, readily accessible and permanently identified (IFGC 2018 409.5.3).

IFGC 2018 Section 411.1.3.1 caps appliance fuel connectors at 6 feet overall measured along the centerline and permits only one connector per appliance.

Sediment traps are not required on illuminating appliances, ranges, clothes dryers, decorative vented appliances for vented fireplaces, gas fireplaces or outdoor grills (IFGC 2018 408.4).

Wet-gas piping is sloped not less than 1/4 inch in 15 feet, and a drip is required at the meter outlet and at any low point where condensate could collect (IFGC 2018 408.1 and 408.2).

Last updated: July 2026

10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors

Quick Answer: IFGC 2018 Section 409.5.1 requires the appliance shutoff valve to be in the same room as the appliance, within 6 feet of it, installed upstream of the union, connector or quick-disconnect device it serves, and provided with access .

Section 409 (shutoff valves), Section 408 (drips and sediment traps) and Section 411 (appliance connections) are the three parts of IFGC Chapter 4 that a plumbing inspector checks on literally every gas appliance installation, which is why they are so heavily represented in the 40-question Gas Appliances and Piping domain. Every rule below is a location, a distance or a fitting type — the exact material multiple-choice questions are built from.

Where Shutoff Valves Go

  • Valve IFGC 2018 Requirement
  • Meter valve 409.2 Every meter is equipped with a shutoff valve on the supply side of the meter
  • Multiple-house line 409.3 One meter serving more than one building or tenant → a separate shutoff for each

Multiple tenants 409.3.1 Other than one- and two-family dwellings: a valve per tenant, and each tenant has access to the valve serving that tenant's space

Multiple buildings 409.3.2 Shutoff valves installed outdoors at each building

Identification 409.3.3 Each house line shutoff valve plainly marked with an identification tag attached by the installer

MP regulator 409.4 A listed shutoff valve immediately ahead of each MP (medium-pressure) regulator

Appliance — standard 409.5.1 Same room, within 6 feet , upstream of the union/connector/quick-disconnect, provided with access

Vented decorative appliances and room heaters 409.5.2 May be remote where provided with ready access , permanently identified, and serving no other appliance

Appliance — at a manifold 409.5.3 Within 50 feet of the appliance served, readily accessible, permanently identified

Laboratories 409.6 Two or more gas outlets → a single dedicated valve, readily accessible, inside the space, adjacent to the egress door , signed "Gas Shutoff"

Three limits apply to every valve in that list. Under 409.1.2 , shutoff valves are prohibited in concealed locations and in furnace plenums . Under 409.1.3 , they must be located so as to provide access for operation and be protected from damage. Under 409.7 , a valve installed in a tubing system must be rigidly and securely supported independently of the tubing , because operating torque on a ball valve handle would otherwise be transmitted straight into soft tube and work-harden or kink it.

Two accessibility nuances trip candidates. First, a valve behind a movable appliance — a range or a clothes dryer — is considered to be provided with access under 409.5.1; you do not need a wall access panel for a dryer valve. Second, " access " (reachable, possibly after removing a panel) is a weaker standard than " ready access " (reachable without removing a panel, door or obstruction and without using a portable ladder), and 409.5.2 and 409.5.3 demand ready access precisely because those valves are remote from the appliance they control.

Where 409.5.2 or 409.5.3 puts the valve away from the appliance, the piping from that valve or manifold to within 6 feet of the appliance must still be designed, sized and installed under Sections 401 through 408 — the remote-valve allowance relaxes the valve location, not the piping standard. Valve approval (409.1.1, Table 409.1.1) is pressure-keyed: ANSI Z21.15/CGA 9.1 valves are limited to the appliance shutoff application up to 1/2 psig; ASME B16.44 valves cover the appliance shutoff application and other applications up to 1/2 psig, up to 2 psig where labeled 2G , and up to 5 psig where labeled 5G ; ASME B16.33 valves cover every column, up to 125 psig .