Study guide
11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting)
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting)
Key Takeaways Explain This Topic AI
IFGC 2018 Section 504 sizes Category I appliance vents only; Categories II, III and IV are sized from the appliance manufacturer's instructions under Section 501.14.
In IFGC 2018 Table 504.2(1) at 20 feet of vent height, a 4-inch Type B vent carries 202,000 Btu/h fan-assisted with zero lateral but only 116,000 Btu/h with a 20-foot lateral, a 43 percent loss.
A common vent is sized on combined input using FAN+FAN, FAN+NAT or NAT+NAT; at 20 feet of height a 5-inch Type B common vent lists 215, 183 and 160 thousand Btu/h respectively in Table 504.3(1).
IFGC 2018 Section 504.2.14 permits interpolation between table entries and Section 504.2.15 prohibits extrapolation beyond them; heights under 6 feet require engineering methods per 504.2.16.
Listed corrugated metallic chimney liners are sized from the Type B tables with maximum capacity reduced 20 percent (0.80 x) under IFGC 2018 Sections 504.2.7 and 504.3.19, with minimum capacity unchanged.
Last updated: July 2026
11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting)
Quick Answer: Sizing a Category I vent is a disciplined table lookup: identify FAN (fan-assisted) or NAT (draft-hood) appliance, count single appliance versus common vent , measure H (total vent height) and L (lateral) - plus R (connector rise) on a common vent - then choose the smallest diameter whose Max capacity equals or exceeds the appliance input and whose Min capacity does not exceed it. IFGC 2018 Section 504 sizes Category I appliances only .
Step 1 - Pick the Right Table
IFGC 2018 Chapter 5 contains thirteen sizing tables that look nearly identical at a glance. The exam does not test your memory of their numbers; it tests whether you land on the correct table.
- Appliances Vent or chimney Connector Table
- Single Category I Type B double-wall vent Connected directly to vent 504.2(1)
- Single Category I Type B double-wall vent Single-wall metal 504.2(2)
- Single Category I Masonry chimney Type B double-wall 504.2(3)
- Single Category I Masonry chimney Single-wall metal 504.2(4)
- Single draft-hood (NAT) Single-wall metal pipe or Type B asbestos cement vent Direct 504.2(5)
- Single NAT Exterior masonry chimney Type B double-wall 504.2(6) - minimum input
- Two or more Category I Type B double-wall vent Type B double-wall 504.3(1)
- Two or more Category I Type B double-wall vent Single-wall metal 504.3(2)
- Two or more Category I Masonry chimney Type B double-wall 504.3(3)
- Two or more Category I Masonry chimney Single-wall metal 504.3(4)
- Two or more draft-hood (NAT) Single-wall metal pipe Direct 504.3(5)
- Two or more, NAT+NAT Exterior masonry chimney Type B double-wall 504.3(6a) max, 504.3(6b) min
- Two or more, FAN+NAT Exterior masonry chimney Type B double-wall 504.3(7a) max, 504.3(7b) min
Section 504.3.22 supplies the mixing rule: where single-wall and Type B double-wall connectors are both used in one system, the common vent must be sized from Table 504.3(2) or 504.3(4) - the single-wall tables - as though the entire system were single-wall.
Step 2 - Measure H, L and R
H, total vent height. For a single appliance, the vertical distance from the draft hood outlet or flue collar to the vent outlet. For multiple appliances on one floor, Section 504.3.12 measures H from the highest draft hood outlet or flue collar up to the level of the common vent outlet.
L, lateral. The horizontal run. Section 503.6.10.2 treats any angle greater than 45 degrees from vertical as horizontal , so a 60-degree offset counts entirely as lateral. Section 504.2.4 permits a "zero lateral" entry only for a straight vertical vent on a top-outlet draft hood or flue collar, and 504.2.3 forbids elbows in a zero-lateral configuration.
R, connector rise (common vents only). Section 504.3.11 measures rise from that appliance's draft hood outlet or flue collar to the centerline where the vent gas streams come together - not to the ceiling and not to the vent cap.
Lateral length quietly destroys capacity. Holding H at 20 feet in Table 504.2(1) and reading down the 4-inch Type B column, in thousands of Btu/h:
- Lateral L (ft) FAN Min FAN Max NAT Max
- 0 0 202 119
- 2 14 149 100
- 5 29 143 96
- 10 38 133 89
- 15 46 124 84
- 20 55 116 78
Going from a straight vertical vent to a 20-foot lateral costs that 4-inch Type B vent 43 percent of its fan-assisted capacity - 202,000 down to 116,000 Btu/h - while the minimum input it can safely carry climbs from zero to 55,000 Btu/h.
Step 3 - Read FAN Min, FAN Max and NAT Max
Section 504.1 defines the column headings:
FAN Min - the minimum input of a Category I fan-assisted appliance that may be attached to that vent or connector.
FAN Max - the maximum input of a Category I fan-assisted appliance.
NAT Max - the maximum input of a Category I draft-hood-equipped appliance. There is no NAT Min; a draft hood dilutes flue gas with room air and does not suffer the same starvation problem.
FAN+FAN, FAN+NAT, NAT+NAT - combined input limits for a common vent, selected by what the pair of appliances actually is.
NA - the configuration is not allowed, because it would form condensate, pressurize the venting system, or is geometrically impossible.
Why a minimum exists at all. A fan-assisted appliance pushes a modest volume of relatively cool flue gas. Put 40,000 Btu/h into a vent sized for 200,000 and the gas slows, surrenders heat to the vent wall, falls below its dew point and condenses inside a vent built of aluminum and galvanized steel that was never meant to sit in acidic water. Draft collapses at the same time. That is why the tables publish a floor as well as a ceiling, and why the instinct that "an oversized vent is a safe vent" is wrong.