Study guide
3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
Maryland Journeyman Plumber Journey Plumber/Gas Fitter
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Maryland Licensing, Code Administration & the Exam
1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy
2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926
2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work
3 Chapter 3: Materials, Uses & Specifications
3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
4 Chapter 4: Sanitary Drainage & Waste Piping
4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors
5 Chapter 5: Venting Systems
5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting
6 Chapter 6: Traps, Interceptors & Backwater Valves
6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators
7 Chapter 7: Water Supply & Distribution Systems
7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection
8 Chapter 8: Backflow Prevention & Cross-Connection Control
8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting
9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing
9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules
10 Chapter 10: Gas Piping Installation, Testing & Purging
10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response
11 Chapter 11: Gas Appliance Venting & Combustion Air
11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing
12 Chapter 12: Gas Appliance Installation & Service
12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety
13 Chapter 13: Plumbing Fixtures, Fittings & Appliances
13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements
14 Chapter 14: Plumbing Mathematics
14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions
3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
Key Takeaways Explain This Topic AI
IPC 2018 Table 706.3 permits a sanitary tee for horizontal-to-vertical changes of direction only; it is not permitted vertical-to-horizontal or horizontal-to-horizontal.
IPC 606.1 requires full-open valves in eight locations, including the water service near the curb, the discharge side of every water meter, the entrance to every dwelling unit, and the supply to every water heater.
IPC 706.3 bars a double sanitary tee from receiving back-to-back water closets unless the horizontal developed length from the closet outlet to the fitting is 18 inches (457 mm) or greater.
IPC 707.1 prohibits exactly six drainage joints: cement or concrete, mastic or hot-pour bituminous, unapproved fittings, elastomeric rolling O-rings between different pipe diameters, solvent-cement joints between different plastics, and saddle-type fittings.
IPC Appendix E rates a 1-inch globe valve at 25.0 feet of equivalent pipe length against 0.6 feet for a 1-inch gate valve — about 42 times the friction loss.
Last updated: July 2026
3.3 Valves, Fittings, Fitting Selection & Prohibited Connections
Quick Answer: A sanitary tee may be used for a horizontal-to-vertical change of direction only (IPC 2018 Table 706.3); it is not permitted vertical-to-horizontal or horizontal-to-horizontal. On the supply side, IPC 606.1 names eight locations where a full-open valve is required, including the water service near the curb, the discharge side of every water meter, the entrance to each dwelling unit, and the supply to every water heater.
Valve and fitting items reward candidates who understand why the code cares. A valve must isolate a section of work without strangling flow through it. A drainage fitting must turn the flow without letting waste fall free, pile up against a shoulder, or siphon the trap opposite it.
Full-open valves versus shutoff valves
The IPC uses two distinct terms and the exam tests the difference. A full-open valve is defined in IPC Chapter 2 as a water control or shutoff component in the water supply piping which, adjusted for maximum flow, presents no restriction in the component's through-flow area . A gate valve, a full-port ball valve and a butterfly valve satisfy that. A globe valve — whose disc seats against a horizontal seat and forces water through a reversing, S-shaped path — does not. A plain "shutoff valve" carries no such requirement, so a globe pattern or an angle stop is acceptable wherever the code says only shutoff .
- IPC 606.1 — where full-open valves are required
- On the building water service pipe from the public water supply, near the curb
- On the water distribution supply pipe at the entrance into the structure
- On the discharge side of every water meter
On the base of every water riser pipe, in occupancies other than one- and two-family dwellings and multiple-family residential occupancies two stories or less in height
On the top of every water down-feed pipe, in occupancies other than one- and two-family dwellings
On the entrance to every water supply pipe to a dwelling unit , except where it supplies a single fixture equipped with individual stops
- On the water supply pipe to a gravity or pressurized water tank
- On the water supply pipe to every water heater
- IPC 606.2 — where shutoff valves are required
On the fixture supply to each plumbing fixture, other than bathtubs and showers in one- and two-family residential occupancies, and other than individual sleeping units already provided with unit shutoff valves in hotels, motels and boarding houses
- On the water supply pipe to each sillcock
- On the water supply pipe to each appliance or mechanical equipment
IPC 606.3 requires access to all full-open and shutoff valves. IPC 606.4 requires service and hose bibb valves to be identified, along with any valve installed away from the fixture or appliance it serves.
Choosing the right valve for the service
- Valve How it closes Full-open? Correct service
- Gate Wedge disc drops perpendicular to flow Yes Main isolation; on/off only, never throttling
- Ball (full port) Bored ball rotates a quarter turn Yes Isolation and fast shutoff; the modern default
- Globe Disc seats on a horizontal seat, flow reverses No Throttling and flow regulation
- Angle Globe pattern turning 90 degrees No Fixture stops, hose connections
- Check (swing) Flow lifts a hinged disc; backflow closes it No One-way service such as pump discharge
Pressure-reducing (PRV) Spring and diaphragm regulator No Required by IPC 604.8 where static pressure exceeds 80 psi
IPC 605.7 requires valves to be compatible with the piping material installed, to conform to one of the standards listed in Table 605.7 or be approved, and — where they supply drinking water — to meet NSF 61 . Fittings are governed separately by IPC 605.5 and Table 605.5, and also carry the NSF 61 requirement in water supply systems; manufactured pipe nipples fall under 605.8 . Two PRV details are frequently tested: 604.8.1 requires the valve to be designed to remain open on failure so supply is not interrupted, and 604.8.2 requires it to be installed so parts can be repaired or removed without breaking the pipeline. Separately, 604.9 requires a water-hammer arrestor conforming to ASSE 1010 wherever quick-closing valves are used.
Why valve choice is really a sizing decision
Appendix E of the IPC publishes friction allowances expressed as equivalent lengths of pipe. For 1-inch threaded components:
- Component (1 inch) Equivalent length
- Gate valve 0.6 ft
- 90-degree elbow 3.0 ft
- Swing check valve 11.2 ft
- Globe valve 25.0 ft
Take a 1-inch run with four 90-degree elbows and one isolation valve. With a gate valve the fitting allowance is 0.6 + (4 x 3.0) = 12.6 feet . Substitute a globe valve and the identical run becomes 25.0 + 12.0 = 37.0 feet — nearly triple the friction from a single component, and 25.0 / 0.6 = about 42 times the loss of the gate valve on its own. That is precisely why the code writes "full-open" wherever a valve exists to isolate rather than to throttle.