Study guide

6.2 Grease, Oil & Special-Waste Interceptors and Separators

Maryland Journeyman Plumber Journey Plumber/Gas Fitter

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Maryland Licensing, Code Administration & the Exam

1.1 Maryland Plumbing Regulations & Licensing 1.2 The Journey Plumber/Gas Fitter Exam: Format, References & Open-Book Strategy

2 Chapter 2: Job-Site Safety & OSHA 29 CFR 1926

2.1 OSHA Construction Safety, PPE & Hazard Communication 2.2 Excavation & Trenching Safety (29 CFR 1926 Subpart P) 2.3 Confined Spaces, Ladders, Scaffolds & Hot Work

3 Chapter 3: Materials, Uses & Specifications

3.1 Approved Plumbing Materials, Pipes & Jointing 3.2 Hanger Spacing, Structural Protection & System Testing 3.3 Valves, Fittings, Fitting Selection & Prohibited Connections

4 Chapter 4: Sanitary Drainage & Waste Piping

4.1 Drainage Fixture Units (DFU) & Drain Pipe Sizing 4.2 Building Sewers, Cleanout Clearances & Underground Piping 4.3 Indirect & Special Waste Systems 4.4 Backwater Valves, Sump Pumps & Sewage Ejectors

5 Chapter 5: Venting Systems

5.1 Vent Sizing, Termination & Soil Stacks 5.2 Individual, Branch & Common Vents 5.3 Wet Venting & Circuit Venting 5.4 Air Admittance Valves (AAVs) & Special Venting

6 Chapter 6: Traps, Interceptors & Backwater Valves

6.1 Traps, Trap Seals & Trap Arm Requirements 6.2 Grease, Oil & Special-Waste Interceptors and Separators

7 Chapter 7: Water Supply & Distribution Systems

7.1 Water Supply Sizing & Fixture Unit (WSFU) Method 7.2 Water Heaters & Safety Devices 7.3 Pressure Regulation, Booster Systems & Disinfection 7.4 Water Service Piping, Meters, Valves & System Protection

8 Chapter 8: Backflow Prevention & Cross-Connection Control

8.1 Backflow Prevention & Cross-Connection Control 8.2 Air Gaps, Vacuum Breakers & Their Application Limits 8.3 Double Check & Reduced Pressure Principle (RPZ) Assemblies 8.4 Backflow Assembly Field Testing Procedures & Gauge Use 8.5 Maryland Backflow Program: 32-Hour Course, Certification & Reporting

9 Chapter 9: Fuel Gas Fundamentals, Materials & Pipe Sizing

9.1 Fuel Gas Properties, Heating Values & IFGC Scope 9.2 Fuel Gas Pipe Sizing & Materials 9.3 Approved Gas Piping Materials, CSST & Bonding 9.4 Gas Pipe Sizing Tables: Longest-Length & Branch-Length Methods 9.5 LP-Gas Systems, NFPA 58 & Propane-Specific Rules

10 Chapter 10: Gas Piping Installation, Testing & Purging

10.1 Gas Piping Installation, Testing & Purging 10.2 Gas Piping Support, Protection, Prohibited Locations & Concealed Piping 10.3 Shutoff Valves, Drips, Unions, Sediment Traps & Appliance Connectors 10.4 Gas Meters, Regulators, Pressure Levels & Overpressure Protection 10.5 Gas Leak Detection, Odorization & Emergency Response

11 Chapter 11: Gas Appliance Venting & Combustion Air

11.1 Gas Appliance Venting & Combustion Air 11.2 Appliance Categories I-IV, Vent Materials & Vent Connectors 11.3 Chimney & Vent Sizing Tables (Type B, Masonry & Common Venting) 11.4 Vent Termination, Clearances & Direct-Vent Systems 11.5 Combustion Air: Indoor & Outdoor Methods and Opening Sizing

12 Chapter 12: Gas Appliance Installation & Service

12.1 Gas Water Heaters, Furnaces & Boilers: Installation Rules 12.2 Appliance Clearances to Combustibles, Access & Location Limits 12.3 Gas Appliance Troubleshooting, Combustion Analysis & CO Safety

13 Chapter 13: Plumbing Fixtures, Fittings & Appliances

13.1 Fixture Clearances, Accessibility & Installation 13.2 Water Conservation Standards & Flow Rates 13.3 Commercial & Specialty Fixture Requirements

14 Chapter 14: Plumbing Mathematics

14.1 Plumbing Math I: Areas, Volumes, Capacities & Water Weight 14.2 Plumbing Math II: Offsets, Travel, Grade & Pipe Layout 14.3 Plumbing Math III: Gas Math, Meter Readings, BTU & Pressure Conversions

6.2 Grease, Oil & Special-Waste Interceptors and Separators

Key Takeaways Explain This Topic AI

IPC 2018 Table 1003.3.5.1 pairs every grease interceptor flow-through rating with a grease retention capacity of exactly 2 pounds per gpm, so a 50 gpm unit must retain 100 pounds.

Gravity grease interceptors are sized under IPC Section 1003.3.7 by multiplying the peak drain flow in gpm by a 30-minute retention time.

IPC Section 1003.3.2 prohibits a food waste disposer from discharging to a grease interceptor, while Section 1003.3.1 requires one to serve dishwashers without prerinse sinks.

Oil separators at garages and service stations need 6 cubic feet of capacity for the first 100 square feet of drained area plus 1 cubic foot for each additional 100 square feet (IPC 1003.4.2.2).

Oil separators must extend not less than 2 feet below the invert of the discharge drain and carry an outlet water seal of not less than 18 inches (IPC 1003.4.2.1).

Last updated: July 2026

6.2 Grease, Oil & Special-Waste Interceptors and Separators

Quick Answer: IPC 2018 Section 1003.3.5.1 requires a grease interceptor to carry a grease retention capacity of 2 pounds for every 1 gpm of rated flow (Table 1003.3.5.1 — a 50 gpm unit retains 100 lb), a gravity grease interceptor is sized as peak drain flow (gpm) x 30 minutes of retention (Section 1003.3.7), and an oil separator at a repair garage needs 6 cubic feet for the first 100 square feet of drained area plus 1 cubic foot for each additional 100 square feet (Section 1003.4.2.2).

Interceptors and separators are the pretreatment devices that keep grease, oil, sand, glass, hair and other harmful substances out of the public sewer, the private sewage system and the treatment plant (Section 1003.1). Section 1003.2 adds two governing rules that shape almost every exam question in this area: the size, type and location of each device are set by the manufacturer's instructions plus this section, based on the anticipated conditions of use ; and wastes that do not require treatment or separation shall not be discharged into any interceptor or separator . That second rule is why you never route a lavatory, a water closet or a clear-water waste line through a grease interceptor — the dilution flow just pushes accumulated grease out the outlet.

1. Where Grease Interceptors Are Required (IPC 1003.3.1)

A grease interceptor or an automatic grease removal device must receive the drainage from fixtures and equipment with grease-laden waste in food preparation areas — restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias and clubs. The code names the fixtures:

  • Pot sinks and prerinse sinks
  • Soup kettles or similar devices, and wok stations
  • Floor drains or sinks into which kettles are drained
  • Automatic hood wash units
  • Dishwashers without prerinse sinks

Two limits complete the picture:

Only grease-bearing waste. Interceptors and grease removal devices "shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged."

A food waste disposer shall not discharge to a grease interceptor (Section 1003.3.2). Ground food solids blind the baffles and destroy separation.

Not required for individual dwelling units or private living quarters (Section 1003.3.4).

Where lack of space prevents installing or replacing an interceptor, Section 1003.3.1 permits one or more interceptors to be installed on or above the floor, upstream of an existing interceptor .

Additives (Section 1003.3.3): dispensing systems that inject emulsifiers, chemicals or enzymes into a grease interceptor are prohibited — they re-liquefy grease so it passes through and congeals in the sewer. Only microbial systems for aerobic bioremediation (or anaerobic pathogen inhibition) conforming to ASME A112.14.6 are permitted, and only where the interceptor manufacturer's instructions allow them.

Exam Trap: Candidates routinely flip the dishwasher and the disposer. The 2018 IPC requires a grease interceptor to serve a dishwasher without a prerinse sink (1003.3.1) and prohibits a food waste disposer from discharging to one (1003.3.2). If an option says "a food waste disposer may discharge to a grease interceptor sized for the additional load," it is wrong under the IPC regardless of the size claimed.