2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

Michigan Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview & NEC General Requirements

1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements

2 Chapter 2: Branch Circuits & Outlets

2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

3 Chapter 3: Load Calculations for Services & Feeders

3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations

4 Chapter 4: Wiring Methods, Conductors & Insulation

4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)

5 Chapter 5: Conduit Fill, Box Fill & Panelboards

5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)

6 Chapter 6: Overcurrent Protection Devices & Tap Rules

6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility

7 Chapter 7: Grounding & Bonding Systems

7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers

8 Chapter 8: Motors, Generators & Transformers

8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)

9 Chapter 9: Special Occupancies, Equipment & Conditions

9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)

10 Chapter 10: Michigan Electrical Law, Rules & Code Administration

10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ

11 Chapter 11: Electrical Theory & General Trade Knowledge

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math

12 Chapter 12: Services & Feeders (Articles 230 & 215)

12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements

13 Chapter 13: Lighting, Appliances & Power-Limited Circuits

13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)

2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

Key Takeaways Explain This Topic AI

NEC 404.2(C) requires a grounded conductor to be provided at the switch location for switches controlling lighting loads, with limited exceptions such as raceway sufficiently sized for a future grounded conductor or cable with an accessible spare.

NEC 404.8(A) limits the center of the grip of a switch operating handle in its highest position to not more than 2.0 m (6 ft 7 in) above the floor or working platform.

NEC 406.4(D) governs receptacle replacement and can require a grounding type, GFCI, AFCI, tamper-resistant, or weather-resistant device depending on where the replacement occurs.

NEC 406.5(E) prohibits receptacles from being installed in a face-up position in or on countertop or work surfaces, and 406.9(B) requires an enclosure that is weatherproof whether or not an attachment plug is inserted for 15- and 20-ampere 125- and 250-volt receptacles in wet locations.

NEC 406.9(C) prohibits receptacles from being installed within a bathtub or shower space, a zone the 2023 NEC continues to police alongside the luminaire and fan restrictions of 410.10(D).

Last updated: August 2026

2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

Exam Focus: 404.2(C) grounded conductor at the switch, 404.8(A) handle height, 406.4(D) replacement rules, 406.5 mounting and the face-up prohibition, 406.9 damp and wet locations, and the bathtub/shower zone.

Sections 2.1 through 2.4 sized the circuit and located the outlets. This section covers the devices that land on those outlets. Article 404 governs switches, Article 406 governs receptacles, cord connectors, and attachment plugs.

  • Switches — Article 404
  • The Grounded Conductor at the Switch (404.2(C))

Where a switch controls a lighting load , the grounded (neutral) conductor must be provided at the switch location . The reason is practical: electronic dimmers, timers, occupancy sensors, and smart switches need a neutral to power their electronics, and without one they leak current through the equipment grounding conductor.

Limited exceptions permit omitting the grounded conductor where:

Conductors enter the box through a raceway with sufficient cross-sectional area to accept a future grounded conductor; or

Cable assemblies enter the box through a framing cavity that is open at the top or bottom on the same floor level, or through a wall, floor, or ceiling that is unfinished on one side .

Switch Mounting and Position

Rule Requirement

404.8(A) The center of the grip of the operating handle, in its highest position, must be not more than 2.0 m (6 ft 7 in) above the floor or working platform

404.7 Single-throw knife switches must be placed so gravity will not close them; general-use switches must clearly indicate on/off position

404.9(B) Metal faceplates must be grounded ; snap switches must be effectively grounded and provide a means to ground the metal faceplate

  • 404.4 Switches in damp or wet locations must be in a weatherproof enclosure
  • 404.2(A) Three-way and four-way switches must switch only the ungrounded conductor

Caution

Never switch the grounded conductor. Switching the neutral leaves the luminaire energized to ground even when the switch is off. This is one of the few code rules that produces a fatality when ignored, and it appears on licensing exams in troubleshooting form.

  • Receptacles — Article 406
  • Mounting and Position (406.5)

Rule Requirement

406.5(A)–(C) Receptacles must be mounted in boxes or assemblies designed for the purpose; boxes set back in noncombustible surfaces may not be set back more than 6 mm (1/4 in)

406.5(E) Receptacles must not be installed in a face-up position in or on countertop or work surfaces

406.5(F) Receptacles must not be installed in a face-up position in seating areas or similar surfaces unless listed for that application

  • 406.5(G) Receptacles installed in a face-up position in a floor require an assembly listed for floor use
  • 406.4(G) Floor receptacles are subject to protection requirements added in the 2023 NEC

The face-up prohibition exists because a face-up receptacle collects liquid, crumbs, and metal debris. The permitted alternative for an island or peninsula is a listed pop-up or countertop assembly , which is why the 2023 island rules in 210.52(C) reference listed assemblies.

Damp and Wet Locations (406.9)

  • Location Required Enclosure
  • Damp location An enclosure weatherproof when the attachment plug is removed

Wet location — 15 A and 20 A, 125 V and 250 V An enclosure weatherproof whether or not the attachment plug is inserted — the "in-use" or bubble cover

Wet location — other receptacles An enclosure weatherproof when the plug is removed, where the receptacle is not likely to be used with a cord left connected

Covers must be capable of opening at least 90 degrees , or fully open where the cover is not designed to open 90 degrees.

The Bathtub and Shower Space (406.9(C))

Receptacles shall not be installed within a bathtub or shower space . Pair this with 410.10(D) , which in the 2023 NEC prohibits a ceiling-suspended fan with a light kit within a zone measured 3 ft horizontally and 8 ft vertically from the top of the bathtub rim or shower stall threshold.

Receptacle Replacement — NEC 406.4(D)

Replacing a receptacle is not always a like-for-like operation. Six separate triggers can attach:

406.4(D) Subsection Trigger

(1) Where a grounding means exists in the box, the replacement must be a grounding-type receptacle connected to the equipment grounding conductor

(2) Where no grounding means exists , the replacement may be (a) another non-grounding type, (b) a GFCI type marked "No Equipment Ground" , or (c) a grounding type supplied through a GFCI and marked "GFCI Protected" and "No Equipment Ground"

(3) Where the location now requires GFCI protection under 210.8, the replacement must be GFCI protected

(4) Where the location now requires AFCI protection under 210.12, the replacement must be AFCI protected — in dwelling units, dormitory units, guest rooms and guest suites, and patient sleeping rooms of nursing homes and limited-care facilities

(5) Where tamper-resistant receptacles are required by 406.12, the replacement must be tamper resistant

(6) Where weather-resistant receptacles are required by 406.9(A) and (B), the replacement must be weather resistant

Important

The replacement rules are how the NEC upgrades existing buildings. A homeowner replacing a broken kitchen receptacle in a 1968 house triggers 210.8 GFCI protection under 406.4(D)(3) even though nothing else in the kitchen changes. Bootleg grounding — jumping the neutral to the ground screw — is never a permitted method and creates an energized equipment ground.

Faceplates, Night Lights, and USB Chargers

406.6 requires faceplates to completely cover the opening and seat against the mounting surface.

406.6(D) addresses receptacle faceplates with an integral night light or USB charger , which must be listed and, where they contain electronics, supplied through the receptacle's own terminals.

406.3(D) requires that receptacles be listed and marked with the manufacturer's identification and ratings.