Study guide

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits

Michigan Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview & NEC General Requirements

1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements

2 Chapter 2: Branch Circuits & Outlets

2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

3 Chapter 3: Load Calculations for Services & Feeders

3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations

4 Chapter 4: Wiring Methods, Conductors & Insulation

4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)

5 Chapter 5: Conduit Fill, Box Fill & Panelboards

5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)

6 Chapter 6: Overcurrent Protection Devices & Tap Rules

6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility

7 Chapter 7: Grounding & Bonding Systems

7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers

8 Chapter 8: Motors, Generators & Transformers

8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)

9 Chapter 9: Special Occupancies, Equipment & Conditions

9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)

10 Chapter 10: Michigan Electrical Law, Rules & Code Administration

10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ

11 Chapter 11: Electrical Theory & General Trade Knowledge

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math

12 Chapter 12: Services & Feeders (Articles 230 & 215)

12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements

13 Chapter 13: Lighting, Appliances & Power-Limited Circuits

13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits

Key Takeaways Explain This Topic AI

Ohm's law states that E = I x R, and the power formulas P = E x I, P = I squared x R, and P = E squared / R let any two known quantities produce the other two.

In a series circuit the current is the same everywhere, the resistances add, and the source voltage divides across the loads in proportion to each resistance.

In a parallel circuit the voltage is the same across every branch, the branch currents add, and the total resistance is always smaller than the smallest single branch resistance.

For two resistances in parallel the product-over-sum shortcut R = (R1 x R2) / (R1 + R2) is exact, and for N equal resistances the total is simply R / N.

The PSI bulletin names electrical theory and general electrical trade knowledge as tested subjects, and theory items are answered from formulas rather than from the code book, so they must be memorized before exam day.

Last updated: August 2026

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits

Exam Focus: E = I x R, the three power formulas, series versus parallel behavior, voltage division, combined resistance shortcuts, and the arithmetic habits that keep a theory item under 90 seconds.

The PSI bulletin lists electrical theory and general electrical trade knowledge among the subjects on the journeyman examination. These are the questions you cannot look up. The NEC contains no page that tells you the current through a 12-ohm heater on a 240-volt circuit — you have to know it. Fortunately the entire theory domain rests on a handful of relationships.

Ohm's Law

E = I × R , where E is electromotive force in volts, I is current in amperes, and R is resistance in ohms.

Rearranged: I = E R R = E I E = I × R I = \frac{E}{R} \qquad R = \frac{E}{I} \qquad E = I \times R I = R E ​ R = I E ​ E = I × R THE OHM'S LAW / POWER WHEEL

  • +-------------------------------------------------------------------------+
  • | |
  • | E = I x R I = E / R R = E / I |
  • | P = E x I P = I^2 x R P = E^2 / R |
  • | |
  • | E = P / I I = P / E R = P / I^2 |
  • | |
  • | Know any TWO of E, I, R, P and you can produce the other two. |
  • +-------------------------------------------------------------------------+

The Three Power Formulas P = E × I P = I 2 × R P = E 2 R P = E \times I \qquad P = I^{2} \times R \qquad P = \frac{E^{2}}{R} P = E × I P = I 2 × R P = R E 2 ​

Which one to reach for:

  • You know volts and amps → P = E × I
  • You know amps and ohms → P = I² × R (this is the heating formula; it is why doubling current quadruples heat)
  • You know volts and ohms → P = E² / R

Important

P = I²R is the one that explains the code. Conductor derating, ampacity correction, loose-connection failures, and overload protection all exist because heat rises with the square of current. A connection carrying twice its intended current dissipates four times the heat.

Series Circuits

A series circuit provides exactly one path for current.

Quantity Series Behavior

Current Same through every component: I T = I 1 = I 2 = I 3 I_T = I_1 = I_2 = I_3 I T ​ = I 1 ​ = I 2 ​ = I 3 ​

Resistance Adds : R T = R 1 + R 2 + R 3 R_T = R_1 + R_2 + R_3 R T ​ = R 1 ​ + R 2 ​ + R 3 ​

Voltage Divides in proportion to resistance: E T = E 1 + E 2 + E 3 E_T = E_1 + E_2 + E_3 E T ​ = E 1 ​ + E 2 ​ + E 3 ​

  • Power Adds : P T = P 1 + P 2 + P 3 P_T = P_1 + P_2 + P_3 P T ​ = P 1 ​ + P 2 ​ + P 3 ​
  • Worked Example — Series

Three resistors of 4 Ω, 6 Ω, and 10 Ω are connected in series across 120 V.

R T = 4 + 6 + 10 = 20 Ω R_T = 4 + 6 + 10 = 20\ \Omega R T ​ = 4 + 6 + 10 = 20 Ω

I T = 120 20 = 6 A I_T = \dfrac{120}{20} = 6\ \text{A} I T ​ = 20 120 ​ = 6 A (the same 6 A flows through all three)

Voltage drops: E 1 = 6 × 4 = 24 V E_1 = 6 \times 4 = 24\ \text{V} E 1 ​ = 6 × 4 = 24 V , E 2 = 6 × 6 = 36 V E_2 = 6 \times 6 = 36\ \text{V} E 2 ​ = 6 × 6 = 36 V , E 3 = 6 × 10 = 60 V E_3 = 6 \times 10 = 60\ \text{V} E 3 ​ = 6 × 10 = 60 V

  • Check: 24 + 36 + 60 = 120 V 24 + 36 + 60 = 120\ \text{V} 24 + 36 + 60 = 120 V ✔
  • Total power: P = 120 × 6 = 720 W P = 120 \times 6 = 720\ \text{W} P = 120 × 6 = 720 W

Trade connection: A loose terminal is a resistance placed in series with the load. It steals voltage from the load and converts it to heat right at the connection — which is why 110.14(D) requires terminations to be torqued to the manufacturer's value.

Parallel Circuits

A parallel circuit provides more than one path for current. Building wiring is overwhelmingly parallel: every receptacle on a circuit sees the same 120 V.

  • Quantity Parallel Behavior
  • Voltage Same across every branch: E T = E 1 = E 2 = E 3 E_T = E_1 = E_2 = E_3 E T ​ = E 1 ​ = E 2 ​ = E 3 ​
  • Current Adds : I T = I 1 + I 2 + I 3 I_T = I_1 + I_2 + I_3 I T ​ = I 1 ​ + I 2 ​ + I 3 ​
  • Resistance Decreases : always less than the smallest branch
  • Power Adds : P T = P 1 + P 2 + P 3 P_T = P_1 + P_2 + P_3 P T ​ = P 1 ​ + P 2 ​ + P 3 ​
  • The Three Resistance Shortcuts

Equal resistances: R T = R N R_T = \dfrac{R}{N} R T ​ = N R ​ — three 30 Ω branches give 10 Ω.

Exactly two resistances (product over sum): R T = R 1 × R 2 R 1 + R 2 R_T = \dfrac{R_1 \times R_2}{R_1 + R_2} R T ​ = R 1 ​ + R 2 ​ R 1 ​ × R 2 ​ ​

Any number (reciprocal method): R T = 1 1 R 1 + 1 R 2 + 1 R 3 R_T = \dfrac{1}{\frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3}} R T ​ = R 1 ​ 1 ​ + R 2 ​ 1 ​ + R 3 ​ 1 ​ 1 ​

Worked Example — Parallel

A 120 V circuit supplies a 24 Ω heater, a 40 Ω lamp bank, and a 60 Ω fan motor.

Branch currents: I 1 = 120 / 24 = 5 A I_1 = 120/24 = 5\ \text{A} I 1 ​ = 120/24 = 5 A , I 2 = 120 / 40 = 3 A I_2 = 120/40 = 3\ \text{A} I 2 ​ = 120/40 = 3 A , I 3 = 120 / 60 = 2 A I_3 = 120/60 = 2\ \text{A} I 3 ​ = 120/60 = 2 A

Total current: 5 + 3 + 2 = 10 A 5 + 3 + 2 = 10\ \text{A} 5 + 3 + 2 = 10 A

Total resistance: R T = 120 / 10 = 12 Ω R_T = 120/10 = 12\ \Omega R T ​ = 120/10 = 12 Ω — smaller than the 24 Ω smallest branch ✔

Total power: P = 120 × 10 = 1,200 W P = 120 \times 10 = 1{,}200\ \text{W} P = 120 × 10 = 1 , 200 W

Caution

The reasonableness check that catches most errors. If a parallel-resistance answer is larger than the smallest branch resistance, it is wrong — no exceptions. If a series-resistance answer is smaller than the largest resistor, it is wrong.

Kirchhoff's Two Laws, Stated for the Trade

Current law: the current entering a node equals the current leaving it. This is why the neutral of a balanced multiwire branch circuit carries the difference and not the sum.

Voltage law: the sum of the voltage drops around a closed loop equals the applied voltage. This is why the three series drops above had to total 120 V.

Exam Technique for Theory Items

Write down what you are given with units. Most wrong answers come from mixing watts with volt-amperes or ohms with amperes.

Identify the topology first. Series or parallel decides which rules apply before any arithmetic happens.

Use the check. Series drops must sum to the source; parallel currents must sum to the total.

Watch kilo prefixes. A 4.8 kW heater is 4,800 W. Dropping the factor of 1,000 turns a right method into a wrong answer.