Study guide

11.3 Power Factor, Efficiency & Transformer Theory

Michigan Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview & NEC General Requirements

1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements

2 Chapter 2: Branch Circuits & Outlets

2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

3 Chapter 3: Load Calculations for Services & Feeders

3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations

4 Chapter 4: Wiring Methods, Conductors & Insulation

4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)

5 Chapter 5: Conduit Fill, Box Fill & Panelboards

5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)

6 Chapter 6: Overcurrent Protection Devices & Tap Rules

6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility

7 Chapter 7: Grounding & Bonding Systems

7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers

8 Chapter 8: Motors, Generators & Transformers

8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)

9 Chapter 9: Special Occupancies, Equipment & Conditions

9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)

10 Chapter 10: Michigan Electrical Law, Rules & Code Administration

10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ

11 Chapter 11: Electrical Theory & General Trade Knowledge

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math

12 Chapter 12: Services & Feeders (Articles 230 & 215)

12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements

13 Chapter 13: Lighting, Appliances & Power-Limited Circuits

13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)

11.3 Power Factor, Efficiency & Transformer Theory

Key Takeaways Explain This Topic AI

Power factor is the ratio of true power in watts to apparent power in volt-amperes, and a purely resistive load has a power factor of 1.0 while inductive loads such as motors lag with power factors typically between 0.80 and 0.95.

True power P equals apparent power S multiplied by power factor, so amperes for a motor load are calculated from volt-amperes rather than from watts.

Transformer voltage, current, and turns follow the relationships Ep/Es = Np/Ns and Ep x Ip = Es x Is, so a step-down in voltage produces a proportional step-up in current.

Transformer kVA is the same on both the primary and the secondary, which is why secondary full-load amperes are found by dividing the kVA by the secondary voltage, times 1.732 for three-phase.

Efficiency is output power divided by input power expressed as a percent, and the difference is dissipated as core loss and copper loss inside the equipment.

Last updated: August 2026

11.3 Power Factor, Efficiency & Transformer Theory

Exam Focus: True/reactive/apparent power and the power triangle, power factor arithmetic, transformer turns and current ratios, primary and secondary full-load current, and efficiency.

Load calculation questions give you volt-amperes . Nameplate questions often give you watts and a power factor . Knowing how to move between them is what separates a correct feeder size from a wrong one.

Three Kinds of Power

  • Symbol Name Unit What It Is
  • P True (real, active) power Watts (W) Power actually converted to work or heat

Q Reactive power Volt-amperes reactive (VAR) Power exchanged with magnetic or electrostatic fields; does no work but occupies conductor capacity

S Apparent power Volt-amperes (VA) The vector total the conductors and transformer must actually carry THE POWER TRIANGLE

  • /|
  • / |
  • S (VA) / | Q (VAR)
  • Apparent / | Reactive
  • / angle |
  • /__________|
  • P (W)
  • True Power
  • P = S x cos(angle) PF = P / S
  • S = sqrt(P^2 + Q^2)

Power Factor P F = P ( watts ) S ( volt-amperes ) PF = \frac{P\ (\text{watts})}{S\ (\text{volt-amperes})} PF = S ( volt-amperes ) P ( watts ) ​

  • Load Type Typical Power Factor Behavior
  • Incandescent lamp, resistance heater, electric range 1.00 Unity — current in phase with voltage
  • Induction motor at full load 0.80 – 0.90 Lagging — current lags voltage
  • Lightly loaded induction motor 0.30 – 0.60 Strongly lagging; the worst case for utility billing
  • Capacitor bank Leading Used to correct a lagging system
  • Worked Example

A single-phase 240 V motor draws 20 A at a power factor of 0.85.

Apparent power: S = 240 × 20 = 4,800 VA S = 240 \times 20 = 4{,}800\ \text{VA} S = 240 × 20 = 4 , 800 VA

True power: P = 4,800 × 0.85 = 4,080 W P = 4{,}800 \times 0.85 = 4{,}080\ \text{W} P = 4 , 800 × 0.85 = 4 , 080 W

Notice the direction of travel: the conductor and overcurrent device are sized from the 4,800 VA / 20 A , not from the 4,080 W. Sizing from watts would undersize the circuit.

Caution

Do not divide watts by volts for a motor. For any load with a power factor below unity, I = P E × P F I = \dfrac{P}{E \times PF} I = E × PF P ​ for single-phase and I = P 1.732 × E × P F I = \dfrac{P}{1.732 \times E \times PF} I = 1.732 × E × PF P ​ for three-phase. On the exam, Article 430 sidesteps this entirely by giving you full-load current directly in Tables 430.248 and 430.250 — use those tables for motor circuit sizing, and reserve the power-factor formula for theory items.

Efficiency % Efficiency = P o u t p u t P i n p u t × 100 \%\ \text{Efficiency} = \frac{P_{output}}{P_{input}} \times 100 % Efficiency = P in p u t ​ P o u tp u t ​ ​ × 100

A motor delivering 10 hp of mechanical output while drawing 8,500 W:

Output in watts: 10 hp × 746 = 7,460 W 10\ \text{hp} \times 746 = 7{,}460\ \text{W} 10 hp × 746 = 7 , 460 W

Efficiency: 7,460 / 8,500 = 0.878 = 87.8 % 7{,}460 / 8{,}500 = 0.878 = \mathbf{87.8\%} 7 , 460/8 , 500 = 0.878 = 87.8%

1 horsepower = 746 watts. Memorize it; it appears in motor questions constantly.

Transformer Theory

A transformer transfers energy between two coils by mutual induction. It changes voltage and current, but not power (apart from losses) and not frequency .

The Three Ratios E P E S = N P N S = I S I P \frac{E_P}{E_S} = \frac{N_P}{N_S} = \frac{I_S}{I_P} E S ​ E P ​ ​ = N S ​ N P ​ ​ = I P ​ I S ​ ​

Read carefully: voltage and turns move together , while current moves opposite . A step-down transformer has more primary turns, less secondary voltage, and more secondary current. E P × I P = E S × I S ( ideal, no losses ) E_P \times I_P = E_S \times I_S \quad (\text{ideal, no losses}) E P ​ × I P ​ = E S ​ × I S ​ ( ideal, no losses )

Worked Example — Turns and Current

A single-phase transformer has 800 primary turns and 100 secondary turns, with 480 V applied to the primary.

  • Turns ratio: 800 : 100 = 8 : 1 800 : 100 = 8 : 1 800 : 100 = 8 : 1 (step-down)
  • Secondary voltage: 480 / 8 = 60 V 480 / 8 = \mathbf{60\ \text{V}} 480/8 = 60 V
  • If the secondary delivers 40 A, primary current is 40 / 8 = 5 A 40 / 8 = \mathbf{5\ \text{A}} 40/8 = 5 A

Check: 480 × 5 = 2,400 VA 480 \times 5 = 2{,}400\ \text{VA} 480 × 5 = 2 , 400 VA and 60 × 40 = 2,400 VA 60 \times 40 = 2{,}400\ \text{VA} 60 × 40 = 2 , 400 VA ✔

Full-Load Current from kVA

The kVA rating is the same on both sides. Use the voltage of the side you want.

  • System Full-Load Current
  • Single-phase I = k V A × 1000 E I = \dfrac{kVA \times 1000}{E} I = E kV A × 1000 ​
  • Three-phase I = k V A × 1000 1.732 × E I = \dfrac{kVA \times 1000}{1.732 \times E} I = 1.732 × E kV A × 1000 ​

Example: a 75 kVA, three-phase transformer with a 208 V secondary. I S = 75,000 1.732 × 208 = 75,000 360.3 = 208.2 A I_S = \frac{75{,}000}{1.732 \times 208} = \frac{75{,}000}{360.3} = \mathbf{208.2\ \text{A}} I S ​ = 1.732 × 208 75 , 000 ​ = 360.3 75 , 000 ​ = 208.2 A

And its 480 V primary: I P = 75,000 1.732 × 480 = 75,000 831.4 = 90.2 A I_P = \frac{75{,}000}{1.732 \times 480} = \frac{75{,}000}{831.4} = \mathbf{90.2\ \text{A}} I P ​ = 1.732 × 480 75 , 000 ​ = 831.4 75 , 000 ​ = 90.2 A

These two numbers feed directly into the Article 450 overcurrent protection rules covered in Chapter 8.

Transformer Losses

Core (iron) loss — hysteresis and eddy currents in the steel. Essentially constant whenever the transformer is energized, regardless of load.

Copper loss — I 2 R I^2R I 2 R in the windings. Varies with the square of the load current .

Because core loss is constant, a lightly loaded transformer is an inefficient transformer, and an energized but unloaded transformer still consumes power.

Quick Reference

  • Relationship Formula
  • Power factor P F = P / S PF = P / S PF = P / S
  • True power from VA P = S × P F P = S \times PF P = S × PF
  • Horsepower to watts 1 hp = 746 W 1\ \text{hp} = 746\ \text{W} 1 hp = 746 W
  • Efficiency P o u t / P i n × 100 P_{out} / P_{in} \times 100 P o u t ​ / P in ​ × 100

Transformer ratio E P / E S = N P / N S = I S / I P E_P/E_S = N_P/N_S = I_S/I_P E P ​ / E S ​ = N P ​ / N S ​ = I S ​ / I P ​

3-phase FLA from kVA I = ( k V A × 1000 ) / ( 1.732 × E ) I = (kVA \times 1000) / (1.732 \times E) I = ( kV A × 1000 ) / ( 1.732 × E )