Study guide

11.4 Voltage Drop, Conductor Resistance & Trade Math

Michigan Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview & NEC General Requirements

1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements

2 Chapter 2: Branch Circuits & Outlets

2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

3 Chapter 3: Load Calculations for Services & Feeders

3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations

4 Chapter 4: Wiring Methods, Conductors & Insulation

4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)

5 Chapter 5: Conduit Fill, Box Fill & Panelboards

5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)

6 Chapter 6: Overcurrent Protection Devices & Tap Rules

6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility

7 Chapter 7: Grounding & Bonding Systems

7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers

8 Chapter 8: Motors, Generators & Transformers

8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)

9 Chapter 9: Special Occupancies, Equipment & Conditions

9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)

10 Chapter 10: Michigan Electrical Law, Rules & Code Administration

10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ

11 Chapter 11: Electrical Theory & General Trade Knowledge

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math

12 Chapter 12: Services & Feeders (Articles 230 & 215)

12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements

13 Chapter 13: Lighting, Appliances & Power-Limited Circuits

13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)

11.4 Voltage Drop, Conductor Resistance & Trade Math

Key Takeaways Explain This Topic AI

Single-phase voltage drop is calculated as VD = (2 x K x I x D) / CM, and three-phase voltage drop uses 1.732 in place of the 2, where D is the one-way circuit length.

The resistivity constant K is approximately 12.9 ohm-circular mils per foot for copper and 21.2 for aluminum at 75 degrees Celsius.

Circular mil areas come from NEC Chapter 9 Table 8, which also lists conductor stranding, overall area, and direct-current resistance per 1,000 feet.

Solving the voltage-drop formula for circular mils, CM = (2 x K x I x D) / VD-allowed, gives the minimum conductor size that will hold a target drop.

The NEC treats voltage drop as advisory informational-note guidance rather than as an enforceable rule, but sensitivity to voltage drop is real: power in a fixed resistance varies with the square of the applied voltage.

Last updated: August 2026

11.4 Voltage Drop, Conductor Resistance & Trade Math

Exam Focus: The two voltage-drop formulas, the K constants, Chapter 9 Table 8, solving for circular mils, and the offset/bending arithmetic that appears under general trade knowledge.

Voltage drop is where theory and the code book meet. The formula is memory work; the circular mil area comes out of Chapter 9, Table 8 , which you are allowed to have in front of you.

The Two Formulas

  • System Voltage Drop Formula
  • Single-phase V D = 2 × K × I × D C M VD = \dfrac{2 \times K \times I \times D}{CM} V D = CM 2 × K × I × D ​

Three-phase V D = 1.732 × K × I × D C M VD = \dfrac{1.732 \times K \times I \times D}{CM} V D = CM 1.732 × K × I × D ​

Where:

  • K = resistivity constant in ohm-circular mils per foot: 12.9 for copper , 21.2 for aluminum (at 75 °C)
  • I = load current in amperes
  • D = one-way circuit length in feet — the 2 (or 1.732) already accounts for the return path

CM = conductor circular mil area from Chapter 9, Table 8 % V D = V D E s o u r c e × 100 \%VD = \frac{VD}{E_{source}} \times 100 % V D = E so u rce ​ V D ​ × 100

Caution

The most common mistake is doubling the distance twice. If a panel is 150 ft from the load, D = 150. The factor of 2 in the numerator is the return conductor. Entering 300 ft and keeping the 2 doubles your answer.

Circular Mil Areas You Should Recognize

Values are read from NEC Chapter 9, Table 8, Conductor Properties , which lists size, stranding, overall area in circular mils and square inches, and direct-current resistance per 1,000 ft for coated and uncoated copper and for aluminum.

  • Conductor Size Circular Mils (CM)
  • 14 AWG 4,110
  • 12 AWG 6,530
  • 10 AWG 10,380
  • 8 AWG 16,510
  • 6 AWG 26,240
  • 4 AWG 41,740
  • 2 AWG 66,360
  • 1/0 AWG 105,600
  • 2/0 AWG 133,100
  • 4/0 AWG 211,600

Two useful patterns: each three AWG sizes roughly doubles the circular mil area , and above 4/0 the sizes are expressed directly in thousands of circular mils (250 kcmil = 250,000 CM).

Worked Example — Finding the Drop

A 120 V single-phase circuit carries 16 A to a load 100 ft from the panel using 12 AWG copper.

C M = 6,530 CM = 6{,}530 CM = 6 , 530 , K = 12.9 K = 12.9 K = 12.9

V D = 2 × 12.9 × 16 × 100 6,530 = 41,280 6,530 = 6.32 V VD = \dfrac{2 \times 12.9 \times 16 \times 100}{6{,}530} = \dfrac{41{,}280}{6{,}530} = 6.32\ \text{V} V D = 6 , 530 2 × 12.9 × 16 × 100 ​ = 6 , 530 41 , 280 ​ = 6.32 V

% V D = 6.32 120 × 100 = 5.27 % \%VD = \dfrac{6.32}{120} \times 100 = 5.27\% % V D = 120 6.32 ​ × 100 = 5.27%

That exceeds the 3% branch-circuit guidance, so upsize:

10 AWG (10,380 CM): V D = 41,280 / 10,380 = 3.98 V = 3.3 % VD = 41{,}280/10{,}380 = 3.98\ \text{V} = 3.3\% V D = 41 , 280/10 , 380 = 3.98 V = 3.3% — still over

8 AWG (16,510 CM): V D = 41,280 / 16,510 = 2.50 V = 2.08 % VD = 41{,}280/16{,}510 = 2.50\ \text{V} = 2.08\% V D = 41 , 280/16 , 510 = 2.50 V = 2.08% — acceptable

Worked Example — Solving for Conductor Size

Rearranging for circular mils is faster than guess-and-check: C M = 2 × K × I × D V D a l l o w e d CM = \frac{2 \times K \times I \times D}{VD_{allowed}} CM = V D a ll o w e d ​ 2 × K × I × D ​

Problem: a 240 V single-phase feeder carries 60 A a distance of 250 ft in copper. Hold the drop to 3%.

Allowable drop: 240 × 0.03 = 7.2 V 240 \times 0.03 = 7.2\ \text{V} 240 × 0.03 = 7.2 V

C M = 2 × 12.9 × 60 × 250 7.2 = 387,000 7.2 = 53,750 CM CM = \dfrac{2 \times 12.9 \times 60 \times 250}{7.2} = \dfrac{387{,}000}{7.2} = 53{,}750\ \text{CM} CM = 7.2 2 × 12.9 × 60 × 250 ​ = 7.2 387 , 000 ​ = 53 , 750 CM

From Table 8, 4 AWG is 41,740 CM (too small) and 3 AWG is 52,620 CM (still short), so 2 AWG at 66,360 CM is the first size that satisfies the target.

Remember: the ampacity requirement and the voltage-drop requirement are two separate tests. Size for ampacity first using Table 310.16 and 110.14(C), then check voltage drop and upsize if needed. The larger of the two results wins.

Three-Phase Example

A 208 V three-phase feeder carries 100 A a distance of 200 ft in 1/0 AWG copper. V D = 1.732 × 12.9 × 100 × 200 105,600 = 446,856 105,600 = 4.23 V VD = \frac{1.732 \times 12.9 \times 100 \times 200}{105{,}600} = \frac{446{,}856}{105{,}600} = 4.23\ \text{V} V D = 105 , 600 1.732 × 12.9 × 100 × 200 ​ = 105 , 600 446 , 856 ​ = 4.23 V % V D = 4.23 208 × 100 = 2.03 % — acceptable \%VD = \frac{4.23}{208} \times 100 = 2.03\% \quad \text{— acceptable} % V D = 208 4.23 ​ × 100 = 2.03% — acceptable

Why Voltage Drop Matters Even Though It Is Advisory

The NEC's 3% and 5% figures sit in informational notes, which 90.5(C) makes non-enforceable. The physics is not advisory:

Resistive loads: power falls with the square of voltage. A 5% drop costs about 10% of the heat output.

Motors: a motor running at reduced voltage draws more current to deliver the same mechanical output, raising winding temperature and shortening insulation life.

Electronic ballasts and drivers: may drop out or run hot at sustained low voltage.

  • Trade Math Under General Electrical Trade Knowledge
  • Conduit Offsets

The travel of an offset is found from the offset height and the bend angle multiplier:

  • Bend Angle Multiplier (travel) Shrink per inch of offset
  • 10° 6.0 1/16 in
  • 22.5° 2.6 3/16 in
  • 30° 2.0 1/4 in
  • 45° 1.4 3/8 in
  • 60° 1.2 1/2 in

Example: a 6 in offset using 30° bends. Distance between bend marks = 6 × 2.0 = 12 in 6 \times 2.0 = 12\ \text{in} 6 × 2.0 = 12 in , and the run shrinks by 6 × 1 / 4 = 1.5 in 6 \times 1/4 = 1.5\ \text{in} 6 × 1/4 = 1.5 in .

  • Other Trade Constants Worth Memorizing
  • 1 hp = 746 W
  • 1 kW = 1.34 hp
  • 1 kWh = 1,000 watts drawn for one hour
  • Right triangle: c = a 2 + b 2 c = \sqrt{a^2 + b^2} c = a 2 + b 2 ​ — used for saddle bends and diagonal runs
  • Circle area = π r 2 \pi r^2 π r 2 — the basis of every conduit-fill calculation in Chapter 9