1.3 NEC Article 100 Essential Definitions
Michigan Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview & NEC General Requirements
1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements
2 Chapter 2: Branch Circuits & Outlets
2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)
3 Chapter 3: Load Calculations for Services & Feeders
3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations
4 Chapter 4: Wiring Methods, Conductors & Insulation
4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
5 Chapter 5: Conduit Fill, Box Fill & Panelboards
5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)
6 Chapter 6: Overcurrent Protection Devices & Tap Rules
6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility
7 Chapter 7: Grounding & Bonding Systems
7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers
8 Chapter 8: Motors, Generators & Transformers
8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)
9 Chapter 9: Special Occupancies, Equipment & Conditions
9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)
10 Chapter 10: Michigan Electrical Law, Rules & Code Administration
10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ
11 Chapter 11: Electrical Theory & General Trade Knowledge
11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math
12 Chapter 12: Services & Feeders (Articles 230 & 215)
12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements
13 Chapter 13: Lighting, Appliances & Power-Limited Circuits
13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)
1.3 NEC Article 100 Essential Definitions
Key Takeaways Explain This Topic AI
Readily Accessible equipment must be reachable quickly for operation, renewal, or inspection without using portable ladders, climbing over obstacles, or resorting to portable tools (Article 100).
A Branch Circuit comprises the circuit conductors between the final overcurrent protective device and the outlet(s), separating it functionally from Feeders and Service conductors.
A Grounded Conductor is an intentionally grounded circuit conductor (neutral), whereas an Equipment Grounding Conductor (EGC) connects non-current-carrying metal parts to ground.
A Continuous Load is any load where the maximum current is expected to continue for 3 hours or more, requiring a 125% rating multiplier for overcurrent devices and branch circuit conductors.
Ampacity is defined as the maximum current, in amperes, that a conductor can carry continuously under conditions of use without exceeding its temperature rating.
Last updated: August 2026
1.3 NEC Article 100 Essential Definitions
Exam Focus: Accessibility classifications, circuit hierarchy (service, feeder, branch circuit), grounding/bonding terminology, continuous load rules, ampacity, and disconnecting means.
Article 100 contains all defined terms essential for applying the National Electrical Code. On the Michigan Journeyman examination, definition questions appear in two forms: direct definition identification and situational application questions where code compliance hinges on the precise legal meaning of a single word.
Accessibility Terms: Accessible vs. Readily Accessible
One of the most frequently tested distinctions in Article 100 is the difference between equipment that is Accessible , Accessible (as applied to wiring methods) , and Readily Accessible . ACCESSIBILITY COMPARISON MATRIX
- +-------------------------------------------------------------------------+
- | READILY ACCESSIBLE (e.g., Service Disconnects, Panel OCPDs) |
- | - Reachable QUICKLY for operation, renewal, or inspection |
- | - NO portable ladders permitted |
- | - NO climbing over obstacles or moving heavy equipment |
- | - NO resorting to portable tools to gain access |
- +-------------------------------------------------------------------------+
- |
- v
- +-------------------------------------------------------------------------+
- | ACCESSIBLE (As Applied to Equipment) |
- | - Admitting close approach; not guarded by locked doors or elevation |
- | - May require opening an access door or stepping onto a fixed platform |
- +-------------------------------------------------------------------------+
- |
- v
- +-------------------------------------------------------------------------+
- | ACCESSIBLE (As Applied to Wiring Methods) (e.g., Junction Boxes) |
- | - Capable of being exposed without damaging building structure |
- | - Installed behind removable lay-in ceiling tiles or access panels |
- +-------------------------------------------------------------------------+
Key Application Examples:
Overcurrent Devices (240.24): Circuit breakers and fuses must be readily accessible . Installing a panelboard above a stairwell or behind heavy stock shelving violates the readily accessible rule.
Junction Boxes above Drop Ceilings (314.29): A junction box located above a lay-in suspended ceiling tile is accessible (as applied to wiring methods) because removing a ceiling tile does not damage the building structure. However, it is NOT readily accessible.
Circuit Hierarchy: Service, Feeder, & Branch Circuit
Electrical power distribution systems are divided into three distinct wiring tiers. Misidentifying where a circuit transitions from a feeder to a branch circuit leads to sizing errors on the exam. POWER DISTRIBUTION SYSTEM HIERARCHY
- Utility Power Source
- |
- v
- [ Service Point ]
- |
- | <--- SERVICE CONDUCTORS (From Service Point to Service Disconnect)
- v
- [ Service Disconnect / Main Panel ]
- |
- | <--- FEEDER CONDUCTORS (Between Service Equipment & Branch OCPD)
- v
- [ Distribution Subpanel ]
- |
- | <--- BRANCH CIRCUIT CONDUCTORS (From Final OCPD to Outlet)
- v
- [ Receptacle / Luminaire / Motor Outlet ]
- 1. Service Conductors
The conductors from the service point (utility connection point) to the service disconnecting means .
2. Feeder
All circuit conductors between the service equipment, the source of a separately derived system, or another power supply source and the final branch-circuit overcurrent device .
3. Branch Circuit
The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s) .
Branch Circuit Classifications:
General Purpose Branch Circuit: A branch circuit that supplies two or more receptacles or outlets for lighting and appliances.
Individual Branch Circuit: A branch circuit that supplies only one utilization equipment (e.g., a dedicated 50A circuit supplying a single electric range).
Appliance Branch Circuit: A branch circuit that supplies one or more outlets to which appliances are to be connected; no permanently connected luminaires.
Multiwire Branch Circuit: A branch circuit consisting of two or more ungrounded (hot) conductors that have a voltage potential between them, and a grounded (neutral) conductor having equal voltage potential between it and each ungrounded conductor of the circuit.
Grounding and Bonding Terminology
Understanding the distinct role of each grounding conductor is critical for Article 250 questions.
Grounding / Bonding Term Article 100 Definition & Function
Grounded Conductor A system or circuit conductor that is intentionally grounded (typically the neutral conductor carrying unbalanced return current).
Grounding Electrode Conductor (GEC) The conductor used to connect the system grounded conductor or equipment to a grounding electrode (ground rod, rebar/Ufer, water pipe).
Equipment Grounding Conductor (EGC) The conductive path(s) that provides a ground-fault current path and connects normally non-current-carrying metal parts of equipment to ground.
Bonding Jumper A reliable conductor to ensure the required electrical conductivity between metal parts required to be electrically connected.
Main Bonding Jumper (MBJ) The connection between the grounded circuit conductor (neutral) and the equipment grounding conductor at the service equipment .
System Bonding Jumper (SBJ) The connection between the grounded circuit conductor and the supply-side bonding jumper at a separately derived system (transformer).
- Load & Operational Definitions
- Continuous Load (CRITICAL EXAM CALCULATIONS)
A load where the maximum current is expected to continue for 3 hours or more .
Examples: Office building general lighting, store display lighting, commercial water heaters under 120 gallons (422.13).
Sizing Rule: Under 210.19(A), 215.2(A), and 240.4, branch circuit conductors and overcurrent protective devices supplying a continuous load must be sized at 125% of the continuous load + 100% of the non-continuous load. Minimum Rating = ( Continuous Load × 1.25 ) + Non-Continuous Load \text{Minimum Rating} = (\text{Continuous Load} \times 1.25) + \text{Non-Continuous Load} Minimum Rating = ( Continuous Load × 1.25 ) + Non-Continuous Load
Ampacity
The maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
Disconnecting Means
A device, or group of devices, or other means by which the conductors of a circuit can be disconnected from their source of supply.
In Sight From (Within Sight)
Where specified that one equipment shall be "in sight from", "within sight from", or "within sight of" another equipment, the specified equipment is to be visible and not more than 50 ft (15 m) distant from the other.
Important
Two-Part Test for 'In Sight From': Equipment is considered within sight ONLY IF it is physically visible AND located within 50 feet. If equipment is 40 feet away but behind a wall, it is NOT within sight. If it is visible down a straight hallway but 60 feet away, it is NOT within sight.