7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122)

Michigan Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview & NEC General Requirements

1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements

2 Chapter 2: Branch Circuits & Outlets

2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

3 Chapter 3: Load Calculations for Services & Feeders

3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations

4 Chapter 4: Wiring Methods, Conductors & Insulation

4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)

5 Chapter 5: Conduit Fill, Box Fill & Panelboards

5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)

6 Chapter 6: Overcurrent Protection Devices & Tap Rules

6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility

7 Chapter 7: Grounding & Bonding Systems

7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers

8 Chapter 8: Motors, Generators & Transformers

8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)

9 Chapter 9: Special Occupancies, Equipment & Conditions

9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)

10 Chapter 10: Michigan Electrical Law, Rules & Code Administration

10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ

11 Chapter 11: Electrical Theory & General Trade Knowledge

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math

12 Chapter 12: Services & Feeders (Articles 230 & 215)

12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements

13 Chapter 13: Lighting, Appliances & Power-Limited Circuits

13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)

7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122)

Key Takeaways Explain This Topic AI

NEC Table 250.122 dictates Equipment Grounding Conductor (EGC) sizing based strictly on the rating of the overcurrent protective device (fuse or circuit breaker) protecting the circuit.

Unlike GEC sizing, an EGC is never required to be larger than the circuit ungrounded conductors supplying the equipment (NEC 250.122(A)).

NEC 250.122(B) mandates that if ungrounded conductors are increased in size for voltage drop or distance, the EGC must be increased proportionally in circular mil area based on the original minimum conductor size required for circuit ampacity.

Under NEC 250.118, metal raceways such as RMC, IMC, and EMT are recognized as equipment grounding conductors; Flexible Metal Conduit (FMC) and Liquidtight FMC (LFMC) have strict length (max 6 ft) and OCPD rating (20A/30A) limits to serve as sole EGCs.

When conductors are run in parallel in multiple raceways per 250.122(F), a full-sized EGC based on the overall circuit OCPD rating must be installed in EACH parallel raceway.

Last updated: August 2026

7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122)

Exam Focus: EGC sizing per NEC Table 250.122, voltage drop proportional adjustment rule (250.122(B)), raceways permitted as EGCs (250.118), FMC/LFMC 6-ft limitations, and parallel circuit EGC sizing in multiple conduits (250.122(F)).

The primary function of an Equipment Grounding Conductor (EGC) is to connect non-current-carrying metal parts of equipment, raceways, and enclosures back to the system grounded conductor at the service disconnect or source of a separately derived system. This forms an effective ground-fault current path —a low-impedance circuit that facilitates the rapid operation of the overcurrent protective device (breaker or fuse) during a ground fault.

Equipment Grounding Conductor Sizing Table (NEC Table 250.122)

Unlike Grounding Electrode Conductors (which are sized per Table 250.66 based on conductor size), Equipment Grounding Conductors are sized per Table 250.122 based strictly on the rating of the automatic overcurrent protective device (OCPD) protecting the circuit.

Rating or Setting of Automatic Overcurrent Device Ahead of Equipment (Amperes) Size of Equipment Grounding Conductor (EGC)

  • Copper (Cu) Aluminum or Cu-Clad Al
  • 15 A 14 AWG 12 AWG
  • 20 A 12 AWG 10 AWG
  • 30 A or 60 A 10 AWG 8 AWG
  • 100 A 8 AWG 6 AWG
  • 200 A 6 AWG 4 AWG
  • 300 A 4 AWG 2 AWG
  • 400 A 3 AWG 1 AWG
  • 500 A 2 AWG 1/0 AWG
  • 600 A 1 AWG 2/0 AWG
  • 800 A 1/0 AWG 3/0 AWG
  • 1000 A 2/0 AWG 4/0 AWG
  • 1200 A 3/0 AWG 250 kcmil

Important

NEC 250.122(A) Limitation: An Equipment Grounding Conductor is never required to be larger than the ungrounded (phase) circuit conductors supplying the equipment.

Proportional Adjustment for Voltage Drop (NEC 250.122(B))

When ungrounded circuit conductors are increased in size to compensate for voltage drop or long distance runs, the equipment grounding conductor MUST be increased proportionally in circular mil area . VOLTAGE DROP EGC ADJUSTMENT STEPS

  • +-------------------------------------------------------------------------+
  • | Step 1: Identify Original Min Conductor Size for OCPD Ampacity (Table 310.16)|
  • | Step 2: Find Circular Mil (cmil) Area of Original & Upsized Conductors |
  • | Step 3: Compute Multiplier = (Upsized cmil Area) / (Original cmil Area) |
  • | Step 4: Multiply Table 250.122 Min EGC cmil Area by Multiplier |
  • | Step 5: Select Final EGC Size from NEC Chapter 9, Table 8 |
  • +-------------------------------------------------------------------------+
  • Worked Calculation Example: Voltage Drop Adjustment

Scenario: A 100A 208V 3-phase feeder circuit is protected by a 100A circuit breaker. Due to a long 350-foot run, the phase conductors are increased from 3 AWG THHN Copper (standard for 100A) to 1/0 AWG THHN Copper . What minimum size copper EGC must be installed?

Step 1: Determine Circular Mil (cmil) Areas (NEC Chapter 9, Table 8):

Original conductor for 100A (3 AWG Cu) = 52,620 cmil .

Upsized conductor installed (1/0 AWG Cu) = 105,600 cmil .

Minimum Table 250.122 EGC for 100A OCPD (8 AWG Cu) = 16,510 cmil .

Step 2: Calculate Upsize Proportional Multiplier: Multiplier = 105 , 600 cmil 52 , 620 cmil = 2.0068 \text{Multiplier} = \frac{105,600\text{ cmil}}{52,620\text{ cmil}} = 2.0068 Multiplier = 52 , 620 cmil 105 , 600 cmil ​ = 2.0068

Step 3: Calculate Required EGC Circular Mil Area: New EGC cmil = 16 , 510 cmil × 2.0068 = 33 , 133 cmil \text{New EGC cmil} = 16,510\text{ cmil} \times 2.0068 = 33,133\text{ cmil} New EGC cmil = 16 , 510 cmil × 2.0068 = 33 , 133 cmil

Step 4: Select EGC Conductor Size from Chapter 9, Table 8:

6 AWG Cu = 26,240 cmil (Too small!).

4 AWG Cu = 41,740 cmil (Sufficient!).

Conclusion: The equipment grounding conductor must be increased from 8 AWG Cu to 4 AWG Cu .

Permitted Equipment Grounding Conductors (NEC 250.118)

NEC 250.118 lists fourteen acceptable types of equipment grounding conductors, including wire-type conductors and metallic raceways. METALLIC RACEWAYS AS EGCs (NEC 250.118)

  • +-------------------------------------------------------------------------+
  • | PERMITTED WITHOUT LENGTH LIMITATION: |
  • | - Rigid Metal Conduit (RMC) |
  • | - Intermediate Metal Conduit (IMC) |
  • | - Electrical Metallic Tubing (EMT) |
  • +-------------------------------------------------------------------------+
  • | STRICTLY LIMITED (Max 6 ft length & Max 20A/30A OCPD): |
  • | - Flexible Metal Conduit (FMC): Max 6 ft ground path, max 20A OCPD. |
  • | - Liquidtight FMC (LFMC): Max 6 ft ground path; max 20A (3/8"-1/2") or |
  • | max 30A (3/4"-1-1/4") OCPD. |
  • +-------------------------------------------------------------------------+
  • Detailed FMC and LFMC Grounding Limitations

Flexible Metal Conduit (FMC) (250.118(5)): Permitted as sole EGC only if:

Total length in any ground return path does NOT exceed 6 ft (1.8 m) .

Circuit conductors contained are protected by OCPD rated 20 amperes or less .

Conduit is terminated in listed fittings.

Liquidtight Flexible Metal Conduit (LFMC) (250.118(6)): Permitted as sole EGC only if:

Total length in ground return path does NOT exceed 6 ft (1.8 m) .

For 3/8 in. and 1/2 in. trade size: OCPD rated 20 amperes or less .

For 3/4 in. through 1-1/4 in. trade size: OCPD rated 30 amperes or less .

If LFMC length exceeds 6 ft or OCPD exceeds 20A/30A, an equipment bonding jumper or wire EGC MUST be installed!

EGC Sizing in Parallel Circuits (NEC 250.122(F))

Caution

Critical Parallel EGC Rule: When conductors are run in parallel in multiple raceways or cables per NEC 310.10(G), a full-sized Equipment Grounding Conductor must be installed in EACH raceway or cable assembly .

The EGC in each parallel conduit is sized based on the total rating of the overcurrent protective device protecting the entire parallel circuit.

Example: An 800A feeder is installed in two parallel 4-inch PVC conduits. Table 250.122 requires a 1/0 AWG Copper EGC for an 800A OCPD. You must install a full-sized 1/0 AWG Copper EGC inside EACH of the two conduits (you cannot split it into 2 AWG in each conduit!).