3.4 Commercial & Non-Dwelling Load Calculations
Michigan Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview & NEC General Requirements
1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements
2 Chapter 2: Branch Circuits & Outlets
2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)
3 Chapter 3: Load Calculations for Services & Feeders
3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations
4 Chapter 4: Wiring Methods, Conductors & Insulation
4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
5 Chapter 5: Conduit Fill, Box Fill & Panelboards
5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)
6 Chapter 6: Overcurrent Protection Devices & Tap Rules
6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility
7 Chapter 7: Grounding & Bonding Systems
7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers
8 Chapter 8: Motors, Generators & Transformers
8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)
9 Chapter 9: Special Occupancies, Equipment & Conditions
9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)
10 Chapter 10: Michigan Electrical Law, Rules & Code Administration
10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ
11 Chapter 11: Electrical Theory & General Trade Knowledge
11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math
12 Chapter 12: Services & Feeders (Articles 230 & 215)
12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements
13 Chapter 13: Lighting, Appliances & Power-Limited Circuits
13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)
3.4 Commercial & Non-Dwelling Load Calculations
Key Takeaways Explain This Topic AI
Show window lighting must be calculated at a minimum of 200 VA per linear foot of show window measured horizontally along its base.
General receptacle loads in non-dwelling occupancies are calculated at 180 VA per yoke under 220.14(I) and may then be reduced under 2023 NEC 220.47 (numbered 220.44 in the 2020 NEC): 100% of the first 10 kVA and 50% of the remainder.
Feeder and service demand calculations for motor loads must include 125% of the full-load current (FLA) rating of the largest motor plus 100% of all other motor FLA ratings (NEC 220.50 & 430.24).
Commercial kitchen equipment feeder loads use Table 220.56 demand factors ranging from 100% for 1-2 units down to 65% for 6 or more units.
Last updated: August 2026
3.4 Commercial & Non-Dwelling Load Calculations
Commercial and non-dwelling installations present unique load calculation challenges compared to residential systems. In commercial environments—such as retail stores, office buildings, restaurants, and schools—electrical loads involve continuous lighting, extensive show windows, heavy receptacle density, commercial kitchen appliances, and large electric motors. Part IV of NEC Article 220 governs these non-dwelling service and feeder calculations.
- 1. Commercial Lighting & Special Outlet Calculations
- Continuous Lighting Loads (NEC 215.2 & 230.42)
In commercial occupancies, lighting routinely operates for 3 hours or more continuously. Under the NEC, continuous loads must be calculated at 125% (1.25) of the unadjusted load when sizing branch circuits, feeders, and service conductors.
Show Window Lighting (NEC 220.14(G) and the show-window rule in Article 220, Part III)
For show windows in commercial occupancies, Article 220 Part III requires calculating the lighting load using one of two options:
Linear Foot Rule: Minimum 200 VA per linear foot of show window measured horizontally along its base.
Outlets Rule: 180 VA per receptacle outlet installed for show window lighting. Show Window Load (VA) = Linear Feet of Show Window × 200 VA/ft \text{Show Window Load (VA)} = \text{Linear Feet of Show Window} \times 200\text{ VA/ft} Show Window Load (VA) = Linear Feet of Show Window × 200 VA/ft
Track Lighting Load (Article 220, Part III)
In non-dwelling occupancies, branch-circuit and feeder calculations for track lighting must include an allowance of 150 VA for every 2 feet (or fraction thereof) of track lighting installed: Track Lighting Load (VA) = ⌈ Track Length (ft) 2 ⌉ × 150 VA \text{Track Lighting Load (VA)} = \left\lceil \frac{\text{Track Length (ft)}}{2} \right\rceil \times 150\text{ VA} Track Lighting Load (VA) = ⌈ 2 Track Length (ft) ⌉ × 150 VA +-----------------------------------------------------------------------+
- | SPECIAL COMMERCIAL OUTLET LOAD SUMMARY |
- | |
- | Show Window Lighting ---> 200 VA per Linear Foot |
- | Track Lighting (Commercial)--> 150 VA per 2 Feet of Track |
- | Heavy-Duty Lampholders ---> 600 VA per Outlet (220.14(E)) |
- | Commercial Signs ---> 1,200 VA Minimum per Outlet (600.5) |
- +-----------------------------------------------------------------------+
- 2. Commercial Receptacle Demand Factors (NEC 220.47)
In non-dwelling occupancies, general convenience receptacles calculated at 180 VA per yoke under NEC 220.14(I) may be reduced using the demand factors permitted by NEC 220.47 — the section numbered 220.44 in the 2020 NEC.
Non-Dwelling Receptacle Demand Factor Schedule (2023 NEC 220.47)
- Portion of Receptacle Load (VA) Demand Factor (%)
- First 10 kVA (10,000 VA) or less 100%
- Remainder over 10 kVA (10,000 VA) 50%
Alternative Office / Bank Method (NEC 220.14(J)): In office buildings and banks, receptacle loads can optionally be included with the general lighting load at 1.0 VA/sq ft for offices or 1.0 VA/sq ft for banks, rather than counting individual yokes at 180 VA.
3. Commercial Motor Loads (NEC 220.50 & 430.24)
When sizing feeders and service conductors that supply motor loads, NEC 220.50 refers to Article 430 rules:
Largest Motor Rule (NEC 430.24): Add 125% (1.25) of the full-load current (FLA) rating of the largest motor to the sum of the full-load current ratings of all other motors served by the feeder. Total Motor Feeder Current = ( 1.25 × FLA largest ) + ∑ FLA other motors \text{Total Motor Feeder Current} = (1.25 \times \text{FLA}_{\text{largest}}) + \sum \text{FLA}_{\text{other motors}} Total Motor Feeder Current = ( 1.25 × FLA largest ) + ∑ FLA other motors
- 4. Specialized Occupancy & Kitchen Equipment Demand Factors
- Commercial Kitchen Equipment (NEC Table 220.56)
For commercial electric cooking equipment, dishwashers, water heaters, and other kitchen equipment in restaurants or institutional cafeterias, NEC Table 220.56 permits demand reductions based on the total number of equipment units:
- Number of Units of Kitchen Equipment Demand Factor (%)
- 1 to 2 units 100%
- 3 units 90%
- 4 units 80%
- 5 units 70%
- 6 or more units 65%
Rule Note: The demanded kitchen equipment load must not be less than the sum of the two largest kitchen equipment items!
5. Comprehensive Worked Commercial Example
Building Details:
A commercial retail clothing store measures 50 ft × 80 ft ( 4 , 000 sq ft 4,000\text{ sq ft} 4 , 000 sq ft ) with a 208Y/120V 3-phase, 4-wire supply system. The store features:
- Show Window: 30 linear feet 30\text{ linear feet} 30 linear feet
- Receptacles: 50 duplex receptacle yokes
- Track Lighting: 30 feet 30\text{ feet} 30 feet of continuous track
HVAC Motor Loads: 3-phase compressor motor ( 18 A 18\text{ A} 18 A FLA) and exhaust fan motor ( 6 A 6\text{ A} 6 A FLA)
Step-by-Step Calculation:
Step 1: General Store Lighting Load (NEC 220.42 / Table 220.42(A)) Floor Area = 50 × 80 = 4 , 000 sq ft \text{Floor Area} = 50 \times 80 = 4,000\text{ sq ft} Floor Area = 50 × 80 = 4 , 000 sq ft
A clothing store is a retail occupancy under the notes to Table 220.42(A), and the retail unit load in the 2023 NEC is 1.9 VA/sq ft 1.9\text{ VA/sq ft} 1.9 VA/sq ft : Lighting Load = 4 , 000 sq ft × 1.9 VA/sq ft = 7 , 600 VA \text{Lighting Load} = 4,000\text{ sq ft} \times 1.9\text{ VA/sq ft} = \mathbf{7,600\text{ VA}} Lighting Load = 4 , 000 sq ft × 1.9 VA/sq ft = 7 , 600 VA
Do not apply 125% again. A note to Table 220.42(A) states that the 125% continuous-load multiplier of 210.20(A) is already included in the tabulated unit loads.
Step 2: Show Window Lighting Load Base Show Window Load = 30 ft × 200 VA/ft = 6 , 000 VA \text{Base Show Window Load} = 30\text{ ft} \times 200\text{ VA/ft} = 6,000\text{ VA} Base Show Window Load = 30 ft × 200 VA/ft = 6 , 000 VA
Apply Continuous Load Factor ( 125 % 125\% 125% ): Show Window Load = 6 , 000 VA × 1.25 = 7 , 500 VA \text{Show Window Load} = 6,000\text{ VA} \times 1.25 = \mathbf{7,500\text{ VA}} Show Window Load = 6 , 000 VA × 1.25 = 7 , 500 VA
Step 3: Track Lighting Load Track Intervals = 30 ft 2 ft = 15 intervals \text{Track Intervals} = \frac{30\text{ ft}}{2\text{ ft}} = 15\text{ intervals} Track Intervals = 2 ft 30 ft = 15 intervals Base Track Load = 15 × 150 VA = 2 , 250 VA \text{Base Track Load} = 15 \times 150\text{ VA} = 2,250\text{ VA} Base Track Load = 15 × 150 VA = 2 , 250 VA
Apply Continuous Load Factor ( 125 % 125\% 125% ): Track Lighting Load = 2 , 250 VA × 1.25 = 2 , 812.5 VA \text{Track Lighting Load} = 2,250\text{ VA} \times 1.25 = \mathbf{2,812.5\text{ VA}} Track Lighting Load = 2 , 250 VA × 1.25 = 2 , 812.5 VA
Step 4: Receptacle Load & 220.47 Demand Total Unadjusted Receptacle Load = 50 yokes × 180 VA = 9 , 000 VA \text{Total Unadjusted Receptacle Load} = 50\text{ yokes} \times 180\text{ VA} = 9,000\text{ VA} Total Unadjusted Receptacle Load = 50 yokes × 180 VA = 9 , 000 VA
Apply 220.47: since 9 , 000 VA 9,000\text{ VA} 9 , 000 VA is less than 10 , 000 VA 10,000\text{ VA} 10 , 000 VA , it is demanded at 100% : Demanded Receptacle Load = 9 , 000 VA \text{Demanded Receptacle Load} = \mathbf{9,000\text{ VA}} Demanded Receptacle Load = 9 , 000 VA
Step 5: Commercial Motor Load Calculation (NEC 430.24)
For a 208V 3-phase system ( VA = 3 × 208 V × Amperes = 360.25 × Amperes \text{VA} = \sqrt{3} \times 208\text{V} \times \text{Amperes} = 360.25 \times \text{Amperes} VA = 3 × 208 V × Amperes = 360.25 × Amperes ):
Largest Motor ( 18 A 18\text{ A} 18 A FLA) at 125 % 125\% 125% : 18 A × 1.25 = 22.5 A 18\text{ A} \times 1.25 = 22.5\text{ A} 18 A × 1.25 = 22.5 A
Fan Motor ( 6 A 6\text{ A} 6 A FLA) at 100 % 100\% 100% : 6 A 6\text{ A} 6 A
Total Motor Feeder Current: 22.5 + 6.0 = 28.5 Amperes 22.5 + 6.0 = 28.5\text{ Amperes} 22.5 + 6.0 = 28.5 Amperes
Motor Volt-Amperes: 28.5 A × 208 V × 3 = 10 , 267 VA 28.5\text{ A} \times 208\text{ V} \times \sqrt{3} = \mathbf{10,267\text{ VA}} 28.5 A × 208 V × 3 = 10 , 267 VA
Step 6: Total Commercial Feeder Load & Line Current Total Calculated Load = 7 , 600 + 7 , 500 + 2 , 812.5 + 9 , 000 + 10 , 267 = 37 , 179.5 VA \text{Total Calculated Load} = 7,600 + 7,500 + 2,812.5 + 9,000 + 10,267 = \mathbf{37,179.5\text{ VA}} Total Calculated Load = 7 , 600 + 7 , 500 + 2 , 812.5 + 9 , 000 + 10 , 267 = 37 , 179.5 VA Line Amperes (3-Phase 208V) = 37 , 179.5 VA 208 V × 3 = 37 , 179.5 360.25 = 103.2 Amperes \text{Line Amperes (3-Phase 208V)} = \frac{37,179.5\text{ VA}}{208\text{ V} \times \sqrt{3}} = \frac{37,179.5}{360.25} = \mathbf{103.2\text{ Amperes}} Line Amperes (3-Phase 208V) = 208 V × 3 37 , 179.5 VA = 360.25 37 , 179.5 = 103.2 Amperes
Result: Requires a minimum 125-Ampere 208Y/120V 3-phase main distribution panel . Notice how much smaller the service became once the rebuilt Table 220.42(A) unit load replaced the legacy 3.0 VA/sq ft 3.0\text{ VA/sq ft} 3.0 VA/sq ft store value — this is precisely why answering from an obsolete table produces a wrong answer.