6.3 Feeder & Transformer Tap Rules (NEC 240.21)

Michigan Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview & NEC General Requirements

1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements

2 Chapter 2: Branch Circuits & Outlets

2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)

3 Chapter 3: Load Calculations for Services & Feeders

3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations

4 Chapter 4: Wiring Methods, Conductors & Insulation

4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)

5 Chapter 5: Conduit Fill, Box Fill & Panelboards

5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)

6 Chapter 6: Overcurrent Protection Devices & Tap Rules

6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility

7 Chapter 7: Grounding & Bonding Systems

7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers

8 Chapter 8: Motors, Generators & Transformers

8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)

9 Chapter 9: Special Occupancies, Equipment & Conditions

9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)

10 Chapter 10: Michigan Electrical Law, Rules & Code Administration

10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ

11 Chapter 11: Electrical Theory & General Trade Knowledge

11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math

12 Chapter 12: Services & Feeders (Articles 230 & 215)

12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements

13 Chapter 13: Lighting, Appliances & Power-Limited Circuits

13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)

6.3 Feeder & Transformer Tap Rules (NEC 240.21)

Key Takeaways Explain This Topic AI

NEC 240.21 mandates that overcurrent protection be located at the point where conductors receive their supply, unless specific tap rules under 240.21(B) or (C) are satisfied.

A feeder tap conductor is defined in NEC 240.2 as a conductor with overcurrent protection ahead of its supply point that exceeds the value specified for its ampacity.

The 10-Foot Feeder Tap Rule (240.21(B)(1)) requires tap conductor ampacity to be not less than the calculated load, not less than 10% (1/10th) of the feeder OCPD rating, enclosed in a raceway, and terminated in a single OCPD.

The 25-Foot Feeder Tap Rule (240.21(B)(2)) requires tap conductor ampacity to be not less than 1/3 (33.33%) of the feeder OCPD rating, protected from physical damage, and terminated in a single OCPD sized for the tap ampacity.

Under transformer secondary tap rules (NEC 240.21(C)), primary OCPDs cannot protect secondary conductors unless it is a 3-wire single-phase or 3-phase delta-delta transformer with a 2-wire primary/secondary setup meeting 240.4(F); all other secondary taps must follow 240.21(C) rules.

Last updated: August 2026

6.3 Feeder & Transformer Tap Rules (NEC 240.21)

Exam Focus: Point of supply rule (240.21), definition of tap conductor (240.2), 10-foot feeder tap rule (240.21(B)(1)), 25-foot feeder tap rule (240.21(B)(2)), 100-foot high-bay tap rule (240.21(B)(3)), and transformer secondary tap rules (240.21(C)).

The general overcurrent protection rule in NEC 240.21 states that an overcurrent protective device must be installed at the point where a conductor receives its supply. If a smaller conductor is spliced or tapped onto a larger feeder conductor, the upstream breaker is too large to protect the smaller wire under standard rules. To avoid installing costly main fused disconnects at every splice point, the NEC provides specific Tap Rules under NEC 240.21(B) and 240.21(C).

What is a Tap Conductor? (NEC 240.2 Definition)

NEC 240.2 Definition: A tap conductor is a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply that exceeds the value specified in Part III of Article 240 for the conductor ampacity. ANATOMY OF A FEEDER TAP

  • +-------------------------------------------------------------------------+
  • | Main Distribution Feeder (e.g., 400A Breaker / 500 kcmil Wire) |
  • | ========================= SPLICED TAP POINT ========================== |
  • | | |
  • | Tap Conductor (e.g., 1/0 AWG Wire) |
  • | Length <= 10 ft or <= 25 ft |
  • | | |
  • | Single Terminating OCPD |
  • | (e.g., 125A Main Breaker Panel) |
  • +-------------------------------------------------------------------------+
  • The 10-Foot Feeder Tap Rule (NEC 240.21(B)(1))

Feeder tap conductors not over 3.0 meters (10 feet) in length are permitted without overcurrent protection at the point of supply, provided ALL five of the following conditions are met:

Calculated Load: The ampacity of the tap conductor is not less than the combined calculated loads on the circuits supplied by the tap conductors.

10% Feeder Rating Rule: The ampacity of the tap conductor is not less than 10% (1/10th) of the rating of the overcurrent device protecting the feeder conductors.

Raceway Enclosure: The tap conductors do not extend beyond the switchboard, panelboard, disconnecting means, or control devices they supply, and are enclosed in an approved raceway (conduit, tubing, or wireway).

Termination Device: The tap conductors terminate in a single circuit breaker or single set of fuses that limits the load to the ampacity of the tap conductors (or a main breaker in a panelboard).

Physical Limits: The tap conductors do not leave the enclosure or room except when enclosed in a raceway.

The 25-Foot Feeder Tap Rule (NEC 240.21(B)(2))

Feeder tap conductors not over 7.5 meters (25 feet) in length are permitted without overcurrent protection at the point of supply, provided ALL four of the following conditions are met:

1/3 Feeder Rating Rule: The ampacity of the tap conductor is not less than 1/3 (33.33%) of the rating of the overcurrent device protecting the feeder conductors.

Physical Protection: The tap conductors are protected from physical damage by being enclosed in an approved raceway or by other approved means.

Single OCPD Termination: The tap conductors terminate in a single circuit breaker or set of fuses having a rating NOT greater than the ampacity of the tap conductors.

Length Restriction: The total length of the tap conductor does not exceed 25 feet. 10-FOOT VS. 25-FOOT TAP RULE COMPARISON

  • +-----------------------------------+-----------------------------------+
  • | 10-FOOT TAP RULE (240.21(B)(1)) | 25-FOOT TAP RULE (240.21(B)(2)) |
  • +-----------------------------------+-----------------------------------+
  • | Max Length: 10 Feet (3.0 m) | Max Length: 25 Feet (7.5 m) |
  • | Min Ampacity: >= 10% Feeder OCPD | Min Ampacity: >= 33.33% (1/3) OCPD|
  • | Min Ampacity: >= Calculated Load | Physical damage protection mandatory|
  • | Enclosed in raceway/enclosure | Terminates in single OCPD <= Wire |
  • | Terminates in single OCPD | Ampacity |
  • +-----------------------------------+-----------------------------------+
  • Specialized Feeder Tap Rules
  • 1. 100-Foot High-Bay Industrial Tap Rule (NEC 240.21(B)(3))

In high-bay industrial manufacturing buildings with walls over 35 feet high, tap conductors up to 100 feet long are permitted IF:

Conditions of maintenance and supervision ensure only qualified persons service the system.

The tap ampacity is at least 1/3 (33.33%) of the feeder OCPD rating.

The horizontal length of the tap does not exceed 25 feet, and total length does not exceed 100 feet.

Conductors are enclosed in raceways and terminate in a single OCPD.

2. Outside Feeder Taps of Unlimited Length (NEC 240.21(B)(5))

Outside taps may be of unlimited length without OCPD at the supply point IF:

Conductors are suitably protected from physical damage.

Conductors terminate in a single OCPD that limits load to wire ampacity.

The OCPD is located outdoors or inside near the point of conductor entrance.

Transformer Secondary Tap Rules (NEC 240.21(C))

Warning

Primary Overcurrent Protection Trap (NEC 240.4(F)): Primary overcurrent devices CANNOT protect secondary conductors unless the transformer is 2-wire primary to 2-wire secondary, or 3-phase delta-delta (3-wire to 3-wire). For standard 480V to 208Y/120V 3-phase 4-wire transformers, primary breakers DO NOT protect secondary conductors! Secondary conductors must follow 240.21(C).

10-Foot Transformer Secondary Tap Rule (NEC 240.21(C)(2))

Secondary conductors of a transformer do not require overcurrent protection at the transformer secondary terminals if length is ≤ 10 ft \le 10\text{ ft} ≤ 10 ft and:

Secondary conductor ampacity ≥ \ge ≥ calculated load.

Secondary ampacity multiplied by the primary-to-secondary voltage ratio is ≥ 10 % ( 1 / 10 th ) \ge 10\% (1/10\text{th}) ≥ 10% ( 1/10 th ) of the primary OCPD rating: Min Secondary Ampacity ≥ Primary OCPD Rating 10 × ( V primary V secondary ) \text{Min Secondary Ampacity} \ge \frac{\text{Primary OCPD Rating}}{10} \times \left( \frac{V_{\text{primary}}}{V_{\text{secondary}}} \right) Min Secondary Ampacity ≥ 10 Primary OCPD Rating ​ × ( V secondary ​ V primary ​ ​ )

Secondary conductors terminate in a single OCPD sized ≤ \le ≤ secondary conductor ampacity.

  • Step-by-Step Worked Tap Calculation Examples
  • Example 1: 10-Foot Feeder Tap Calculation

Scenario: A 400A circuit breaker protects a 3-phase feeder. A 10-foot tap is made to supply a small subpanel with a calculated load of 32A. What is the minimum size copper THHN conductor (75°C terminals) required for the tap?

Rule 1: Check 10% Feeder OCPD Rule: Min Ampacity = 400 A × 0.10 = 40 Amperes \text{Min Ampacity} = 400\text{ A} \times 0.10 = 40\text{ Amperes} Min Ampacity = 400 A × 0.10 = 40 Amperes

Rule 2: Check Calculated Load: Load = 32A.

Select Conductor: The required ampacity is the larger of 40A or 32A → \rightarrow → 40 Amperes .

Table 310.16 (75°C Column):

10 AWG Cu = 35A (too small).

8 AWG Cu = 50A (compliant).

Terminating OCPD: The subpanel must be equipped with a main breaker rated 50A or less to protect the 8 AWG wire.

Example 2: 25-Foot Feeder Tap Calculation

Scenario: A 400A feeder breaker supplies a distribution trough. A 22-foot feeder tap is run in EMT to supply a disconnect switch. What is the minimum required copper THHN wire size and maximum terminating fuse size?

Rule 1: Check 1/3 Feeder OCPD Rule: Min Ampacity = 400 A × 1 3 = 133.33 Amperes \text{Min Ampacity} = 400\text{ A} \times \frac{1}{3} = 133.33\text{ Amperes} Min Ampacity = 400 A × 3 1 ​ = 133.33 Amperes

Select Conductor (Table 310.16 75°C Column):

1/0 AWG Cu = 150A (exceeds 133.33A requirement).

Terminating OCPD: The disconnect switch fuses must be rated 150A or less (matching 1/0 AWG ampacity).

Loading diagram... NEC 240.21 Feeder Tap Rules Comparison (400A Feeder Example)