4.3 Cable Assemblies (NM-B, MC, UF)
Michigan Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview & NEC General Requirements
1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements
2 Chapter 2: Branch Circuits & Outlets
2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)
3 Chapter 3: Load Calculations for Services & Feeders
3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations
4 Chapter 4: Wiring Methods, Conductors & Insulation
4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
5 Chapter 5: Conduit Fill, Box Fill & Panelboards
5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)
6 Chapter 6: Overcurrent Protection Devices & Tap Rules
6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility
7 Chapter 7: Grounding & Bonding Systems
7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers
8 Chapter 8: Motors, Generators & Transformers
8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)
9 Chapter 9: Special Occupancies, Equipment & Conditions
9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)
10 Chapter 10: Michigan Electrical Law, Rules & Code Administration
10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ
11 Chapter 11: Electrical Theory & General Trade Knowledge
11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math
12 Chapter 12: Services & Feeders (Articles 230 & 215)
12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements
13 Chapter 13: Lighting, Appliances & Power-Limited Circuits
13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)
4.3 Cable Assemblies (NM-B, MC, UF)
Key Takeaways Explain This Topic AI
Nonmetallic-Sheathed Cable (Type NM-B) governed by NEC Article 334 requires ampacity sizing based exclusively on the 60°C column of Table 310.16 per NEC 334.80, regardless of the 90°C conductor insulation inside.
Type NM-B cable is permitted in Type III, IV, and V building construction, but is strictly prohibited in Type I and II fire-resistive construction unless installed inside approved raceways per NEC 334.10.
NM-B cable must be secured within 12 inches of every cabinet, box, or fitting (or 8 inches for plastic boxes without cable clamps) and supported at intervals not exceeding 4.5 feet per NEC 334.30.
Metal-Clad Cable (Type MC) governed by NEC Article 330 permits full 90°C conductor ampacity ratings for derating and 75°C terminal usage, and must be secured within 12 inches of boxes and supported at intervals not exceeding 6 feet per NEC 330.30.
NEC 300.4 requires steel nail safety plates at least 1/16 inch thick where cables pass through wood framing holes or notches located less than 1-1/4 inches from the nearest framing edge.
Last updated: August 2026
4.3 Cable Assemblies (NM-B, MC, UF)
Exam Focus: Article 334 (NM-B ampacity & support rules), Article 330 (MC cable installation & fittings), Article 340 (UF-B burial depths & ratings), and NEC 300.4 physical protection (nail plates).
Field wiring often relies on factory-assembled cable packages containing phase, neutral, and equipment grounding conductors bundled inside a protective outer sheath. The three most widely tested cable assemblies on the Michigan licensing exam are Nonmetallic-Sheathed Cable (Type NM-B) , Metal-Clad Cable (Type MC) , and Underground Feeder Cable (Type UF-B) .
Nonmetallic-Sheathed Cable (Type NM-B) — Article 334
Type NM-B (commonly referred to by the trade brand Romex) consists of two or more insulated conductors and a bare equipment grounding conductor encased in a flame-retardant nonmetallic outer sheath. +-------------------------------------------------------------------------+
- | TYPE NM-B CABLE ANATOMY & RULES |
- | |
- | [ Outer Flame-Retardant PVC Jacket ] |
- | +-- THHN 90°C Phase Conductor (Black) |
- | +-- THHN 90°C Neutral Conductor (White) |
- | +-- Bare Equipment Grounding Conductor (Cu) |
- | |
- | AMPACITY MANDATE (NEC 334.80): MUST use 60°C Column of Table 310.16 |
- +-------------------------------------------------------------------------+
- 1. Ampacity Limitation — NEC 334.80
Conductors inside NM-B are manufactured with 90°C rated insulation (THHN).
CRITICAL CODE RULE: Under NEC 334.80 , the allowable ampacity of Type NM cable shall NOT exceed that of a 60°C rated conductor in Table 310.16.
Derating Exception: The 90°C rating MAY be used as the starting base ampacity ( I base I_{\text{base}} I base ) when calculating ambient temperature or bundle derating factors, provided the final adjusted ampacity does not exceed the 60°C rating.
2. Permitted & Prohibited Building Construction Types — NEC 334.10 & 334.12
Permitted Uses: One- and two-family dwellings, multi-family dwellings, and other structures classified as Type III, IV, and V construction (wood-frame or non-combustible exterior wall construction).
Prohibited Uses: Commercial structures of Type I and II construction (fire-resistive steel/concrete construction), commercial garages, theaters, places of assembly (over 100 persons occupancy), motion picture studios, damp or wet locations, or exposed inside drop ceiling spaces in commercial buildings.
3. Support & Securing Rules — NEC 334.30
Must be secured within 12 inches (300 mm) of every cabinet, box, fitting, or termination.
Exception: Nonmetallic single-gang boxes without internal cable clamps permit securing within 8 inches (200 mm) of the box.
Must be supported at intervals not exceeding 4.5 feet (1.4 m) along runs.
Staples must be installed flat and tight without crushing the outer sheath.
Metal-Clad Cable (Type MC Cable) — Article 330
Type MC cable features insulated conductors enclosed in a flexible, interlocked armor tape (aluminum or steel) or a smooth/corrugated metallic sheath.
1. Construction & Advantages over NM-B
Permitted in Type I, II, III, IV, and V construction , commercial drop ceilings, places of assembly, and exposed or concealed runs.
Conductor insulation is rated 90°C (THHN/THWN-2).
Ampacity is based on Table 310.16 (75°C column for terminations per 110.14(C), and full 90°C column for ampacity derating calculations under NEC 330.80).
2. Support & Securing Rules — NEC 330.30
Must be secured within 12 inches (300 mm) of every box, cabinet, fitting, or termination.
Must be supported at intervals not exceeding 6 feet (1.8 m) .
Horizontal runs passing through wood or metal framing members are considered supported at 6-foot intervals.
3. Connectors & Anti-Short Bushings
Must be installed with listed MC cable connectors .
Anti-short bushings (red plastic sleeves, trade name "red devils") must be installed at armor cut ends where required by manufacturer listing and NECA standards.
Underground Feeder Cable (Type UF-B) — Article 340
Type UF cable is designed for direct earth burial and wet location installations. Its conductors are solidly embedded inside a continuous, solid moisture-resistant plastic compound.
1. Ampacity Rating — NEC 340.80
Type UF cable ampacity MUST be determined using the 60°C column of Table 310.16.
- 2. Direct Burial Depth Requirements — NEC Table 300.5 NEC TABLE 300.5 DIRECT BURIAL DEPTHS
- +-------------------------------------------------------------------------+
- | Wiring Method / Location | Minimum Cover |
- +---------------------------------------------------------+---------------+
- | Direct Burial UF Cable (No raceway or concrete envelope)| 24 Inches |
- | Rigid Metal Conduit (RMC) or Intermediate Metal (IMC) | 6 Inches |
- | Nonmetallic Raceway (PVC Schedule 40/80) Direct Burial | 18 Inches |
- | Residential 120V 20A Branch Circuit w/ GFCI Protection | 12 Inches |
- | Under 4-Inch Concrete Building Slab (No vehicular traffic)| 4 Inches |
- | Under Commercial Driveways & Parking Lots (All methods) | 24 Inches |
- +---------------------------------------------------------+---------------+
Important
Physical Protection at Grade (NEC 300.5(D)): Where direct buried cables emerge from the ground, they must be protected against physical damage by a raceway (Schedule 80 PVC or RMC) extending from 18 inches below grade to a point at least 8 feet above finished grade .
Physical Protection of Cables — NEC 300.4
Cables installed through or parallel to structural framing members must be protected against mechanical damage caused by dry-wall screws and nails.
1. Framing Clearance & Nail Plate Rules (NEC 300.4(A))
Where cables pass through bored holes or notches in wood studs, joists, or rafters, the edge of the hole must be at least 1-1/4 inches (32 mm) from the nearest edge of the wood framing member.
If clearance is less than 1-1/4 inches , the cable must be protected by a steel plate at least 1/16 inch (1.6 mm) thick of suitable length and width. NAIL PLATE CLEARANCE REQUIREMENT
- +-------------------------------------------------------+
- | Edge of Stud |
- | | <-- Distance < 1-1/4 in. --> [ Bored Hole w/ Cable] |
- | | |
- | Steel Nail Plate (Min. 1/16 in. / 1.6mm thick) REQUIRED|
- +-------------------------------------------------------+
- 2. Metal Stud Installations (NEC 300.4(B))
Cables passing through factory or field-punched holes in metal studs must be protected by listed bushing or grommets securely fastened in the opening prior to pulling cable.
Cable Assembly Comparison Table
- Cable Specification Type NM-B (Art. 334) Type MC (Art. 330) Type UF-B (Art. 340)
- Ampacity Column 60°C Column Only 75°C / 90°C Columns 60°C Column Only
- Max Securing Distance 12 inches from box 12 inches from box 12 inches from box
- Max Support Spacing 4.5 feet (1.4 m) 6.0 feet (1.8 m) 4.5 feet (1.4 m)
- Direct Burial Allowed? NO (Dry only) NO (Unless jacketed) YES (24 in. cover)
- Type I/II Construction? Prohibited Permitted Prohibited