4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
Michigan Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview & NEC General Requirements
1.1 Michigan LARA Electrical Licensing & Exam Format 1.2 NEC Article 90 & Code Structure 1.3 NEC Article 100 Essential Definitions 1.4 NEC Article 110 General Installation Requirements
2 Chapter 2: Branch Circuits & Outlets
2.1 Branch Circuit Ratings & Conductor Sizing 2.2 GFCI Protection Requirements (NEC 210.8) 2.3 AFCI & Tamper-Resistant Outlets (NEC 210.12 & 406.12) 2.4 Receptacle Outlets & Dwelling Unit Spacing (NEC 210.52 & 210.11) 2.5 Switches, Receptacles & Wiring Devices (NEC Articles 404 & 406)
3 Chapter 3: Load Calculations for Services & Feeders
3.1 General Lighting & Receptacle Load Calculations 3.2 Fixed Appliance, Dryer, & Cooking Unit Loads 3.3 Dwelling Unit Service & Feeder Calculations 3.4 Commercial & Non-Dwelling Load Calculations
4 Chapter 4: Wiring Methods, Conductors & Insulation
4.1 Conductor Types & Ampacity Sizing 4.2 Ampacity Adjustment & Correction Factors 4.3 Cable Assemblies (NM-B, MC, UF) 4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
5 Chapter 5: Conduit Fill, Box Fill & Panelboards
5.1 Raceway Fill Calculations 5.2 Outlet & Junction Box Sizing (NEC 314.16(A)) 5.3 Box Fill Volume Deductions (NEC 314.16(B)) 5.4 Panelboards, Switchboards & Cabinets (NEC Article 408)
6 Chapter 6: Overcurrent Protection Devices & Tap Rules
6.1 Fuses & Circuit Breakers (NEC Article 240) 6.2 Small Conductor Rules & Protection Limits (NEC 240.4(D)) 6.3 Feeder & Transformer Tap Rules (NEC 240.21) 6.4 Location, Enclosures & Overcurrent Protection Accessibility
7 Chapter 7: Grounding & Bonding Systems
7.1 Grounding Electrode Systems & Electrodes (NEC 250.50 & 250.52) 7.2 Grounding Electrode Conductor (GEC) Sizing (NEC Table 250.66) 7.3 Equipment Grounding Conductors (EGC) Sizing (NEC Table 250.122) 7.4 Bonding Requirements & Main Bonding Jumpers
8 Chapter 8: Motors, Generators & Transformers
8.1 Motor Full-Load Current (FLA) & Conductor Sizing (NEC Article 430) 8.2 Motor Short-Circuit & Ground-Fault Protection (Table 430.52) 8.3 Motor Overload Protection & Disconnecting Means 8.4 Transformer Sizing, Protection & Installation (NEC Article 450)
9 Chapter 9: Special Occupancies, Equipment & Conditions
9.1 Hazardous (Classified) Locations (NEC Articles 500-516) 9.2 Commercial Garages, Service Stations & Healthcare Facilities (Articles 511, 514, 517) 9.3 Swimming Pools, Fountains & Equipotential Bonding (NEC Article 680) 9.4 Renewable Energy Systems & Generators (NEC Articles 690, 700, 702)
10 Chapter 10: Michigan Electrical Law, Rules & Code Administration
10.1 Skilled Trades Regulation Act: License Classes, Scope & Supervision 10.2 Licensure, Examination Eligibility, Retakes & Continuing Education 10.3 Michigan Electrical Code Part 8 Rules & the 2023 NEC Adoption 10.4 Michigan Amendments & Key 2023 NEC Changes Enforced in Michigan 10.5 Stille-DeRossett-Hale Act, Permits, Inspections & the AHJ
11 Chapter 11: Electrical Theory & General Trade Knowledge
11.1 Ohm's Law, Power Formulas & Series/Parallel Circuits 11.2 Alternating Current, Single-Phase & Three-Phase Systems 11.3 Power Factor, Efficiency & Transformer Theory 11.4 Voltage Drop, Conductor Resistance & Trade Math
12 Chapter 12: Services & Feeders (Articles 230 & 215)
12.1 Service Conductors, Clearances & Service-Entrance Requirements 12.2 Service Disconnecting Means, Overcurrent Protection & Service Grounding 12.3 Feeders: Sizing, Overcurrent Protection & Article 215 Requirements
13 Chapter 13: Lighting, Appliances & Power-Limited Circuits
13.1 Luminaires & Lighting Installations (NEC Article 410) 13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424) 13.3 Class 1, Class 2 & Class 3 Power-Limited Circuits (Articles 724 & 725) 13.4 Fire Alarm, Communications & Optical Fiber Systems (Articles 760, 770, 800-820)
4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
Key Takeaways Explain This Topic AI
Electrical Metallic Tubing (EMT) governed by NEC Article 358 must be supported within 3 feet of every box, cabinet, or fitting and at intervals not exceeding 10 feet per NEC 358.30.
Rigid Metal Conduit (RMC) governed by NEC Article 344 provides heavy-wall physical protection, utilizes standard NPT 3/4-inch taper per foot threads, and serves as an approved equipment grounding conductor.
Rigid Polyvinyl Chloride Conduit (PVC) under NEC Article 352 requires Schedule 80 in areas subject to physical damage, support spacing per Table 352.30, and expansion fittings per NEC 352.44 where thermal movement exceeds 0.25 inches.
Flexible Metal Conduit (FMC, Art. 348) and Liquidtight Flexible Metal Conduit (LFMC, Art. 350) must be secured within 12 inches of terminations and supported every 4.5 feet, with exceptions for lengths up to 3 feet at terminals where flexibility is required.
FMC and LFMC can only serve as the sole equipment grounding conductor in circuit sizes up to 20 amperes with a maximum length of 6 feet; larger circuits or longer lengths require an internal or external equipment bonding jumper per NEC 250.118, 348.60, and 350.60.
Last updated: August 2026
4.4 Raceways & Flexible Conduits (EMT, RMC, PVC, FMC)
Exam Focus: Support spacing for EMT (Article 358), RMC (Article 344), PVC (Article 352), FMC/LFMC (Articles 348/350), 360° total bend rules, PVC expansion fittings under 352.44, and flexible conduit grounding limits under NEC 250.118.
Raceway systems serve two primary electrical safety functions: they provide mechanical protection for enclosed conductors and, in the case of metallic raceways, often act as an equipment grounding path. The Michigan Journeyman examination heavily tests raceway support intervals, total allowable bends, ground continuity rules, and environmental suitability.
General Raceway Rules: 360° Bend Limit
For ALL conduit systems (EMT, RMC, IMC, PVC, FMC, LFMC), the total equivalent bend angle between pull points (boxes, cabinets, or conduit bodies) must NOT exceed 360 degrees (the equivalent of four 90-degree quarter bends). Total Bends = ∑ θ bends ≤ 360 ∘ \text{Total Bends} = \sum \theta_{\text{bends}} \le 360^\circ Total Bends = ∑ θ bends ≤ 36 0 ∘
Caution
Exceeding 360° between pull boxes causes severe insulation burn-through during conductor pulling and violates NEC 358.26, 344.26, 352.26, and 348.26.
Electrical Metallic Tubing (EMT) — Article 358
EMT is an unthreaded thin-wall metallic raceway commonly used in commercial and industrial interior wiring.
1. Support & Securing Rules — NEC 358.30
Must be securely fastened within 3 feet (900 mm) of each outlet box, junction box, cabinet, conduit body, or termination.
Must be supported at intervals not exceeding 10 feet (3.0 m) along runs.
Framing Exception: Where structural framing prevents securing within 3 feet, distance may be extended up to 5 feet (1.5 m) .
2. Wet Location Connectors
In wet locations, all couplings and connectors must be listed raintight compression type (NEC 358.42).
Rigid Metal Conduit (RMC) — Article 344
RMC is a heavy-wall threaded metallic raceway providing maximum mechanical protection.
1. Threading Specifications — NEC 344.28
Field threads must be cut using a standard NPT (National Pipe Taper) die with a taper of 3/4 inch per foot (1 in 16 taper).
Threaded joints must be made up wrench-tight. Field-cut threads must be coated with an electrically conductive anti-corrosion compound.
2. Support Spacing — NEC Table 344.30(B)(2) +-------------------------------------------------------------------------+
- | RMC STRAIGHT RUN SUPPORT SPACING TABLE |
- +------------------------------------+------------------------------------+
- | Trade Size | Maximum Support Spacing |
- +------------------------------------+------------------------------------+
- | 1/2 in. and 3/4 in. | 10 Feet (3.0 m) |
- | 1 in. | 12 Feet (3.7 m) |
- | 1-1/4 in. and 1-1/2 in. | 14 Feet (4.3 m) |
- | 2 in. and 2-1/2 in. | 16 Feet (4.9 m) |
- | 3 in. and larger | 20 Feet (6.0 m) |
- +------------------------------------+------------------------------------+
RMC must be supported within 3 feet (900 mm) of each box or termination.
Rigid Polyvinyl Chloride Conduit (PVC) — Article 352
PVC is a rigid nonmetallic raceway resistant to moisture, chemicals, and soil corrosion.
1. Schedule 40 vs. Schedule 80 Applications (NEC 352.10)
Schedule 40 PVC: Standard wall thickness approved for underground burial, concrete slabs, and aboveground areas not subject to physical damage.
Schedule 80 PVC: Heavy wall thickness REQUIRED where conduit is exposed to physical damage (e.g., lower sections of exterior pole risers or exposed industrial walls).
2. Thermal Expansion & Contraction — NEC 352.44
PVC has a high coefficient of thermal expansion ( 4.06 inches per 100 feet per 100 ∘ F 4.06 \text{ inches per } 100 \text{ feet per } 100^\circ\text{F} 4.06 inches per 100 feet per 10 0 ∘ F temp change).
Expansion Fittings Required: An expansion fitting must be installed whenever thermal expansion or contraction is expected to cause a length change of 0.25 inch (6 mm) or greater between fixed points.
3. Support Spacing — NEC Table 352.30
- PVC Trade Size Maximum Support Spacing
- 1/2 in. through 1 in. 3 Feet (900 mm)
- 1-1/4 in. through 2 in. 5 Feet (1.5 m)
- 2-1/2 in. through 3 in. 6 Feet (1.8 m)
- 3-1/2 in. through 5 in. 7 Feet (2.1 m)
- 6 in. 8 Feet (2.5 m)
- Flexible Metal Conduit (FMC) & Liquidtight Flexible Metal Conduit (LFMC)
FMC (Article 348) and LFMC (Article 350) provide flexibility for connecting motors, transformers, and vibrating equipment.
1. Support & Securing Rules (NEC 348.30 & 350.30)
Must be secured within 12 inches (300 mm) of each box, cabinet, or fitting.
Supported at intervals not exceeding 4.5 feet (1.4 m) .
Flexibility Exceptions: Unsupported lengths permitted up to 3 feet (900 mm) at terminals where flexibility is required for equipment vibration.
2. Equipment Grounding Limitations — NEC 250.118(5) & (6)
FMC or LFMC may serve as the sole equipment grounding conductor ONLY IF ALL of the following criteria are satisfied:
The flex conduit is terminated in listed fittings .
The trade size is 1/2 in. through 1-1/4 in.
The total ground return path length of flex in the circuit does NOT exceed 6 feet (1.8 m) .
Overcurrent protection for the circuit is rated 20 amperes or less . +-------------------------------------------------------------------------+
- | FMC / LFMC GROUNDING CONTINUITY DECISION MATRIX |
- +-------------------------------------------------------------------------+
- | Criteria Check: |
- | - Circuit Overcurrent Protection ≤ 20 Amperes? |
- | - Total Flex Length in Ground Path ≤ 6.0 Feet? |
- | - Listed Grounding Fittings Used? |
- +-------------------------------------------------------------------------+
- |
- +------------------+------------------+
- | YES | NO
- v v
- Flex Armor Acts as Sole EGC Equipment Bonding Jumper (EGC)
- (No internal wire EGC needed) MUST be Installed (250.118)
- +-------------------------------------------------------------------------+
Warning
If the circuit breaker is rated 30A, 40A, or 50A , or if the flex length is 8 feet , you MUST pull an internal copper Equipment Grounding Conductor (EGC) through the flex!
Master Raceway Summary Comparison Table
- Raceway Type NEC Article Max Securing Distance Max Support Spacing (1/2" - 1") Grounding Rating
- EMT Art. 358 3 Feet 10 Feet Approved EGC
- RMC Art. 344 3 Feet 10 Feet (12' for 1") Approved EGC
- PVC (Sched 40/80) Art. 352 Table 352.30 3 Feet Requires Wire EGC
- FMC Art. 348 12 Inches 4.5 Feet EGC only if ≤ 20 A \le 20\text{A} ≤ 20 A & ≤ 6 ft \le 6\text{ ft} ≤ 6 ft
- LFMC Art. 350 12 Inches 4.5 Feet EGC only if ≤ 20 A \le 20\text{A} ≤ 20 A & ≤ 6 ft \le 6\text{ ft} ≤ 6 ft