3.4 Combustion Analysis, Flue Gas Spillage & Carbon Monoxide Diagnostics

Michigan Mechanical Contractor License HVAC

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Michigan Regulatory Framework, Skilled Trades Act & Licensing

1.1 Michigan Skilled Trades Regulation Act (PA 407 of 2016 Article 8) & BCC Organization 1.2 The 14 Work Classification Examinations, Scope of Work & Experience Standards 1.3 Mechanical Permits, Inspection Protocols, Violations & Sanctions 1.4 Construction Lien Act (PA 497 of 1980), Timelines, Notices & Waivers

2 Chapter 2: Heating Equipment & Forced Air Systems

2.1 Warm Air Furnaces: Categories, Configurations & Heat Exchangers 2.2 High-Efficiency Condensing Furnaces & Condensate Management 2.3 Air-Source & Dual-Fuel Heat Pump Systems & Electric Auxiliary Heating 2.4 Ignition Control Systems, Gas Valves, Safety Switches & Sequence of Operation 2.5 Oil-Fired Furnaces, Burners, Fuel-Oil Storage & Piping

3 Chapter 3: Combustion Air, Fuel Gas Venting & Flue Gas Analysis

3.1 Combustion Air Requirements: Standard Method, Known Infiltration & Mechanical Air 3.2 Category I Venting: Type B Vents, Masonry Chimneys & Sizing Rules 3.3 Categories III & IV Venting: Direct-Vent Terminations, Clearances & Polypropylene/PVC 3.4 Combustion Analysis, Flue Gas Spillage & Carbon Monoxide Diagnostics

4 Chapter 4: Fuel Gas Piping Systems & Storage

4.1 Fuel Gas Pipe Sizing: Longest-Length Method & Branch Calculations 4.2 CSST Installation Standards, Mechanical Protection & Electrical Bonding 4.3 Gas Piping Materials, Joining Specifications, Pressure Testing & Purging 4.4 Liquefied Petroleum (LP) Gas: Tank Sizing, Regulators & Vaporization

5 Chapter 5: Refrigeration Cycle, Cooling Systems, Heat Pumps & Packaged Equipment

5.1 Vapor Compression Refrigeration Cycle & Enthalpy Calculations 5.2 Refrigerant Safety Groups, EPA Section 608 & Low-GWP A2L Transition 5.3 System Evacuation, Micron Gauges, Moisture Removal & Leak Detection 5.4 Charging Procedures: Superheat, Subcooling, TXV vs Fixed Orifice Diagnostics 5.5 Water-to-Air & Geothermal Heat Pump Systems 5.6 Ductless Mini-Split & Variable Refrigerant Flow Systems 5.7 Packaged Rooftop Units 2 to 25 Tons: Curbs, Access & Economizers

6 Chapter 6: Load Calculation, Duct Design & Air Distribution

6.1 ACCA Manual J Load Calculation & Equipment Selection 6.2 ACCA Manual D Fundamentals: Friction Rate, Available Static Pressure & Sizing 6.3 Duct Construction Standards (SMACNA), Sheet Metal Gauges & Hangers 6.4 Air Distribution Principles: Throw, Spread, Drop, Face Velocity & System Balancing 6.5 Mechanical Ventilation: ASHRAE 62.2, HRVs, ERVs & Michigan Energy Code Duct Insulation

7 Chapter 7: Commercial Kitchen Hoods & Building Exhaust Systems

7.1 Type I Commercial Kitchen Hoods & Grease Duct Systems 7.2 Type II Hoods, Kitchen Exhaust Fans & Makeup Air 7.3 Clothes Dryer, Bathroom & Hazardous Exhaust Systems

8 Chapter 8: Hydronic Heating, Steam Boilers & Process Piping

8.1 Hydronic Boilers: Low-Pressure Steam, Hot Water, ASME Code Trim & Safety Relief 8.2 Hydronic Loop Configurations: Series Loop, One-Pipe Mono-Flo, Two-Pipe Direct & Reverse Return 8.3 Expansion Tank Sizing, Air Elimination Devices & Circulator Pump Head Calculations 8.4 Steam Heating Specialties: Steam Traps, Hartford Loops, Vacuum Breakers & Water Feeders

9 Chapter 9: Jobsite Safety (MIOSHA), Electrical Controls & Business Management

9.1 MIOSHA Standards: Fall Protection, Confined Spaces, Ladder Safety & PPE 9.2 HVAC Electrical Safety: Lockout/Tagout, Disconnects, Overcurrent Protection & NEC Wire Sizing 9.3 Carbon Monoxide Hazards, HazCom (GHS/SDS) & Refrigerant Safety (ASHRAE 15) 9.4 Contractor Business Practice: Estimating, Contracts, Insurance & Lien Law Compliance

3.4 Combustion Analysis, Flue Gas Spillage & Carbon Monoxide Diagnostics

Key Takeaways Explain This Topic AI

Electronic combustion analyzers utilize electrochemical sensors to measure O2 (0% to 21%) and CO (PPM), calculating CO2, excess air, and net stack temperature (T_stack - T_ambient).

Category I natural draft must establish a steady negative pressure of -0.02 to -0.04 in. w.c. within 5 minutes of firing; positive pressure indicates flue blockage or spillage.

Air-free carbon monoxide normalizes measured CO by removing excess dilution air using the formula: CO_airfree = CO_measured × [20.9 / (20.9 - O2_measured)], which must not exceed the ANSI Z21 / MMC limit of 400 PPM.

During Combustion Appliance Zone (CAZ) depressurization testing, maximum allowable negative pressure is -3 to -5 Pa for Category I draft-hood appliances with Type B vents; draft hood spillage must cease within 60 seconds.

In the Blower-On Heat Exchanger Integrity Test, an O2 shift of greater than 1.0% or a sharp surge in CO upon circulating blower startup confirms a cracked or breached heat exchanger.

Last updated: September 2026

Combustion Analysis, Flue Gas Spillage & Carbon Monoxide Diagnostics

Quick Answer: Under the Michigan Mechanical Code and ANSI Z21 standards, complete fuel gas combustion verification requires instrumented electronic combustion analysis. An atmospheric appliance must achieve steady-state draft of -0.02 to -0.04 in. w.c. within 5 minutes. The legal limit for carbon monoxide in flue gas is 400 PPM air-free , calculated via the formula: CO_air-free = CO_measured ×[20.9 / (20.9 - O_2,measured)]. In Combustion Appliance Zone (CAZ) testing, negative depressurization cannot exceed -3 to -5 Pascals for Category I draft hoods, and startup spillage must cease within 60 seconds . A heat exchanger breach is confirmed if the circulating blower startup causes an O₂ shift > 1.0% or a sharp CO spike. Ambient CO levels of ≥35 PPM mandate immediate building evacuation.

Combustion analysis has evolved from a subjective visual flame check (looking for 'crisp blue flames') into a precise, instrumented science. Modern residential and commercial heating systems cannot be safely commissioned, tuned, or diagnosed without a calibrated electronic combustion analyzer and digital differential manometer.

Electronic Combustion Analyzer Operation & Architecture

A modern portable combustion analyzer utilizes precision electrochemical sensors and integrated thermistors to sample flue gas products through an insertion probe placed in the flue breach:

Electrochemical Oxygen Sensor (O₂): Measures atmospheric and flue oxygen concentration from 0.0% to 20.9%. The sensor generates a micro-voltage proportional to the partial pressure of oxygen diffusing across a chemical membrane.

Electrochemical Carbon Monoxide Sensor (CO): Measures carbon monoxide in parts per million (PPM) from 0 to 2,000+ PPM. Premium analyzers feature hydrogen-compensated CO sensors to eliminate false-high readings caused by trace hydrogen (H₂) gas in rich burner flames.

Thermocouple Flue Probe: Measures the gross flue gas temperature (T_stack) in the center of the exhaust stream.

Ambient Air Temperature Sensor: Measures the temperature of combustion air entering the burner (T_ambient).

Differential Pressure Manometer: Measures flue stack draft relative to mechanical room pressure.

Net Stack Temperature & Combustion Efficiency Calculations

An analyzer does not measure carbon dioxide (CO₂) directly; it calculates CO₂, excess air, and combustion efficiency using measured O₂ and net stack temperature : Net Stack Temperature = T stack − T ambient \text{Net Stack Temperature} = T_{\text{stack}} - T_{\text{ambient}} Net Stack Temperature = T stack ​ − T ambient ​

In an 80% AFUE induced-draft furnace, a typical gross stack temperature of 380°F in a 70°F basement yields a net stack temperature of 310°F.

In a 95% condensing furnace, gross stack temperature typically ranges from 100°F to 125°F, yielding a net stack temperature of 30°F to 55°F. Excessively high net stack temperatures indicate scaled heat exchangers, overfiring, or insufficient air handler airflow.

Stack Draft Verification in Category I Systems

Draft verification is mandatory on all Category I natural-draft appliances. The technician drills a 5/16" test port in the vent connector between the appliance draft hood and the chimney breach (at least two pipe diameters downstream of the draft hood and one diameter upstream of any elbow):

Cold Start Behavior: When the burner first ignites, the chimney is cold, producing zero draft or slight positive pressure. Minor spillage at the draft hood relief opening is normal during the first 30 to 60 seconds.

Steady-State Benchmark: Within 5 minutes of continuous burner firing, the stack must establish a negative pressure of -0.02 to -0.04 in. w.c. (-5 to -10 Pa).

Failure Conditions: A steady-state reading of 0.00 in. w.c. or positive pressure indicates a blocked flue, disconnected chimney liner, severe building depressurization, or undersized venting.

Air-Free Carbon Monoxide: Formula & Code Thresholds

A raw CO reading taken with an analyzer probe is deceptive. For example, sampling flue gas downstream of an atmospheric draft hood introduces large volumes of dilution air (containing 20.9% oxygen), artificially diluting 200 PPM of actual burner CO down to a 'measured' 50 PPM. To eliminate dilution distortion, code and equipment standards mandate calculating Air-Free Carbon Monoxide (CO_air-free) .

The Mathematical Formula (ANSI Z21 / MMC) CO air-free = CO measured × ( 20.9 20.9 − O 2 , measured ) \text{CO}_{\text{air-free}} = \text{CO}_{\text{measured}} \times \left( \frac{20.9}{20.9 - \text{O}_{2,\text{measured}}} \right) CO air-free ​ = CO measured ​ × ( 20.9 − O 2 , measured ​ 20.9 ​ )

Where:

  • CO_measured is the raw, unadjusted parts-per-million reading from the analyzer
  • O_2,measured is the percentage of oxygen measured in the flue gas sample
  • 20.9 is the volumetric percentage of oxygen in clean, standard atmospheric air
  • Worked Calculation: Air-Free Carbon Monoxide

A technician tests an atmospheric warm air furnace. The analyzer probe in the draft hood connector measures 80 PPM of CO and 9.5% O₂. Calculate the air-free CO concentration.

Calculate the dilution multiplier: Multiplier = 20.9 20.9 − 9.5 = 20.9 11.4 ≈ 1.8333 \text{Multiplier} = \frac{20.9}{20.9 - 9.5} = \frac{20.9}{11.4} \approx 1.8333 Multiplier = 20.9 − 9.5 20.9 ​ = 11.4 20.9 ​ ≈ 1.8333

Multiply raw CO by the dilution multiplier: CO air-free = 80 PPM × 1.8333 = 146.67 PPM \text{CO}_{\text{air-free}} = 80\text{ PPM} \times 1.8333 = 146.67\text{ PPM} CO air-free ​ = 80 PPM × 1.8333 = 146.67 PPM

Analysis: While the raw reading (80 PPM) appeared modest, the true stoichiometric burner output is 146.7 PPM air-free.

The Code Benchmark: 400 PPM Air-Free Limit

Under ANSI Z21.47 / Michigan Mechanical Code Section 801 , the absolute maximum allowable level of carbon monoxide in an undiluted flue gas sample is 400 PPM air-free . Operating an appliance above 400 PPM air-free is a critical safety violation requiring immediate shutdown and red-tagging. However, modern professional trade guidelines (such as National Comfort Institute / NCI standards) recommend that a properly tuned gas furnace should never exceed 50 to 100 PPM air-free in clean steady-state operation.

Combustion Appliance Zone (CAZ) Depressurization Testing

In modern energy-tight homes, powerful exhaust devices (range hoods, downdraft kitchen exhausters, clothes dryers, central vacuums, and bath fans) remove hundreds of cubic feet per minute of air. If makeup air is absent, the house acts as a large vacuum, creating negative pressure inside the Combustion Appliance Zone (CAZ) . If CAZ negative pressure exceeds the natural buoyancy draft of a Category I water heater, toxic flue gases will backdraft down the chimney and spill out the draft hood into the home.

Worst-Case Depressurization Test (WCDT) Protocol

To evaluate venting safety under extreme conditions, the technician performs a Worst-Case Depressurization Test (BPI-1200 / ACCA 5 QI standard):

Close all exterior windows, doors, and fireplace dampers.

Turn on all exhaust fans in the home (kitchen range hood on high, bathroom exhausters, clothes dryer).

Close all interior doors connecting bedrooms to the central hallway.

Set the central air handler blower to run continuously on high speed.

Using a digital micro-manometer referenced to the outdoors (via a reference tube running through an exterior door), measure the baseline CAZ pressure.

Systematically open and close interior bedroom doors to discover the configuration that produces the greatest negative pressure in the CAZ.

CAZ Negative Pressure Limits

Under code diagnostic standards, the maximum allowable negative CAZ pressure depends on appliance category and vent construction:

Appliance / Vent Configuration Maximum Permissible CAZ Depressurization Failure Consequence

Category I Atmospheric Appliance with Single-Wall Vent Connector -3.0 Pascals (-0.012 in. w.c.) Natural draft stalls immediately; rapid spillage

Category I Atmospheric Appliance with Type B Double-Wall Vent -5.0 Pascals (-0.020 in. w.c.) Maximum threshold before draft fails

Fan-Assisted Category I Appliance (Induced Draft without Draft Hood) -15.0 Pascals (-0.060 in. w.c.) Fan exhauster overcomes moderate room vacuum

Category IV Direct-Vent Sealed Combustion Appliance -50.0 Pascals (-0.200 in. w.c.) Immune to room depressurization; sealed to exterior

The 60-Second Spillage Test

With the house configured in worst-case depressurization, fire the smallest fuel-burning appliance (usually the atmospheric water heater) first:

Hold a chemical smoke pen, mirror, or personal CO monitor along the lower lip of the draft hood relief opening.

Flue gases may spill momentarily upon cold startup, but spillage must completely cease within 60 seconds .

If the smoke is blown outward or the mirror fogs continuously after 60 seconds (or after 5 minutes of continuous operation), the system fails the spillage test. The contractor must provide dedicated combustion makeup air or replace the atmospheric appliance with a direct-vent unit.

Heat Exchanger Integrity: The "Blower-On Test"

A cracked, corroded, or breached heat exchanger allows circulating indoor air (pressurized by the main supply blower) to blow directly into the burner combustion chamber, disrupting the combustion flame and pushing carbon monoxide into the supply ductwork.

Blower-On Test Diagnostic Protocol

While visual inspection with a camera probe or smoke bomb is helpful, the instrumented Blower-On Test is the definitive diagnostic method:

Insert the combustion analyzer probe into the flue breach of the furnace downstream of the induced-draft blower.

Disconnect the 120V power to the main indoor circulating blower motor (or remove the blower door safety switch wire) to prevent the blower from starting.

Fire the furnace burners and allow them to run for approximately 3 to 4 minutes until steady-state combustion is established.

Record the baseline flue gas readings: O₂%, CO (PPM), and stack temperature.

Manually energize the circulating supply blower (reconnecting power or jumping the fan control).

Closely observe the analyzer display for 90 seconds following blower energization.

Interpreting Diagnostic Results

Healthy Heat Exchanger: The O₂ concentration remains stable (shifting less than 0.5%) and the CO reading does not rise. Flue temperature slowly declines as the blower strips heat from the exterior of the cells.

Breached / Cracked Heat Exchanger: An O₂ shift of greater than 1.0% (for example, rising rapidly from 6.2% to 7.8%) or a sharp surge in CO (jumping by >25 to 50+ PPM) immediately upon blower startup confirms a cracked heat exchanger . High-pressure supply air is blowing through cracks into the burner cells, diluting combustion gases and destabilizing the flame envelope. The furnace must be immediately locked out, tagged out, and replaced.

Ambient Carbon Monoxide Safety Levels & Evacuation Thresholds

Carbon monoxide is an odorless, colorless, tasteless, and non-irritating toxic gas. When inhaled, CO binds to blood hemoglobin with an affinity 210 to 250 times greater than oxygen , forming carboxyhemoglobin (COHb) in red blood cells and suffocating body tissues at the cellular level.

Technicians must carry a calibrated personal ambient CO monitor whenever entering a building for service. The Michigan Mechanical Code, MIOSHA, and CPSC establish strict response tiers:

Ambient CO Concentration Health Hazard Level Mandatory Contractor / Occupant Action

0 to 9 PPM Normal Background Safe ambient level (EPA outdoor ambient standard is 9 PPM over 8 hours). Proceed with service.

10 to 34 PPM Elevated / Warning Chronic exposure hazard. Advise building occupants. Open windows to ventilate; investigate fuel-burning equipment, water heaters, attached garages, and gas stoves to locate source.

≥35 PPM DANGEROUS / EVACUATE Immediate Life-Safety Emergency. Evacuate all occupants from the structure to fresh outdoor air immediately. Shut off fuel supply valves from outside if accessible. Call 911 / Fire Department. Do not re-enter until building is cleared by emergency personnel with calibrated instruments.

50 PPM Occupational Limit MIOSHA / OSHA 8-hour Permissible Exposure Limit (PEL) for industrial workplaces.

100 to 200 PPM Severe Toxicity Frontal headache, dizziness, nausea, and mental confusion within 1 to 2 hours of exposure.

400 to 800 PPM Critical Life Threat Severe headache, convulsions, loss of consciousness within 45 minutes; death within 1 to 2 hours.

≥1,200 PPM IDLH NIOSH Immediately Dangerous to Life or Health threshold; death within minutes.

Loading diagram... Comprehensive Combustion Analysis and Life-Safety Diagnostic Flowchart