5.1 Vapor Compression Refrigeration Cycle & Enthalpy Calculations
Michigan Mechanical Contractor License HVAC
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Michigan Regulatory Framework, Skilled Trades Act & Licensing
1.1 Michigan Skilled Trades Regulation Act (PA 407 of 2016 Article 8) & BCC Organization 1.2 The 14 Work Classification Examinations, Scope of Work & Experience Standards 1.3 Mechanical Permits, Inspection Protocols, Violations & Sanctions 1.4 Construction Lien Act (PA 497 of 1980), Timelines, Notices & Waivers
2 Chapter 2: Heating Equipment & Forced Air Systems
2.1 Warm Air Furnaces: Categories, Configurations & Heat Exchangers 2.2 High-Efficiency Condensing Furnaces & Condensate Management 2.3 Air-Source & Dual-Fuel Heat Pump Systems & Electric Auxiliary Heating 2.4 Ignition Control Systems, Gas Valves, Safety Switches & Sequence of Operation 2.5 Oil-Fired Furnaces, Burners, Fuel-Oil Storage & Piping
3 Chapter 3: Combustion Air, Fuel Gas Venting & Flue Gas Analysis
3.1 Combustion Air Requirements: Standard Method, Known Infiltration & Mechanical Air 3.2 Category I Venting: Type B Vents, Masonry Chimneys & Sizing Rules 3.3 Categories III & IV Venting: Direct-Vent Terminations, Clearances & Polypropylene/PVC 3.4 Combustion Analysis, Flue Gas Spillage & Carbon Monoxide Diagnostics
4 Chapter 4: Fuel Gas Piping Systems & Storage
4.1 Fuel Gas Pipe Sizing: Longest-Length Method & Branch Calculations 4.2 CSST Installation Standards, Mechanical Protection & Electrical Bonding 4.3 Gas Piping Materials, Joining Specifications, Pressure Testing & Purging 4.4 Liquefied Petroleum (LP) Gas: Tank Sizing, Regulators & Vaporization
5 Chapter 5: Refrigeration Cycle, Cooling Systems, Heat Pumps & Packaged Equipment
5.1 Vapor Compression Refrigeration Cycle & Enthalpy Calculations 5.2 Refrigerant Safety Groups, EPA Section 608 & Low-GWP A2L Transition 5.3 System Evacuation, Micron Gauges, Moisture Removal & Leak Detection 5.4 Charging Procedures: Superheat, Subcooling, TXV vs Fixed Orifice Diagnostics 5.5 Water-to-Air & Geothermal Heat Pump Systems 5.6 Ductless Mini-Split & Variable Refrigerant Flow Systems 5.7 Packaged Rooftop Units 2 to 25 Tons: Curbs, Access & Economizers
6 Chapter 6: Load Calculation, Duct Design & Air Distribution
6.1 ACCA Manual J Load Calculation & Equipment Selection 6.2 ACCA Manual D Fundamentals: Friction Rate, Available Static Pressure & Sizing 6.3 Duct Construction Standards (SMACNA), Sheet Metal Gauges & Hangers 6.4 Air Distribution Principles: Throw, Spread, Drop, Face Velocity & System Balancing 6.5 Mechanical Ventilation: ASHRAE 62.2, HRVs, ERVs & Michigan Energy Code Duct Insulation
7 Chapter 7: Commercial Kitchen Hoods & Building Exhaust Systems
7.1 Type I Commercial Kitchen Hoods & Grease Duct Systems 7.2 Type II Hoods, Kitchen Exhaust Fans & Makeup Air 7.3 Clothes Dryer, Bathroom & Hazardous Exhaust Systems
8 Chapter 8: Hydronic Heating, Steam Boilers & Process Piping
8.1 Hydronic Boilers: Low-Pressure Steam, Hot Water, ASME Code Trim & Safety Relief 8.2 Hydronic Loop Configurations: Series Loop, One-Pipe Mono-Flo, Two-Pipe Direct & Reverse Return 8.3 Expansion Tank Sizing, Air Elimination Devices & Circulator Pump Head Calculations 8.4 Steam Heating Specialties: Steam Traps, Hartford Loops, Vacuum Breakers & Water Feeders
9 Chapter 9: Jobsite Safety (MIOSHA), Electrical Controls & Business Management
9.1 MIOSHA Standards: Fall Protection, Confined Spaces, Ladder Safety & PPE 9.2 HVAC Electrical Safety: Lockout/Tagout, Disconnects, Overcurrent Protection & NEC Wire Sizing 9.3 Carbon Monoxide Hazards, HazCom (GHS/SDS) & Refrigerant Safety (ASHRAE 15) 9.4 Contractor Business Practice: Estimating, Contracts, Insurance & Lien Law Compliance
5.1 Vapor Compression Refrigeration Cycle & Enthalpy Calculations
Key Takeaways Explain This Topic AI
The standard vapor compression refrigeration cycle consists of four primary mechanical components: compressor (work input), condenser (heat rejection), metering device (isenthalpic expansion), and evaporator (heat absorption).
Refrigerant undergoes four continuous thermodynamic state transitions: low-pressure superheated vapor enters the compressor, high-pressure superheated vapor discharges to the condenser, high-pressure subcooled liquid exits the condenser, and a low-pressure saturated liquid/vapor mixture enters the evaporator.
On a Pressure-Enthalpy (P-h) Mollier diagram, constant pressure phase changes appear as horizontal lines across the saturation dome, while isenthalpic expansion through the metering device drops vertically (h3 = h4).
The Net Refrigeration Effect (NRE) is calculated as h1 - h4 (in BTU/lb), Heat of Compression (HOC) is h2 - h1 (in BTU/lb), and Total Heat of Rejection (THR) is h2 - h3, where THR = NRE + HOC.
Coefficient of Performance (COP) equals NRE / HOC, and the Energy Efficiency Ratio (EER) is directly derived by multiplying COP by 3.41214 (EER = 3.41214 * COP).
Last updated: September 2026
Vapor Compression Refrigeration Cycle & Enthalpy Calculations
The vapor compression refrigeration cycle represents the thermodynamic foundation of all modern mechanical cooling equipment, split air conditioning systems, heat pumps, and commercial refrigeration units installed throughout Michigan. Licensed mechanical contractors must understand both the physical behavior of circulating refrigerants and the mathematical models used to evaluate system capacity, compressor workload, and thermal efficiency. Mastery of Pressure-Enthalpy (P-h) diagrams and enthalpy equations is essential for diagnosing complex system faults and passing the Michigan Mechanical Contractor examination.
1. Thermodynamic Architecture & The Four Primary Components
The vapor compression cycle operates as a closed, hermetically sealed mechanical loop that transfers heat from a lower-temperature medium (the conditioned indoor space) to a higher-temperature medium (the outdoor ambient environment). The system relies on the continuous manipulation of refrigerant pressures to exploit the latent heat of vaporization. +-----------------------+
- | COMPRESSOR |
- | (Low-P Sup. Vapor -> |
- | High-P Sup. Vapor) |
- +-----------+-----------+
- | Discharge Line (Hot, High-P Gas)
- v
- +--------------------------+--------------------------+
- | CONDENSER |
- | 1. Desuperheating (Sensible Heat Loss) |
- | 2. Condensing (Latent Heat Rejection to Ambient) |
- | 3. Subcooling (Sensible Heat Loss Below Sat. Temp) |
- +--------------------------+--------------------------+
- | Liquid Line (High-P Subcooled Liquid)
- v
- +-----------+-----------+
- | METERING DEVICE |
- | (Isenthalpic Drop -> |
- | Flash Gas Mixture) |
- +-----------+-----------+
- | Distributor / Evaporator Inlet
- v
- +--------------------------+--------------------------+
- | EVAPORATOR |
- | 1. Boiling / Vaporizing (Latent Heat Absorption) |
- | 2. Superheating (Sensible Heat Gain Above Sat. T) |
- +--------------------------+--------------------------+
- | Suction Line (Cold, Low-P Superheated Gas)
- +--------------------------+
The cycle is divided along two distinct operational boundaries:
The Pressure Boundary (High Side vs. Low Side): The dividing line between the high-pressure side and the low-pressure side runs directly through the compressor discharge valves and the orifice of the expansion metering device. The high side comprises the compressor cylinder heads, discharge line, condenser coil, and liquid line. The low side comprises the metering device outlet, distributor tubes, evaporator coil, suction line, and compressor crankcase/motor housing.
The Thermal Boundary (Heat Absorption vs. Heat Rejection): Heat is absorbed into the cycle exclusively through the low-temperature evaporator coil, while heat is expelled from the cycle exclusively through the high-temperature condenser coil.
The Compressor
The compressor serves as the mechanical pump and pressure-generating heart of the refrigeration system. Its dual operational functions are:
Maintaining a low suction pressure in the evaporator so that refrigerant boils at a temperature lower than the conditioned indoor space.
Compressing the low-pressure suction vapor into a high-pressure, high-temperature discharge vapor so that its saturation temperature is substantially higher than the ambient cooling medium (such as outdoor air at 95°F).
Only vapor may enter a compressor. Liquid refrigerant is virtually incompressible; liquid droplets entering the compression chamber cause violent hydraulic shock, fractured reed valves, bent connecting rods, damaged scroll flanks, and washed-out bearing lubrication.
The Condenser
The condenser is a forced-convection finned-tube or microchannel heat exchanger located outdoors in split-system air conditioning or heat pump installations. It receives superheated discharge vapor from the compressor and rejects thermal energy to the ambient air stream across three successive stages:
Desuperheating: The high-temperature superheated vapor gives up sensible heat until its temperature drops to the refrigerant condensing saturation temperature corresponding to head pressure.
Condensing: Latent heat of vaporization is rejected to the ambient air at a constant saturation temperature and pressure. The refrigerant changes phase from 100% saturated vapor to 100% saturated liquid.
Subcooling: The liquid refrigerant gives up additional sensible heat, dropping its temperature below the condensing saturation point before leaving the coil. Subcooling prevents premature flashing in the liquid line.
The Metering Device
The metering device (thermostatic expansion valve, electronic expansion valve, or fixed orifice/piston) creates a designated restriction in the liquid line. It drops the high-pressure subcooled liquid down to the low-pressure evaporating level.
Because no external work is performed and heat transfer through the valve body is negligible, expansion across a metering device is modeled as an isenthalpic process (constant enthalpy, where h₃ = h₄).
As the pressure plummets across the restriction, the boiling point of the refrigerant drops below its entering temperature. A portion of the liquid (typically 15% to 25% by mass) instantaneously boils—or flashes —into vapor. This flash gas absorbs sensible heat from the remaining liquid, cooling the remaining 75% to 85% of liquid down to the low saturation temperature required in the evaporator.
The Evaporator
The evaporator is a finned-tube heat exchanger located in the indoor air stream (or chilled water barrel). Cold, low-pressure liquid-vapor mixture enters through a distributor assembly:
Boiling (Latent Heat Absorption): The liquid refrigerant boils at a constant saturation temperature and pressure, absorbing latent heat from the indoor air stream moving across the coil fins.
Superheating: After the final droplet of liquid vaporizes at the 100% saturated vapor line, the vapor continues traveling through the remaining evaporator passes, absorbing sensible heat. This superheat raises the vapor temperature safely above its saturation point, guaranteeing dry gas enters the suction line.
2. Refrigerant State Changes Around the Cycle
Tracing the refrigerant through four primary thermodynamic milestones reveals the precise state, pressure, and enthalpy changes:
State Point Physical Location Fluid Phase / Thermodynamic State Pressure Level Temperature Relative to Saturation
1 Evaporator Outlet / Compressor Inlet Low-pressure superheated vapor Low (Suction) Sensibly heated 8°F to 15°F above evaporating saturation temperature
2 Compressor Discharge / Condenser Inlet High-pressure superheated vapor High (Discharge) Sensibly heated 40°F to 80°F above condensing saturation temperature
3 Condenser Outlet / Metering Device Inlet High-pressure subcooled liquid High (Liquid) Sensibly cooled 8°F to 14°F below condensing saturation temperature
4 Metering Device Outlet / Evaporator Inlet Low-pressure saturated liquid/vapor mixture Low (Evaporating) Exact saturation temperature at evaporating pressure (refrigerant quality x ≈0.15 - 0.25)
3. Pressure-Enthalpy (P-h) Mollier Diagram Analysis
The Pressure-Enthalpy (P-h) diagram, commonly referred to as a Mollier chart, maps the complete thermodynamic properties of a specific refrigerant on a single graphical coordinate plane:
Vertical Y-Axis (Pressure): Displays absolute pressure (P in psia) plotted on a logarithmic scale to compress wide pressure swings into readable increments.
Horizontal X-Axis (Enthalpy): Displays heat content (h in BTU/lb of refrigerant) plotted on a linear scale .
Anatomy of the Saturation Dome
A bell-shaped curve dominates the center of the diagram:
Saturated Liquid Line: The left boundary of the dome. Represents 100% liquid at its boiling point (refrigerant quality x = 0.0). Any heat removed from liquid on this line produces subcooled liquid.
Saturated Vapor Line: The right boundary of the dome. Represents 100% dry saturated vapor with no liquid droplets remaining (refrigerant quality x = 1.0). Any heat added to vapor on this line produces superheated vapor.
Critical Point: The apex where the saturated liquid and saturated vapor lines meet. Above the critical temperature and pressure, distinct liquid and vapor phases cannot coexist regardless of pressure.
The Three Thermodynamic Regions
Subcooled Liquid Region (Left of Dome): Fluid exists purely as a liquid at a temperature below its boiling point for that pressure.
Two-Phase Mixture Region (Inside Dome): Liquid and vapor coexist in equilibrium at constant saturation temperature and pressure. The horizontal distance across the dome reflects the latent heat of vaporization (h_fg).
Superheated Vapor Region (Right of Dome): Fluid exists purely as a dry gas at a temperature above its saturation temperature for that pressure.
Thermodynamic Isolines
Constant Pressure Lines (Isobars): Run horizontally across the entire chart.
Constant Enthalpy Lines (Isenthalps): Run vertically from top to bottom.
Constant Temperature Lines (Isotherms): Run almost vertically downward in the subcooled region, turn perfectly horizontal across the two-phase dome (because phase change occurs at constant temperature and pressure), and drop steeply downward to the right in the superheated region.
Constant Entropy Lines (Isentropes): Slope steeply upward to the right in the superheated vapor region. An ideal, frictionless, adiabatic compression process follows a line of constant entropy (s = constant).
4. Fundamental Enthalpy Calculations
Thermodynamic performance is calculated directly from enthalpy values (h) extracted from the four state points on a P-h chart.
Net Refrigeration Effect (NRE)
The Net Refrigeration Effect is the quantity of thermal energy that each pound of circulating refrigerant absorbs from the conditioned space as it traverses the evaporator: NRE = h 1 − h 4 \text{NRE} = h_1 - h_4 NRE = h 1 − h 4
Because expansion across the metering device is isenthalpic (h₃ = h₄), NRE can also be expressed as: NRE = h 1 − h 3 \text{NRE} = h_1 - h_3 NRE = h 1 − h 3
Where:
- NRE = Net Refrigeration Effect in BTU/lb
- h₁ = Enthalpy of superheated vapor leaving the evaporator in BTU/lb
- h₄ = Enthalpy of saturated mixture entering the evaporator in BTU/lb
- h₃ = Enthalpy of subcooled liquid entering the expansion valve in BTU/lb
- Heat of Compression (HOC)
The Heat of Compression represents the mechanical work energy added to each pound of refrigerant by the compressor motor: HOC = h 2 − h 1 \text{HOC} = h_2 - h_1 HOC = h 2 − h 1
Where:
- HOC = Heat of Compression in BTU/lb
- h₂ = Enthalpy of discharge gas leaving the compressor in BTU/lb
- h₁ = Enthalpy of suction gas entering the compressor in BTU/lb
- Total Heat of Rejection (THR)
The Total Heat of Rejection is the total thermal energy that must be expelled into the ambient air by the outdoor condenser coil. It equals the heat absorbed in the indoor evaporator plus the heat added by the compressor: THR = h 2 − h 3 \text{THR} = h_2 - h_3 THR = h 2 − h 3 THR = NRE + HOC = ( h 1 − h 4 ) + ( h 2 − h 1 ) \text{THR} = \text{NRE} + \text{HOC} = (h_1 - h_4) + (h_2 - h_1) THR = NRE + HOC = ( h 1 − h 4 ) + ( h 2 − h 1 )
Note
In air conditioning applications, the Total Heat of Rejection is roughly 15% to 30% higher than the cooling capacity of the unit. This added heat represents the thermal conversion of electrical energy expended by the compressor motor in compressing the vapor.
Refrigerant Mass Flow Rate (ṁ)
To achieve a target cooling capacity, a specific mass of refrigerant must be circulated per unit of time: m ˙ = Cooling Capacity (BTU/hr) NRE (BTU/lb) = 12 , 000 × Tonnage NRE \dot{m} = \frac{\text{Cooling Capacity (BTU/hr)}}{\text{NRE (BTU/lb)}} = \frac{12,000 \times \text{Tonnage}}{\text{NRE}} m ˙ = NRE (BTU/lb) Cooling Capacity (BTU/hr) = NRE 12 , 000 × Tonnage
Where:
- ṁ = Mass flow rate in pounds per hour (lb/hr)
- 1 ton of refrigeration = 12,000 BTU/hr
- Coefficient of Performance (COP)
The Coefficient of Performance is the dimensionless ratio of useful cooling produced to the energy input required to run the compressor: COP = Useful Cooling Effect Work of Compression = NRE HOC = h 1 − h 4 h 2 − h 1 \text{COP} = \frac{\text{Useful Cooling Effect}}{\text{Work of Compression}} = \frac{\text{NRE}}{\text{HOC}} = \frac{h_1 - h_4}{h_2 - h_1} COP = Work of Compression Useful Cooling Effect = HOC NRE = h 2 − h 1 h 1 − h 4
Energy Efficiency Ratio (EER)
In the United States HVAC trade, cooling efficiency is conventionally expressed as the Energy Efficiency Ratio (EER), defined as the ratio of cooling output in BTU/hr to electrical power input in Watts: EER = Cooling Capacity (BTU/hr) Electrical Power Input (Watts) \text{EER} = \frac{\text{Cooling Capacity (BTU/hr)}}{\text{Electrical Power Input (Watts)}} EER = Electrical Power Input (Watts) Cooling Capacity (BTU/hr)
Because 1 Watt = 3.41214 BTU/hr, EER is mathematically related to COP by the direct conversion factor: EER = 3.41214 × COP \text{EER} = 3.41214 \times \text{COP} EER = 3.41214 × COP
5. Comprehensive Step-by-Step Thermodynamic Calculation
To illustrate these principles, consider a 3-ton (36,000 BTU/hr) split-system air conditioner utilizing R-410A operating under standard design conditions:
Evaporating Conditions: Evaporating pressure of 130.7 psig (145.4 psia), corresponding to a saturation temperature of 45°F. Suction gas warms to 55°F at the evaporator outlet (10°F of superheat). From the R-410A P-h chart, suction gas enthalpy is h₁ = 118.5 BTU/lb .
Discharge Conditions: Discharge pressure of 390.0 psig (404.7 psia), corresponding to a condensing saturation temperature of 115°F. The compressor discharges gas at 175°F. From the P-h chart, discharge enthalpy is h₂ = 135.2 BTU/lb .
Liquid Conditions: Condensing at 115°F, the liquid is subcooled by 10°F down to 105°F as it enters the expansion valve. From the P-h chart, liquid enthalpy is h₃ = 48.2 BTU/lb .
Metering Outlet Conditions: Because expansion is isenthalpic, h₄ = h₃ = 48.2 BTU/lb .
Step 1: Calculate Net Refrigeration Effect (NRE) NRE = h 1 − h 4 = 118.5 − 48.2 = 70.3 BTU/lb \text{NRE} = h_1 - h_4 = 118.5 - 48.2 = 70.3\text{ BTU/lb} NRE = h 1 − h 4 = 118.5 − 48.2 = 70.3 BTU/lb
Each pound of R-410A absorbs 70.3 BTU of heat from the conditioned building.
Step 2: Calculate Heat of Compression (HOC) HOC = h 2 − h 1 = 135.2 − 118.5 = 16.7 BTU/lb \text{HOC} = h_2 - h_1 = 135.2 - 118.5 = 16.7\text{ BTU/lb} HOC = h 2 − h 1 = 135.2 − 118.5 = 16.7 BTU/lb
The compressor motor adds 16.7 BTU of mechanical energy to each pound of vapor compressed.
Step 3: Calculate Total Heat of Rejection (THR) THR = h 2 − h 3 = 135.2 − 48.2 = 87.0 BTU/lb \text{THR} = h_2 - h_3 = 135.2 - 48.2 = 87.0\text{ BTU/lb} THR = h 2 − h 3 = 135.2 − 48.2 = 87.0 BTU/lb
Verification using component summation: THR = NRE + HOC = 70.3 + 16.7 = 87.0 BTU/lb \text{THR} = \text{NRE} + \text{HOC} = 70.3 + 16.7 = 87.0\text{ BTU/lb} THR = NRE + HOC = 70.3 + 16.7 = 87.0 BTU/lb
Step 4: Calculate Refrigerant Mass Flow Rate (ṁ) m ˙ = 36 , 000 BTU/hr 70.3 BTU/lb ≈ 512.09 lb/hr \dot{m} = \frac{36,000\text{ BTU/hr}}{70.3\text{ BTU/lb}} \approx 512.09\text{ lb/hr} m ˙ = 70.3 BTU/lb 36 , 000 BTU/hr ≈ 512.09 lb/hr
To maintain a 3-ton capacity, the compressor must pump approximately 512.1 pounds of R-410A per hour (8.53 lb/min).
Step 5: Determine Theoretical Compressor Power Draw Work Output Rate = m ˙ × HOC = 512.09 lb/hr × 16.7 BTU/lb = 8 , 551.9 BTU/hr \text{Work Output Rate} = \dot{m} \times \text{HOC} = 512.09\text{ lb/hr} \times 16.7\text{ BTU/lb} = 8,551.9\text{ BTU/hr} Work Output Rate = m ˙ × HOC = 512.09 lb/hr × 16.7 BTU/lb = 8 , 551.9 BTU/hr
Converting to electrical power in Kilowatts (1 kW = 3,412.14 BTU/hr): P theoretical = 8 , 551.9 BTU/hr 3 , 412.14 BTU/hr per kW ≈ 2.506 kW P_{\text{theoretical}} = \frac{8,551.9\text{ BTU/hr}}{3,412.14\text{ BTU/hr per kW}} \approx 2.506\text{ kW} P theoretical = 3 , 412.14 BTU/hr per kW 8 , 551.9 BTU/hr ≈ 2.506 kW
Step 6: Calculate Coefficient of Performance (COP) COP = NRE HOC = 70.3 BTU/lb 16.7 BTU/lb ≈ 4.21 \text{COP} = \frac{\text{NRE}}{\text{HOC}} = \frac{70.3\text{ BTU/lb}}{16.7\text{ BTU/lb}} \approx 4.21 COP = HOC NRE = 16.7 BTU/lb 70.3 BTU/lb ≈ 4.21
Step 7: Calculate Energy Efficiency Ratio (EER) EER = 3.41214 × COP = 3.41214 × 4.21 ≈ 14.36 BTU/Watt-hr \text{EER} = 3.41214 \times \text{COP} = 3.41214 \times 4.21 \approx 14.36\text{ BTU/Watt-hr} EER = 3.41214 × COP = 3.41214 × 4.21 ≈ 14.36 BTU/Watt-hr
Alternatively, checking directly against capacity and theoretical power: EER = 36 , 000 BTU/hr 2 , 506.3 Watts ≈ 14.36 BTU/Watt-hr \text{EER} = \frac{36,000\text{ BTU/hr}}{2,506.3\text{ Watts}} \approx 14.36\text{ BTU/Watt-hr} EER = 2 , 506.3 Watts 36 , 000 BTU/hr ≈ 14.36 BTU/Watt-hr
6. Practical Impact of Operating Conditions on the P-h Cycle
Thermodynamic efficiency shifts markedly when field operating conditions deviate from standard parameters:
Elevated Condensing Temperature (Dirty Outdoor Coil / High Ambient): Shifts state point 2 to a higher pressure and enthalpy (h₂ increases), while shifting point 3 to the right (h₃ increases). This expands the required compressor work (h₂ - h₁ increases) while reducing the Net Refrigeration Effect (h₁ - h₄ decreases). Consequently, cooling capacity drops while compressor power consumption spikes, severely degrading COP and EER.
Depressed Evaporating Temperature (Dirty Indoor Filter / Low Airflow): Shifts state point 1 downward on the pressure axis (h₁ decreases). This lowers the density of the suction vapor entering the compressor, diminishing the mass flow rate pumped by the compressor while increasing the compression ratio. System capacity plummets, and the evaporator coil risks freezing.