12.3 Grease Interceptors: Hydromechanical (HGI) vs. Gravity (GGI)

Michigan Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Michigan Plumbing Law, Administration & Licensing

1.1 Michigan Skilled Trades Regulation Act (PA 407 Article 11) & Licensing Hierarchy 1.2 Permits, Applications, Inspections & Code Enforcement 1.3 Essential Plumbing Code Definitions & Terminology

2 Chapter 2: General Regulations & Structural Safety

2.1 Piping Protection, Trenching, Bedding & Backfill 2.2 Structural Safety: Boring, Notching & Cutting of Structural Members 2.3 Pipe Hangers, Supports & Spacing Requirements 2.4 Michigan Frost Protection & Underground Piping Depths

3 Chapter 3: Fixtures, Faucets & Fixture Fittings

3.1 Minimum Plumbing Fixtures, Occupancy Calculations & ADA Accessibility 3.2 Installation of Fixtures: Setting, Clearances, Connections & Access 3.3 Water Closets, Urinals & Flushing Devices 3.4 Showers, Bathtubs & Scald Prevention Standards 3.5 Sinks, Lavatories, Drinking Fountains & Emergency Fixtures

4 Chapter 4: Water Heaters & Hot Water Safety

4.1 Water Heater Sizing, Location, Clearances & Combustion Air 4.2 Temperature & Pressure (T&P) Relief Valves & Discharge Piping 4.3 Thermal Expansion Control, Safety Pans & Drain Terminations

5 Chapter 5: Water Supply Sizing & Distribution

5.1 Water Service Sizing & Water Supply Fixture Units (WSFU) 5.2 Water Distribution Pipe Sizing, Velocity & Pressure Drop 5.3 Potable Water Piping Materials, Joining Methods & Valves 5.4 Potable Water System Testing, Disinfection & Commissioning 5.5 Health Care Plumbing: Hospitals, Labs & Medical Offices (MPC 609)

6 Chapter 6: Cross-Connection Control & Backflow Prevention

6.1 Backflow Principles: Backpressure, Backsiphonage & Hazard Levels 6.2 Backflow Prevention Assemblies & Devices 6.3 Installation, Testing & Certification of Backflow Preventers

7 Chapter 7: Sanitary Drainage: Sizing & System Layout

7.1 Drainage Fixture Units (DFU) & Building Drain / Sewer Sizing 7.2 Minimum Slopes, Flow Velocity & Horizontal Drainage Piping 7.3 Soil & Waste Stacks, Stack Offsets & Base Fittings 7.4 Sump Pumps, Sewage Ejectors & Macerating Toilet Systems

8 Chapter 8: Sanitary Drainage: Cleanouts, Materials & Testing

8.1 Cleanout Sizing, Location, Clearances & Direction of Flow 8.2 Drainage Pipe Materials, Drainage Fittings & Prohibited Fittings 8.3 Drainage System Testing: Water, Air & Final Inspection Tests

9 Chapter 9: Indirect & Special Waste Systems

9.1 Air Gaps vs. Air Breaks: Code Definitions, Sizing & Applications 9.2 Food Handling Establishments, Commercial Dishwashers & Beverage Lines 9.3 Chemical, Corrosive & Special Laboratory Waste Systems

10 Chapter 10: Vents & Venting: Principles & Sizing

10.1 Venting Fundamentals: Atmospheric Pressure & Trap Seal Protection 10.2 Vent Stacks, Stack Vents & Individual Vent Sizing Rules 10.3 Vent Terminations, Roof Penetrations & Michigan Frost Closure

11 Chapter 11: Advanced Venting Systems

11.1 Wet Venting: Horizontal & Vertical Rules and Pipe Sizing 11.2 Circuit & Loop Venting: Sizing, Fixture Limits & Relief Vents 11.3 Combination Waste & Vent Systems (CWV) 11.4 Air Admittance Valves (AAVs) & Michigan Part 7 Restrictions

12 Chapter 12: Traps, Interceptors & Separators

12.1 Fixture Trap Design, Trap Seal Depth & Maximum Trap-to-Vent Distance 12.2 Prohibited Traps, Double Trapping & Trap Seal Primer Mechanisms 12.3 Grease Interceptors: Hydromechanical (HGI) vs. Gravity (GGI) 12.4 Oil Separators, Sand Interceptors & Flammable Liquid Separation

13 Chapter 13: Storm Drainage Systems

13.1 Roof Drainage Sizing & Michigan Rainfall Rates 13.2 Primary vs. Secondary (Emergency) Overflow Roof Drainage 13.3 Conductors, Leaders, Building Storm Drains & Sump Systems

14 Chapter 14: Gas Piping Systems: Fuel Gas & Medical Gas

14.1 Fuel Gas Sizing Methods: Longest Length & Branch Sizing 14.2 Fuel Gas Piping Materials, Fittings, Joining & Hangers 14.3 Appliance Shutoffs, Regulators, Sediment Traps & Pressure Testing 14.4 Medical Gas, Vacuum & Nonmedical Oxygen Piping (MPC Chapter 12)

15 Chapter 15: Isometric Drawings & Blueprint Reading

15.1 Isometric Drawing Fundamentals: 30-Degree Axes & Fitting Symbols 15.2 Reading & Interpreting DWV Isometric Riser Diagrams 15.3 Reading & Interpreting Water Supply & Gas Isometric Layouts 15.4 Identifying Code Violations & Layout Errors in Isometric Drawings

16 Chapter 16: Plumbing Math, Calculations & Practical Skills

16.1 45-Degree Offsets, Rolling Offsets & Fitting Allowances 16.2 Grade, Fall, Percentage of Slope & Invert Elevation Calculations 16.3 Volume, Capacity, Head Pressure & Flow Rate Calculations 16.4 Michigan Practical Examination: Soldering, Brazing, Assembly & Safety

12.3 Grease Interceptors: Hydromechanical (HGI) vs. Gravity (GGI)

Key Takeaways Explain This Topic AI

Commercial food service establishments generate fats, oils, and grease (FOG) that congeal upon cooling; under MPC Section 1003.3, all fixtures discharging grease-laden waste must route through an approved grease interceptor.

Hydromechanical Grease Interceptors (HGIs) comply with ASME A112.14.3 / CSA B481.1, utilize hydromechanical air entrainment and internal baffles, are typically installed indoors near point-of-use, and require a certified external vented flow control device.

Under ASME A112.14.3, an HGI's grease retention capacity in pounds must equal at least twice its certified flow rating in gallons per minute (Pounds >= 2 x GPM).

Gravity Grease Interceptors (GGIs) comply with IAPMO Z1001, consist of large outdoor multi-compartment underground vaults (750 to 2,000+ gallons), and rely strictly on natural floatation over an engineering minimum hydraulic retention time of 30 minutes.

MPC Section 1003.3.2 strictly prohibits connecting human sanitary waste (water closets, urinals) and commercial food waste disposers (garbage grinders) to grease interceptors.

Last updated: September 2026

12.3 Grease Interceptors: Hydromechanical (HGI) vs. Gravity (GGI)

Exam Focus: Commercial kitchen fats, oils, and grease (FOG) represent the leading cause of structural sewer blockages and sanitary sewer overflows (SSOs) nationwide. The Michigan Journeyman Plumber licensing examination tests the candidate's mastery of Michigan Plumbing Code (MPC) Section 1003.3 , the engineering distinctions between Hydromechanical Grease Interceptors (HGI) complying with ASME A112.14.3 / PDI G-101 and Gravity Grease Interceptors (GGI) complying with IAPMO Z1001 , the mandatory flow control fitting , the 2x GPM rule for grease capacity, and the explicit list of prohibited fixture connections .

1. The Municipal FOG Crisis & Statutory Mandate (MPC Section 1003.3)

In commercial food preparation facilities—such as restaurants, hospital kitchens, school cafeterias, bakeries, and butcher shops—wastewater contains significant concentrations of animal fats, vegetable oils, and shortening (collectively termed FOG ). FOG enters the drainage system as a warm liquid emulsion ( 120 ∘ F 120^\circ\text{F} 12 0 ∘ F to 160 ∘ F 160^\circ\text{F} 16 0 ∘ F ). As the effluent moves into public sewer mains and cools below 100 ∘ F 100^\circ\text{F} 10 0 ∘ F ( 38 ∘ C 38^\circ\text{C} 3 8 ∘ C ), the lipids congeal and undergo saponification —chemically reacting with alkaline calcium salts in municipal wastewater to form rock-like deposits known as fatbergs .

Under MPC Section 1003.3.1 , an approved grease interceptor must be installed in the waste line leading from sinks and fixtures in all commercial establishments where grease, fat, or oil can be introduced into the drainage system. Discharging untreated grease-laden waste into public sewers violates local sewer use ordinances, Michigan Department of Environment, Great Lakes, and Energy (EGLE) regulations, and the federal Clean Water Act.

2. Hydromechanical Grease Interceptors (HGI / ASME A112.14.3 & PDI G-101)

A Hydromechanical Grease Interceptor (HGI) is an engineered, compact appliance designed to separate FOG from wastewater through a combination of flow restriction, hydromechanical air entrainment, and precision internal baffling. HYDROMECHANICAL GREASE INTERCEPTOR (HGI)

  • FIXTURE WASTE
  • |
  • v
  • [VENTED FLOW] <--- Air Intake Draws Atmospheric Air (Venturi Effect)
  • [CONTROL DEV] Air Bubbles Attach to Microscopic Grease Droplets
  • |
  • +--------------------+
  • |
  • +-------------------------v-----------------------------------------+
  • | REMOVABLE COVER / GASKET |
  • | +-------------+ |
  • | | AIR & GREASE| FLOATING GREASE LAYER |
  • | | DIFFUSER | ~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
  • | +-------------+ CLEAN EFFLUENT |
  • | | DRAWS FROM |
  • | v WATER SEPARATION ZONE THE BOTTOM |
  • | [BAFFLE] | |
  • | | +-----+-----+ |
  • | +---------------------------------------->| OUTLET TEE|==>|==> TO SEWER
  • | +-----------+ |
  • | SETTLED SOLIDS / FOOD SLUDGE |
  • +-------------------------------------------------------------------+
  • Key Engineering Principles of HGIs

Standards & Certification: Must be tested and listed in compliance with ASME A112.14.3 , PDI G-101 , or CSA B481.1 .

Installation Location: Typically installed indoors , directly adjacent to or under the fixtures served (point-of-use), recessed flush with the finished floor, or in a nearby basement/mechanical room.

Construction Materials: Fabricated from heavy-gauge epoxy-coated steel, stainless steel, or high-density engineered thermoplastics (polyethylene or polypropylene).

Vented Flow Control Device (FCD):

Mandatory Component: Every HGI must be installed with an external calibrated flow control fitting on its inlet piping.

Air Injection Mechanism: The flow control fitting incorporates an atmospheric air intake. As wastewater rushes through the calibrated orifice, the pressure drop draws room air into the stream via the venturi effect.

Bubble Attachment: Microscopic air bubbles entrain into the wastewater and attach to suspended grease droplets. Because the combined air-grease agglomerations have a very low specific gravity, their upward flotation velocity increases dramatically, separating FOG in seconds within a compact chamber.

The Certified 2x Retention Rating Rule (ASME A112.14.3):

HGIs are rated by flow capacity in Gallons Per Minute (GPM) and grease retention capacity in Pounds (lbs) .

Under ASME A112.14.3, an HGI must be certified to retain a minimum grease mass in pounds that is at least twice its rated flow in GPM before grease breakthrough occurs: Minimum Grease Retention Capacity (lbs) ≥ 2 × Certified Flow Rate (GPM) \mathbf{\text{Minimum Grease Retention Capacity (lbs)} \ge 2 \times \text{Certified Flow Rate (GPM)}} Minimum Grease Retention Capacity (lbs) ≥ 2 × Certified Flow Rate (GPM)

Standard ASME A112.14.3 Sizing Ratings

  • Flow Rating (GPM) Minimum Certified Grease Capacity (Lbs) Recommended Fixture Capacity Served
  • 20 GPM 40 lbs 1-compartment or 2-compartment prep sink
  • 25 GPM 50 lbs 2-compartment or small 3-compartment pot sink
  • 35 GPM 70 lbs Standard 3-compartment commercial pot-washing sink
  • 50 GPM 100 lbs Heavy 3-compartment sink plus pre-rinse station
  • 75 GPM 150 lbs Multiple commercial scullery sinks
  • 100 GPM 200 lbs Large institutional dish-washing battery
  • Fixture Volume Sizing Formula for HGIs

When sizing an HGI for a commercial sink, plumbers calculate the cubic volume of all sink compartments in inches, convert to gallons, apply a practical fill factor, and divide by the drainage time: Total Volume (gallons) = Length × Width × Depth (inches) × Number of Compartments 231 cu in/gal \text{Total Volume (gallons)} = \frac{\text{Length} \times \text{Width} \times \text{Depth (inches)} \times \text{Number of Compartments}}{231 \text{ cu in/gal}} Total Volume (gallons) = 231 cu in/gal Length × Width × Depth (inches) × Number of Compartments ​ Required Flow (GPM) = Total Volume × 0.75 (75% Fill Factor) Drain-Down Period (1 or 2 Minutes) \mathbf{\text{Required Flow (GPM)} = \frac{\text{Total Volume} \times 0.75 \text{ (75\% Fill Factor)}}{\text{Drain-Down Period (1 or 2 Minutes)}}} Required Flow (GPM) = Drain-Down Period (1 or 2 Minutes) Total Volume × 0.75 (75% Fill Factor) ​

3. Gravity Grease Interceptors (GGI / IAPMO Z1001)

A Gravity Grease Interceptor (GGI) is a large-volume, multi-compartment vault that relies strictly on quiescent, gravity-driven flotation and sedimentation without mechanical air injection or external flow control fittings. GRAVITY GREASE INTERCEPTOR (GGI)

  • INLET MANHOLE BAFFLE MANHOLE OUTLET MANHOLE
  • FRAME & COVER FRAME & COVER FRAME & COVER
  • +-------------+ +-------------+ +-------------+
  • | AT GRADE | | AT GRADE | | AT GRADE |
  • ===+ +------+------+ +------+------+ +------+------+ +===
  • | | | | |
  • | | CHAMBER 1 (2/3) | CHAMBER 2 (1/3) | |
  • IN | +-----v----+ +-----v----+ +-----v----+ | OUT
  • ==>|===>|INLET SAN | FLOATING | BAFFLE | SECONDARY |OUTLET SAN|====>|===>
  • | |TEE BAFFLE| GREASE LAYER | WALL | GREASE LAYER |TEE BAFFLE| | SEWER
  • | +-----+----+ ~~~~~~~~~~~~~ | | ~~~~~~~~~~~~~ +-----+----+ |
  • | | | | ^ |
  • | v QUIESCENT | TRANSFER | QUIESCENT | |
  • | SETTLING ZONE | PORT | SETTLING ZONE | |
  • | | | | |
  • | [SETTLED SLUDGE BASIN] | | [SETTLED SLUDGE] | |
  • +---------------------------------+----------+-----------------------+----------+
  • Key Engineering Principles of GGIs

Standards & Certification: Must comply with IAPMO Z1001 or ASTM C1613 (for precast concrete structures).

Installation Location: Installed outdoors, buried underground outside the building envelope, accessible for commercial vacuum pumper trucks.

Construction Materials: Precast reinforced concrete (minimum 4,000 psi), structural fiberglass, or rotational-molded high-density polyethylene.

The 30-Minute Hydraulic Retention Time (HRT) Formula:

GGIs do not have air bubbles to accelerate separation; they rely entirely on natural buoyancy ( S G grease ≈ 0.88 SG_{\text{grease}} \approx 0.88 S G grease ​ ≈ 0.88 vs. S G water = 1.00 SG_{\text{water}} = 1.00 S G water ​ = 1.00 ).

To allow microscopic grease droplets to rise through deep water columns, wastewater must remain inside the tank for a minimum hydraulic retention time of 30 minutes under peak flow conditions: Minimum Tank Volume (Gallons) = Peak Drainage Flow Rate (GPM) × 30 Minutes \mathbf{\text{Minimum Tank Volume (Gallons)} = \text{Peak Drainage Flow Rate (GPM)} \times 30\text{ Minutes}} Minimum Tank Volume (Gallons) = Peak Drainage Flow Rate (GPM) × 30 Minutes

Standard GGI Capacities: Because of the 30-minute HRT requirement, GGIs are massive structures, with standard municipal sizes ranging from 750 gallons, 1,000 gallons, 1,500 gallons, to 2,000+ gallons .

Internal Compartmentation: GGIs must incorporate at least two chambers. The primary chamber comprises two-thirds (2/3) of the total liquid capacity, and the secondary chamber comprises one-third (1/3) . Baffles extend from 6 inches above the water line to within 12 inches of the floor to prevent short-circuiting.

4. Master Comparison: HGI vs. GGI

  • Engineering Characteristic Hydromechanical Grease Interceptor (HGI) Gravity Grease Interceptor (GGI)
  • Governing Standards ASME A112.14.3, PDI G-101, CSA B481.1 IAPMO Z1001, ASTM C1613

Primary Installation Site Indoors (under counter, adjacent, or recessed in floor) Outdoors (buried underground below frost line)

Separation Physics Hydromechanical air entrainment + baffled flow Quiescent gravity flotation + 30-min retention

Flow Control Requirement Mandatory external vented flow control device Prohibited (direct gravity drainage flow)

Capacity Sizing Metric Flow rate in GPM + Grease mass in Lbs ( 2 × GPM 2\times\text{GPM} 2 × GPM ) Total liquid holding capacity in Gallons (750–2,000+ gal)

Cleaning Method & Cycle Manual or automated cleanout; weekly to bi-weekly Vacuum tanker truck pump-out; every 30 to 90 days

Air Entrainment Vent Yes (draws room air into flow control via venturi) No (sealed system with external atmospheric vents)

5. Prohibited Connections & The 25% Rule (MPC Section 1003.3.2)

Connecting inappropriate waste streams to grease interceptors destroys separation efficiency, creates biohazards, and violates state plumbing codes: +-----------------------------------------------------------------------------+

  • | PROHIBITED GREASE INTERCEPTOR CONNECTIONS |
  • +-----------------------------------------------------------------------------+
  • | |
  • | [1] HUMAN SANITARY BLACKWATER (MPC 1003.3.2): |
  • | - Toilets, water closets, urinals, and bidets are STRICTLY PROHIBITED. |
  • | - Introduces fecal coliforms, causes septic methane gas generation, |
  • | and contaminates grease rendering/recycling streams. |
  • | |
  • | [2] COMMERCIAL FOOD WASTE DISPOSERS / GARBAGE GRINDERS: |
  • | - Commercial food grinders CANNOT discharge into a grease interceptor.|
  • | - Ground organic slurry coats grease, prevents flotation, and causes |
  • | immediate sediment choking. (Solids interceptor required if mandated)|
  • | |
  • | [3] COMMERCIAL HIGH-TEMPERATURE DISHWASHERS (> 140°F): |
  • | - Discharging automated sanitizing rinse water emulsifies grease. |
  • | - Emulsified grease passes straight through interceptor into sewer. |
  • +-----------------------------------------------------------------------------+
  • The 25 Percent Maintenance Rule

Under universal plumbing codes and municipal sewer pre-treatment ordinances, a grease interceptor must be pumped and cleaned whenever: Depth of Floating FOG + Depth of Settled Sludge ≥ 25 % of Total Liquid Depth \mathbf{\text{Depth of Floating FOG} + \text{Depth of Settled Sludge} \ge 25\% \text{ of Total Liquid Depth}} Depth of Floating FOG + Depth of Settled Sludge ≥ 25% of Total Liquid Depth

When combined solids and grease exceed 25% of the operating depth , the effective clear water zone between them is choked. Flow velocity accelerates through the narrow remaining gap, destroying laminar settling and causing grease carryover directly into the municipal sewer.