Study guide

12.1 Attic Ventilation Requirements & Net Free Vent Area Calculations (MRC R806)

Michigan Roofing Contractor Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: The Exam & Michigan Licensing Law

1.1 The Michigan Roofing License Exam: Format, Fees & Test-Day Rules 1.2 Who Must Be Licensed: Residential Builder vs. M&A Roofing & the Exemptions 1.3 Prelicensure Education, Application, Renewal & Continuing Competency 1.4 Company Licenses, Qualifying Officers, Salespersons & Reporting Changes 1.5 Rules of Conduct: Place of Business, Advertising, Written Agreements & Records 1.6 Complaints, Investigations, Hearings, Arbitration & Penalties

2 Chapter 2: Codes, Permits, Civil Rights & Environmental Rules

2.1 The State Construction Code, Permits & Inspections 2.2 Civil Rights, Fair Housing, ADA & Michigan Barrier-Free Design 2.3 EPA Hazardous-Materials Rules: Lead-Safe Renovation, Asbestos & Radon

3 Chapter 3: Business Organization, Contracts & In-Home Sales

3.1 Types of Business Organization: Sole Proprietorship, Partnership, LLC & Corporation 3.2 Contract Essentials: Requirements, Types, Terminology & When a Contract Binds 3.3 Addenda, Change Orders, Allowances, Schedules, Warranties, Financing & Breach 3.4 In-Home Sales: The Home Solicitation Sales Act & Door-to-Door Roofing Sales

4 Chapter 4: Project Management, Accounting, Taxes & Personnel

4.1 Project Management & Administration: Quality, Logistics, Schedules, Draws & Retainage 4.2 Accounting & Finance: Costs, Receivables, Cash Flow, Financial Statements & Ratios 4.3 Payroll & Tax Obligations: Federal, Michigan, Unemployment & Sales/Use Tax 4.4 Personnel: MIOSHA Administration, Recordkeeping, Wages, Minors & Benefits

5 Chapter 5: Insurance, Bonds & Construction Liens

5.1 Insurance for Roofing Contractors: Liability, Workers' Compensation, Vehicles, Property & Builders' Risk 5.2 Bonds, Public Works Bonding & the Building Contract Fund Act 5.3 Construction Lien Act I: Notices of Commencement & Furnishing, Sworn Statements & Waivers 5.4 Construction Lien Act II: Claims of Lien, Foreclosure, Priority & Residential Protections

6 Chapter 6: Roofing Safety & Public Protection (MIOSHA)

6.1 MIOSHA Part 45 Fall Protection & Personal Fall Arrest Systems 6.2 Guardrails, Safety Nets, Warning Lines, Safety Monitors, Covers & Fall Protection Plans 6.3 Ladders, Scaffolds, Roof Brackets & Aerial Lifts (MIOSHA Parts 11, 12 & 32) 6.4 Hazard Communication, SDS, Silica, Lead & Asbestos Exposure, Power Lines & Heat 6.5 Hoisting & Lift Equipment, Fire Prevention, PPE, Barricades, Debris & Recycling

7 Chapter 7: Planning, Structure & Estimating

7.1 Roof Types, Framing Terminology & Structural Loads 7.2 Pre-Job Walk-Through, Plans & Details, Permits & Selecting the Roof System 7.3 Roof Geometry, Slope, Pitch & Slope Factors for Measuring Roofs 7.4 Material Takeoffs: Squares, Bundles, Waste, Underlayment, Ice Barrier, Metals & Fasteners 7.5 Labor, Subcontractor & Access Costs and Preparing the Estimate

8 Chapter 8: Tear-Off, Deck Preparation & Underlayment

8.1 Roof Sheathing: Panel Grades, Spans, Edge Support & Nailing 8.2 Tear-Off vs. Recover, Reroofing Rules & Preparing the Site (MRC R908) 8.3 Michigan's Ice Barrier Requirement: Coverage, Materials & Detailing (R905.1.2) 8.4 Underlayment: Standards, Application by Slope & Attachment (R905.1.1) 8.5 Roof & Ceiling Insulation, Vapor Retarders, Air Sealing & Unvented Assemblies

9 Chapter 9: Steep-Slope Roof Systems

9.1 Asphalt Shingles: Types, ASTM D3462, Wind Classes, Impact & Fire Ratings 9.2 Installing Asphalt Shingles: Starter, Exposure, Nailing, Steep Slopes & Caps 9.3 Valleys: Linings, Open Metal, Closed-Cut & Woven Valleys 9.4 Metal Roof Systems, Tile, Slate & Wood Shingles and Shakes

10 Chapter 10: Low-Slope Roof Systems & Drainage

10.1 Single-Ply Membranes: EPDM, TPO & PVC 10.2 Built-Up Roofing & Modified Bitumen: Materials, Application, Kettles & Torch Safety 10.3 Low-Slope Drainage: Positive Drainage, Roof Drains, Overflow Scuppers & Correcting Ponding

11 Chapter 11: Flashings, Transitions & Penetrations

11.1 Drip Edge & Roof-Edge Metals (R905.2.8.5 and R903.2) 11.2 Sidewalls, Headwalls, Kick-Outs, Counterflashing & Pitch Transitions 11.3 Chimneys & Crickets, Skylights, Pipes, Flues, Exhaust Vents & Solar

12 Chapter 12: Ventilation, Inspection & Repair

12.1 Attic Ventilation Requirements & Net Free Vent Area Calculations (MRC R806) 12.2 Balanced Airflow, Vent Installation Practice & Preventing Ice Dams 12.3 Roof Inspections, Leak Diagnosis, Repairs & Roofovers

12.1 Attic Ventilation Requirements & Net Free Vent Area Calculations (MRC R806)

Key Takeaways Explain This Topic AI

Enclosed attics and enclosed rafter spaces need cross ventilation, with openings protected from rain and snow, opening directly to the outside air (R806.1).

Vent openings must have a least dimension of at least 1/16 inch and no more than 1/4 inch. Larger openings need corrosion-resistant wire cloth, hardware cloth, or similar screening with openings in that range.

The minimum net free ventilating area is 1/150 of the vented space, or 1/300 if a Class I or II ceiling vapor retarder is installed in climate zones 6–8 or 40–50% of the required area is in upper vents within 3 feet of the ridge (R806.2).

At eave or cornice vents, insulation must not block airflow, and at least 1 inch of space is required between the insulation and the roof sheathing at the vent (R806.3).

To convert square feet of NFVA into square inches, multiply by 144, and then divide by each product's labeled NFVA per foot or per unit.

Last updated: September 2026

Why Vent an Attic?

In a Michigan winter, warm, moist indoor air leaks into the attic. Without ventilation and air sealing, the moisture condenses or frosts on the cold underside of the sheathing and roofing nails. When it thaws, it drips, stains ceilings, and rots the deck. Heat in the attic also melts snow that refreezes at the eaves (Section 12.2). In summer, ventilation removes some heat and helps keep shingles within the manufacturer's warranty conditions. Most shingle manufacturers require code-compliant ventilation for full warranty coverage.

The Code Requirements (MRC R806)

Section Requirement

R806.1 Enclosed attics and enclosed rafter spaces (where ceilings are applied directly to rafters) need cross ventilation for each separate space . Openings must be protected against the entrance of rain or snow and open directly to the outside air

R806.1 opening size Least dimension 1/16 inch minimum and 1/4 inch maximum . Larger openings need corrosion-resistant wire cloth, hardware cloth, or similar with openings in that range

R806.2 Minimum net free ventilating area = 1/150 of the vented space

R806.2 exception 1/300 if either (1) in climate zones 6, 7, and 8 , a Class I or II vapor retarder is installed on the warm-in-winter side of the ceiling, or (2) 40–50 percent of the required area is in upper ventilators located no more than 3 feet below the ridge or highest point (measured vertically), with the rest in eave or cornice vents

R806.3 Insulation must not block eave or cornice vents. Keep at least a 1-inch space between the insulation and the sheathing at the vent

  • R806.4 Install ventilators per the manufacturer's instructions , and flash them in roofs per R903
  • R806.5 Unvented attics are allowed only if every listed condition is met (Section 8.5)
  • Applying the 1/300 Exception in Michigan

Climate zone 5A (southern Lower Peninsula): the vapor retarder option is not available , because it applies only in zones 6–8. The upper-and-lower (balanced) option is available everywhere.

Zones 6A and 7 (northern Lower Peninsula and Upper Peninsula): either option can reduce the ratio to 1/300.

If framing blocks upper vents within 3 feet of the ridge, the code allows them to be installed lower (R806.2).

What "Net Free Area" Means

Net free ventilating area is the actual open area air can pass through, after subtracting louvers, screens, and baffles. A 16 × 8 inch soffit vent has 128 square inches of gross area but much less net free area. Always use the NFVA printed on the product label or literature , usually given in square inches per linear foot for ridge and strip vents, or square inches per unit for louvers and box vents.

  • Calculating Required Vent Area
  • Step by Step

Find the attic floor area (the vented space), in square feet. Use the ceiling area below the attic, not the roof surface area.

Divide by 150 , or by 300 if an exception applies. The result is square feet of NFVA.

Multiply by 144 to convert to square inches.

With the balanced option, put 40–50 percent in upper (exhaust) vents and the rest in eave (intake) vents.

Divide each portion by the product's NFVA rating to find linear feet or the number of units.

Worked Example 1: 1/150

A ranch house in Lansing (zone 5A) has a 1,500 sq ft attic and no qualifying vent arrangement.

1,500 ÷ 150 = 10 sq ft NFVA.

10 × 144 = 1,440 sq in .

Worked Example 2: 1/300 With Balanced Vents

The same house uses ridge vents near the peak and continuous soffit vents.

1,500 ÷ 300 = 5 sq ft = 720 sq in .

Upper vents: 40–50 percent = 288 to 360 sq in . Using 50 percent, 360 sq in upper and 360 sq in lower.

If the ridge vent label says 18 sq in NFVA per linear foot: 360 ÷ 18 = 20 linear feet of ridge vent.

If the soffit vent strip label says 9 sq in per linear foot: 360 ÷ 9 = 40 linear feet of soffit vent, split between both eaves.

The ratings in this example are for practice only. Real products vary, so always use the label.

Worked Example 3: Zone 6A With a Vapor Retarder

A Traverse City home (zone 6A) has a 1,200 sq ft attic and a Class II vapor retarder on the warm side of the ceiling. The vapor retarder exception applies:

1,200 ÷ 300 = 4 sq ft = 576 sq in total NFVA.

Types of Vents

Location Type Notes

Intake (low) Continuous soffit strip, individual soffit vents, perforated soffit panels The most common intake. Keep them clear of insulation with baffles

Intake (low) Vented drip edge or fascia vents Used where there is little or no soffit overhang. Check the NFVA, because it is often low per foot

Intake (low) Over-fascia or "smart" intake vents installed in the lower roof deck Used where soffits cannot be vented

Exhaust (high) Ridge vent A continuous slot at the ridge covered by a baffled vent and ridge cap. Cut the slot to the maker's width, and stop short of the ends as directed

Exhaust (high) Static louvers (box vents), turbines, gable louvers Place them within 3 feet of the ridge to count as upper vents for the 1/300 option

  • Exhaust (high) Powered attic ventilators Not required by code. Discussed in Section 12.2
  • Common Exam Traps

The code uses attic floor area , not roof area.

1/150 is the default . 1/300 needs a qualifying condition.

The vapor retarder exception is limited to zones 6–8 , not the whole state.

The balanced exception needs 40–50 percent high, not "at least 50 percent".

Screening openings must be between 1/16 and 1/4 inch .