2.2 AC Fundamentals: Reactance, Impedance & Power Factor
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
2.2 AC Fundamentals: Reactance, Impedance & Power Factor
Key Takeaways Explain This Topic AI
In sinusoidal alternating current ( 60 Hz 60\text{ Hz} 60 Hz in North America), root-mean-square voltage represents heating equivalence to DC: V RMS = V peak 2 ≈ 0.7071 × V peak V_{\text{RMS}} = \frac{V_{\text{peak}}}{\sqrt{2}} \approx 0.7071 \times V_{\text{peak}} V RMS = 2 V peak ≈ 0.7071 × V peak .
Inductive reactance ( X L = 2 π f L X_L = 2\pi f L X L = 2 π f L ) opposes current changes and causes current to lag voltage, while capacitive reactance ( X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C = 2 π f C 1 ) opposes voltage changes and causes current to lead voltage ('ELI the ICE man').
Total opposition to alternating current is impedance ( Z Z Z ), calculated in series RLC circuits as Z = R 2 + ( X L − X C ) 2 Z = \sqrt{R^2 + (X_L - X_C)^2} Z = R 2 + ( X L − X C ) 2 in ohms ( Ω \Omega Ω ).
The AC power triangle relates true power ( P P P in watts), reactive power ( Q Q Q in VAR), and apparent power ( S S S in VA) through the Pythagorean relationship S = P 2 + Q 2 S = \sqrt{P^2 + Q^2} S = P 2 + Q 2 .
Power factor is true power divided by apparent power ( PF = P S = cos θ \text{PF} = \frac{P}{S} = \cos \theta PF = S P = cos θ ); correction capacitors are sized as Q C = P ( tan θ 1 − tan θ 2 ) Q_C = P(\tan\theta_1 - \tan\theta_2) Q C = P ( tan θ 1 − tan θ 2 ) .
Last updated: October 2026
2.2 AC Fundamentals: Reactance, Impedance & Power Factor
While direct current flows steadily in a single direction, commercial and residential utility power is generated and distributed as sinusoidal alternating current (AC). In alternating current systems, voltage and current continuously reverse polarity and direction. The presence of coils (magnetic fields) and dielectric surfaces (electrostatic fields) introduces reactive phenomena that fundamentally alter circuit calculations compared to basic DC resistive networks.
Nature of Alternating Current Waveforms
In North America, utility electrical systems operate at a standard frequency ( f f f ) of 60 hertz 60\text{ hertz} 60 hertz ( Hz \text{Hz} Hz ), completing 60 complete cycles of positive and negative alternation per second. The time required to complete one full cycle is the period ( T T T ):
T = 1 f = 1 60 Hz ≈ 0.01667 s = 16.67 ms T = \frac{1}{f} = \frac{1}{60\text{ Hz}} \approx 0.01667\text{ s} = 16.67\text{ ms} T = f 1 = 60 Hz 1 ≈ 0.01667 s = 16.67 ms
Sinusoidal Voltage Measurements
Because an AC sine wave continuously changes value from zero to positive peak, back through zero to negative peak, and returns to zero, electricians use three distinct voltage metrics:
Peak Voltage ( V peak V_{\text{peak}} V peak ): The maximum instantaneous potential attained during the cycle, measured from the zero baseline to the crest.
Peak-to-Peak Voltage ( V pk-pk V_{\text{pk-pk}} V pk-pk ): The total voltage excursion from the positive crest to the negative trough: V pk-pk = 2 × V peak V_{\text{pk-pk}} = 2 \times V_{\text{peak}} V pk-pk = 2 × V peak .
Root-Mean-Square Voltage ( V RMS V_{\text{RMS}} V RMS ): Also termed the effective voltage , V RMS V_{\text{RMS}} V RMS represents the DC equivalent voltage that would produce identical thermal heating in a pure resistance:
V RMS = V peak 2 ≈ 0.7071 × V peak V_{\text{RMS}} = \frac{V_{\text{peak}}}{\sqrt{2}} \approx 0.7071 \times V_{\text{peak}} V RMS = 2 V peak ≈ 0.7071 × V peak V peak = 2 × V RMS ≈ 1.4142 × V RMS V_{\text{peak}} = \sqrt{2} \times V_{\text{RMS}} \approx 1.4142 \times V_{\text{RMS}} V peak = 2 × V RMS ≈ 1.4142 × V RMS
All standard multimeters, utility service ratings, and National Electrical Code voltage classifications ( 120 V 120\text{ V} 120 V , 208 V 208\text{ V} 208 V , 240 V 240\text{ V} 240 V , 277 V 277\text{ V} 277 V , 480 V 480\text{ V} 480 V ) denote RMS values. For example, a nominal 120 V 120\text{ V} 120 V RMS branch circuit actually reaches a peak instantaneous potential of:
V peak = 120 V × 1.4142 ≈ 169.7 V V_{\text{peak}} = 120\text{ V} \times 1.4142 \approx 169.7\text{ V} V peak = 120 V × 1.4142 ≈ 169.7 V
Inductive and Capacitive Reactance
When pure resistance is energized by AC, current and voltage remain precisely in phase—both pass through zero and reach peak values simultaneously. However, electromagnetic coils and capacitors introduce opposition to alternating current known as reactance ( X X X ), measured in ohms ( Ω \Omega Ω ).
Inductive Reactance ( X L X_L X L )
An inductor (such as a motor winding, transformer coil, or magnetic ballast) stores energy within a concentrated magnetic field. According to Faraday's and Lenz's Laws, any change in current induces a counter-electromotive force (CEMF) that directly opposes that change. This opposition is inductive reactance ( X L X_L X L ):
X L = 2 π f L X_L = 2\pi f L X L = 2 π f L
Where:
- f f f = frequency in hertz ( Hz \text{Hz} Hz )
- L L L = inductance in henrys ( H \text{H} H )
- X L X_L X L = inductive reactance in ohms ( Ω \Omega Ω )
Because an inductor opposes current changes, current is delayed behind voltage. In an ideal, purely inductive circuit, current lags voltage by exactly 90 ∘ 90^\circ 9 0 ∘ .
Capacitive Reactance ( X C X_C X C )
A capacitor stores energy electrostatically across conductive plates separated by an insulating dielectric. As alternating potential rises, charge rushes into the plates; when potential falls, charge discharges back into the line. The opposition offered to alternating current flow is capacitive reactance ( X C X_C X C ):
X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C = 2 π f C 1
Where:
- f f f = frequency in hertz ( Hz \text{Hz} Hz )
- C C C = capacitance in farads ( F \text{F} F )
- X C X_C X C = capacitive reactance in ohms ( Ω \Omega Ω )
In a capacitor, maximum current flows when voltage is zero but changing at its fastest rate. Therefore, in an ideal purely capacitive circuit, current leads voltage by exactly 90 ∘ 90^\circ 9 0 ∘ .
The "ELI the ICE man" Mnemonic
Electricians use a standard trade mnemonic to remember phase angle relationships:
ELI: Voltage ( E E E ) Leads Current ( I I I ) in an Inductor ( L L L ).
ICE: Current ( I I I ) Leads Voltage ( E E E ) in a Capacitor ( C C C ).
Circuit Impedance ( Z Z Z )
In practical AC circuits containing resistance ( R R R ), inductance ( L L L ), and capacitance ( C C C ), total opposition to current cannot be found through simple arithmetic addition. Because resistance and net reactance act 90 ∘ 90^\circ 9 0 ∘ apart in time, they must be combined using vector addition (the Pythagorean theorem). The total opposition is impedance ( Z Z Z ), measured in ohms ( Ω \Omega Ω ).
The Series Impedance Formula
Because inductive reactance and capacitive reactance act 180 ∘ 180^\circ 18 0 ∘ opposite each other, they cancel directly:
X net = X L − X C X_{\text{net}} = X_L - X_C X net = X L − X C
Total circuit impedance is given by:
Z = R 2 + ( X L − X C ) 2 Z = \sqrt{R^2 + (X_L - X_C)^2} Z = R 2 + ( X L − X C ) 2
Applying Ohm's Law to AC circuits utilizes impedance in place of pure resistance:
V = I × Z I = V Z Z = V I V = I \times Z \qquad I = \frac{V}{Z} \qquad Z = \frac{V}{I} V = I × Z I = Z V Z = I V
Worked Example: Series RLC Circuit
A 120 V 120\text{ V} 120 V , 60 Hz 60\text{ Hz} 60 Hz single-phase AC circuit contains a resistor with R = 8 Ω R = 8\ \Omega R = 8 Ω , an inductor with X L = 15 Ω X_L = 15\ \Omega X L = 15 Ω , and a capacitor with X C = 9 Ω X_C = 9\ \Omega X C = 9 Ω connected in series.
Calculate Net Reactance ( X net X_{\text{net}} X net ): X net = X L − X C = 15 Ω − 9 Ω = 6 Ω (net inductive) X_{\text{net}} = X_L - X_C = 15\ \Omega - 9\ \Omega = 6\ \Omega\text{ (net inductive)} X net = X L − X C = 15 Ω − 9 Ω = 6 Ω (net inductive)
Calculate Total Impedance ( Z Z Z ): Z = R 2 + X net 2 = 8 2 + 6 2 = 64 + 36 = 100 = 10 Ω Z = \sqrt{R^2 + X_{\text{net}}^2} = \sqrt{8^2 + 6^2} = \sqrt{64 + 36} = \sqrt{100} = 10\ \Omega Z = R 2 + X net 2 = 8 2 + 6 2 = 64 + 36 = 100 = 10 Ω
Calculate Circuit Current ( I I I ): I = V Z = 120 V 10 Ω = 12 A I = \frac{V}{Z} = \frac{120\text{ V}}{10\ \Omega} = 12\text{ A} I = Z V = 10 Ω 120 V = 12 A
Calculate Component Voltage Drops:
V R = I × R = 12 A × 8 Ω = 96 V V_R = I \times R = 12\text{ A} \times 8\ \Omega = 96\text{ V} V R = I × R = 12 A × 8 Ω = 96 V
V L = I × X L = 12 A × 15 Ω = 180 V V_L = I \times X_L = 12\text{ A} \times 15\ \Omega = 180\text{ V} V L = I × X L = 12 A × 15 Ω = 180 V
V C = I × X C = 12 A × 9 Ω = 108 V V_C = I \times X_C = 12\text{ A} \times 9\ \Omega = 108\text{ V} V C = I × X C = 12 A × 9 Ω = 108 V
Verification via vector sum: V T = V R 2 + ( V L − V C ) 2 = 96 2 + ( 180 − 108 ) 2 = 9 , 216 + 5 , 184 = 14 , 400 = 120 V V_T = \sqrt{V_R^2 + (V_L - V_C)^2} = \sqrt{96^2 + (180 - 108)^2} = \sqrt{9,216 + 5,184} = \sqrt{14,400} = 120\text{ V} V T = V R 2 + ( V L − V C ) 2 = 9 6 2 + ( 180 − 108 ) 2 = 9 , 216 + 5 , 184 = 14 , 400 = 120 V
The AC Power Triangle and Power Factor
In AC circuits containing reactance, voltage and current waveforms are out of phase. As a result, not all apparent energy delivered to the circuit performs useful mechanical or thermal work.
The Three Components of AC Power
True Power ( P P P ): Also known as real power or active power , measured in watts ( W \text{W} W ) or kilowatts ( kW \text{kW} kW ). True power represents the rate of actual energy consumed and transformed into mechanical shaft rotation, heat, or light: P = V × I × cos θ = I 2 × R P = V \times I \times \cos \theta = I^2 \times R P = V × I × cos θ = I 2 × R
Reactive Power ( Q Q Q ): Measured in volt-amperes reactive ( VAR \text{VAR} VAR ) or kilovolt-amperes reactive ( kVAR \text{kVAR} kVAR ). Reactive power represents the energy that oscillates back and forth between the power source and the magnetic/electrostatic fields without doing net work: Q = V × I × sin θ = I 2 × X Q = V \times I \times \sin \theta = I^2 \times X Q = V × I × sin θ = I 2 × X
Apparent Power ( S S S ): Measured in volt-amperes ( VA \text{VA} VA ) or kilovolt-amperes ( kVA \text{kVA} kVA ). Apparent power represents the total vector combination of true and reactive power, reflecting the total capacity that utility generators, transformers, and conductors must supply: S = V × I = I 2 × Z = P 2 + Q 2 S = V \times I = I^2 \times Z = \sqrt{P^2 + Q^2} S = V × I = I 2 × Z = P 2 + Q 2
Understanding Power Factor ( PF \text{PF} PF )
Power factor is the ratio of true work-performing power to apparent power supplied:
PF = P S = cos θ \text{PF} = \frac{P}{S} = \cos \theta PF = S P = cos θ
Where θ \theta θ is the phase angle between voltage and current waveforms. Power factor is expressed either as a decimal between 0.0 0.0 0.0 and 1.0 1.0 1.0 , or as a percentage from 0 % 0\% 0% to 100 % 100\% 100% .
Lagging Power Factor: Occurs in inductive circuits (e.g., induction motors, welders, HID ballasts) where current lags voltage.
Leading Power Factor: Occurs in capacitive circuits where current leads voltage.
Unity Power Factor ( 1.0 1.0 1.0 or 100 % 100\% 100% ): Occurs in purely resistive circuits where voltage and current are in phase ( S = P S = P S = P ).
Practical Trade Impact: Conductor Sizing and Power Factor Correction
A low power factor forces conductors, circuit breakers, and distribution transformers to carry excessive current to deliver a given amount of true power. For instance, consider a 480 V 480\text{ V} 480 V industrial pump drawing 48 kW 48\text{ kW} 48 kW of true power:
At 0.60 Power Factor: S = 48 kW 0.60 = 80 kVA ⟹ I = 80 , 000 VA 480 V ≈ 166.7 A S = \frac{48\text{ kW}}{0.60} = 80\text{ kVA} \implies I = \frac{80,000\text{ VA}}{480\text{ V}} \approx 166.7\text{ A} S = 0.60 48 kW = 80 kVA ⟹ I = 480 V 80 , 000 VA ≈ 166.7 A
At 1.00 Power Factor (Corrected): S = 48 kW 1.00 = 48 kVA ⟹ I = 48 , 000 VA 480 V = 100.0 A S = \frac{48\text{ kW}}{1.00} = 48\text{ kVA} \implies I = \frac{48,000\text{ VA}}{480\text{ V}} = 100.0\text{ A} S = 1.00 48 kW = 48 kVA ⟹ I = 480 V 48 , 000 VA = 100.0 A
By installing power factor correction capacitors in parallel with inductive loads, the capacitive leading current ( I C I_C I C ) cancels out the inductive lagging current ( I L I_L I L ). Conductor current drops by 66.7 A 66.7\text{ A} 66.7 A ( 40 % 40\% 40% ), reducing I 2 R I^2 R I 2 R heat loss, freeing up feeder capacity, and eliminating utility low-power-factor penalties.
Sizing Correction Capacitors (kVAR)
To raise a load's power factor, a capacitor bank supplies the reactive power that the load would otherwise draw from the source. The capacitor rating is the difference between the reactive power before and after correction:
Q C = P × ( tan θ 1 − tan θ 2 ) Q_C = P \times (\tan\theta_1 - \tan\theta_2) Q C = P × ( tan θ 1 − tan θ 2 )
where θ 1 = cos − 1 ( PF 1 ) \theta_1 = \cos^{-1}(\text{PF}_1) θ 1 = cos − 1 ( PF 1 ) and θ 2 = cos − 1 ( PF 2 ) \theta_2 = \cos^{-1}(\text{PF}_2) θ 2 = cos − 1 ( PF 2 ) .
Example: A 100 kW load runs at 0.70 PF and is to be corrected to 0.95 PF.
θ 1 = cos − 1 ( 0.70 ) = 45.57 ∘ \theta_1 = \cos^{-1}(0.70) = 45.57^\circ θ 1 = cos − 1 ( 0.70 ) = 45.5 7 ∘ , so tan θ 1 = 1.020 \tan\theta_1 = 1.020 tan θ 1 = 1.020
θ 2 = cos − 1 ( 0.95 ) = 18.19 ∘ \theta_2 = \cos^{-1}(0.95) = 18.19^\circ θ 2 = cos − 1 ( 0.95 ) = 18.1 9 ∘ , so tan θ 2 = 0.329 \tan\theta_2 = 0.329 tan θ 2 = 0.329
Q C = 100 × ( 1.020 − 0.329 ) = 69.1 Q_C = 100 \times (1.020 - 0.329) = 69.1 Q C = 100 × ( 1.020 − 0.329 ) = 69.1 kVAR
Apparent power drops from 100 ÷ 0.70 = 142.9 100 \div 0.70 = 142.9 100 ÷ 0.70 = 142.9 kVA to 100 ÷ 0.95 = 105.3 100 \div 0.95 = 105.3 100 ÷ 0.95 = 105.3 kVA, so the source and feeder current fall by about 26%. The capacitor installation itself is covered by NEC Article 460, which requires capacitor circuit conductors to have an ampacity of at least 135% of the capacitor's rated current.
Note
DLI's exam guide states that, unless a question says otherwise, all questions assume a unity power factor . Use power-factor math only when the question gives a power factor or asks about correction.
Summary of AC Power Quantities
Quantity Symbol Unit Formula Physical Meaning
True Power P P P Watts ( W \text{W} W , kW \text{kW} kW ) P = V × I × cos θ P = V \times I \times \cos \theta P = V × I × cos θ Useful energy converted to heat, light, motion
Reactive Power Q Q Q Volt-Amps Reactive ( VAR \text{VAR} VAR ) Q = V × I × sin θ Q = V \times I \times \sin \theta Q = V × I × sin θ Energy oscillating in magnetic/dielectric fields
Apparent Power S S S Volt-Amps ( VA \text{VA} VA , kVA \text{kVA} kVA ) S = V × I = P 2 + Q 2 S = V \times I = \sqrt{P^2 + Q^2} S = V × I = P 2 + Q 2 Total line capacity delivered by utility
Power Factor PF \text{PF} PF Dimensionless (Ratio / % \% % ) PF = P S = cos θ \text{PF} = \frac{P}{S} = \cos \theta PF = S P = cos θ Efficiency of power utilization