3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

Key Takeaways Explain This Topic AI

Outdoor over-1000 V installations accessible to unqualified persons need a fence at least 7 ft high, or a 6 ft fence topped with at least 1 ft of three or more strands of barbed wire (110.31).

Table 110.34(A) requires 4 ft, 5 ft, and 6 ft of working space depth for Conditions 1, 2, and 3 at 2501 to 9000 volts.

Rooms and enclosures containing exposed live parts over 1000 V must be kept locked unless under the observation of a qualified person, and must carry permanent DANGER warning signs (110.34(C)).

A round manhole access opening must be at least 26 in. in diameter, and a rectangular opening at least 26 in. by 22 in. (110.75(A)).

Manhole covers must weigh over 100 lb or require tools to open, and must carry an identifying mark or logo showing electrical use (110.75(D) and (E)).

Last updated: October 2026

Where the over-1000-volt rules live in the 2026 NEC

Journeyworkers install switchgear, transformers, and feeders at 4160 V, 13.2 kV, or higher on campus and industrial sites. Article 110 still contains the general rules:

Part III: over 1000 V ac, 1500 V dc, nominal: enclosures, working space, guarding, and terminations.

Part IV: tunnel installations over 1000 V.

Part V: manholes and other enclosures intended for personnel entry, at any voltage.

The 2026 NEC moved the other over-1000-volt material into a dedicated group of articles:

  • Article Covers
  • 245 Overcurrent protection for systems over 1000 V ac, 1500 V dc

265, 266, 267 Branch circuits, feeders, and outside branch circuits and feeders over 1000 V (formerly Article 235)

  • 268 Services over 1000 V
  • 270 Grounding and bonding of systems over 1000 V
  • 305 General wiring methods and materials over 1000 V
  • 315 Medium-voltage (Type MV) conductors, cable, cable joints, and terminations
  • 495 Equipment over 1000 V ac, 1500 V dc
  • Enclosing high-voltage installations (110.31)

Electrical installations in a vault, room, closet, or area surrounded by a wall, screen, or fence with access controlled by lock and key are considered accessible to qualified persons only .

Situation Requirement

Outdoor fence At least 7 ft high, or a 6 ft fence plus 1 ft or more of three or more strands of barbed wire (or equivalent)

Fence clearance to live parts Table 110.31: 10 ft for 1001 to 13,799 V; 15 ft for 13,800 V to 230 kV; 18 ft over 230 kV

Indoor, accessible to unqualified persons Use metal-enclosed equipment; openings in ventilated dry-type transformers must deflect inserted objects away from energized parts

Outdoor, accessible to unqualified persons Metal-enclosed equipment; doors or hinged covers locked, and bolts or screws on covers not readily removable

Working space over 1000 volts (110.32 to 110.34)

Section 110.34(A) requires a working space at least 6½ ft high and 3 ft wide (or the equipment width) in front of equipment likely to need examination, adjustment, servicing, or maintenance while energized, with enough room for doors and hinged panels to open at least 90 degrees. Depth comes from Table 110.34(A), using the same three conditions as Table 110.26(A)(1):

  • Nominal voltage to ground Condition 1 Condition 2 Condition 3
  • 1001 to 2500 V 3 ft 4 ft 5 ft
  • 2501 to 9000 V 4 ft 5 ft 6 ft
  • 9001 to 25,000 V 5 ft 6 ft 9 ft
  • 25,001 V to 75 kV 6 ft 8 ft 10 ft
  • Above 75 kV 8 ft 10 ft 12 ft

Condition 1 has no live or grounded parts across the space; Condition 2 has grounded parts (including concrete, brick, or tile walls) across the space; Condition 3 has exposed live parts on both sides. Working space is not required in back of equipment, such as dead-front switchgear, where there are no renewable or adjustable parts and all connections are accessible from other than the back.

Entrances (110.33)

At least one entrance 24 in. wide and 6½ ft high must give access to the working space. Where switchgear or control panels are more than 6 ft wide , an entrance is needed at each end , unless the location permits a continuous and unobstructed way of exit or the working space is doubled. Personnel doors less than 25 ft from the nearest edge of the working space must open in the direction of egress and have listed panic or fire exit hardware.

Locking, signs, and lighting (110.34(C) and (D))

Buildings, vaults, rooms, or enclosures containing exposed live parts or exposed conductors over 1000 V must be kept locked unless under the observation of a qualified person.

Permanent, conspicuous signs must read DANGER — HIGH VOLTAGE — KEEP OUT , following 110.21(B).

Lighting outlets must be arranged so that people changing lamps or repairing the lighting system are not endangered by live parts, and the lighting controls must be located so people do not contact live parts when operating them.

Elevation of unguarded live parts (110.34(E))

  • Nominal voltage between phases Minimum elevation
  • 1001 to 7500 V 9 ft
  • 7501 V to 35 kV 9 ft 6 in
  • Over 35 kV 9 ft 6 in plus 0.37 in. per kV above 35 kV

Section 110.34(F) also keeps pipes and ducts foreign to the electrical installation away from service equipment, metal-enclosed power switchgear, and industrial control assemblies, or requires protection against leaks and condensation.

Pull and junction boxes over 1000 volts

The pull and junction box rules for systems over 1000 V (Part IV of Article 314 in the 2023 NEC; the 2026 NEC gathers over-1000 V wiring method and material rules in new Article 305) size boxes by cable diameter, not raceway trade size :

Pull Minimum box dimension

Straight pull Length at least 48 times the outside diameter, over the sheath, of the largest shielded or lead-covered conductor or cable; 32 times for the largest nonshielded conductor or cable

Angle or U pull Distance from each cable entry to the opposite wall at least 36 times the outside diameter of the largest cable, increased by the diameters of other entries through the same wall; distance between the entry and exit of the same cable at least 36 times its outside diameter

Box covers must be permanently marked "DANGER — HIGH VOLTAGE — KEEP OUT" on the outside, in block letters at least ½ in. high. Example: the largest shielded cable entering a straight-pull box has an outside diameter of 1.5 in., so the box must be at least 48 × 1.5 = 72 48 \times 1.5 = 72 48 × 1.5 = 72 in. long.

Manholes and other enclosures for personnel entry (Part V)

Part V applies to manholes, vaults, and similar enclosures that people enter to install, operate, or maintain equipment and conductors, at any voltage.

  • Rule Requirement
  • Strength (110.71) Designed under qualified engineering supervision to withstand all expected loads

Cabling work space (110.72) At least 3 ft wide where cables are on both sides, or 2½ ft where cables are on one side only; at least 6 ft of vertical headroom unless the access opening is within 1 ft horizontally of the adjacent interior side wall

Equipment work space (110.73) Where equipment with moving parts needs servicing, provide working space per Table 110.26(A)(1) or Table 110.34(A)

Access openings (110.75(A)) Rectangular openings at least 26 in. × 22 in. ; round openings at least 26 in. in diameter; an exception allows a 24 in. round opening in specific cases, such as a manhole with a fixed ladder that does not obstruct the opening

Obstructions and location (110.75(B), (C)) Openings may not be obstructed by objects that would inhibit ready exit, and should not be directly above electrical equipment or conductors where possible

Covers (110.75(D), (E)) Covers must weigh over 100 lb or require tools to open; they must be restrained so they cannot fall into the manhole or onto energized parts, and must carry a mark or logo showing electrical use

Guarding (110.78) Conductors and equipment that could be contacted by objects falling or being moved through the opening must be protected

Fixed ladders (110.79) Must be corrosion resistant

Warning

A manhole is also a permit-required confined space under OSHA rules. Atmospheric testing, ventilation, attendants, and rescue planning come from OSHA and NFPA 70E, not the NEC.

Worked example

A 12.47 kV switchgear lineup faces a concrete block wall. The voltage to ground of a 12.47Y/7.2 kV system is 7200 V, which falls in the 2501 to 9000 V row. A concrete wall is grounded, so the space is Condition 2 , and Table 110.34(A) requires a working space depth of 5 ft . If a second lineup with exposed live parts faced it instead, Condition 3 would require 6 ft .