Study guide

6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44)

Key Takeaways Explain This Topic AI

Table 120.42(A) lists general lighting unit loads such as 1.3 VA/ft² for offices, 1.9 for retail, 1.5 for schools and restaurants, 1.2 for warehouses, and 2.2 for manufacturing facilities.

Nondwelling receptacle outlets are calculated at 180 VA per single or multiple receptacle on one yoke.

Table 120.44 permits nondwelling receptacle loads to be taken at 100% of the first 10 kVA and 50% of the remainder.

In banks and office buildings, the receptacle load is the larger of the calculated 180 VA per outlet load after demand or 1 VA/ft² (120.14(K)).

Each required sign outlet adds at least 1,200 VA (120.14(F)), and show-window lighting adds 200 VA per linear foot of show window.

Last updated: October 2026

Commercial calculations on the exam

DLI's knowledge areas include commercial load calculations . Expect a building area, an occupancy type, and a list of receptacles, signs, show windows, and equipment. Build the load line by line, apply only the demand factors the Code allows, and convert to amperes with the correct voltage formula.

General lighting (120.42 and Table 120.42(A))

Multiply the floor area (outside dimensions, 120.5(C)) by the unit load for the occupancy:

  • Occupancy VA/ft² Occupancy VA/ft²
  • Automotive facility 1.5 Manufacturing facility 2.2
  • Convention center 1.4 Motion picture theater 1.6
  • Courthouse 1.4 Museum 1.6
  • Dormitory 1.5 Office 1.3
  • Exercise center 1.4 Parking garage 0.3
  • Fire station 1.3 Penitentiary 1.2
  • Gymnasium 1.7 Performing arts theater 1.5
  • Health care clinic 1.6 Police station 1.3
  • Hospital 1.6 Post office 1.6
  • Hotel and motel, including apartment houses without cooking provisions 1.7 Religious facility 2.2
  • Library 1.5 Restaurant 1.5
  • Retail 1.9 School or university 1.5
  • Sports arena 1.1 Town hall 1.4
  • Transportation 1.2 Warehouse 1.2
  • Workshop 1.7

Table 120.45 demand factors then apply: 100% for most occupancies, with reductions only for dwellings, hotels and motels, and warehouses (first 12,500 VA at 100%, remainder at 50%). Section 120.42(B) allows a building designed to an adopted energy code to use the energy code's lighting power values under specific conditions, such as a power monitoring system.

Note

The 2023 edition had a note stating that the Table 220.42(A) unit loads already included the 125% continuous-load multiplier. The 2026 edition deleted that note without changing the values, and 120.5(E) states that load calculations do not apply the 125% factor. The 125% factor appears when sizing conductors and OCPDs for continuous loads (215.2, 215.3, 230.42). Read each exam question carefully for whether it asks for the calculated load or the minimum conductor ampacity .

Receptacles and outlets (120.14)

Load Value

General receptacle outlet (120.14(I)) 180 VA for each single or multiple receptacle on one yoke; a single piece of equipment with four or more receptacles counts at least 90 VA per receptacle

Multioutlet assembly (120.14(H)) 180 VA per 5 ft , or 180 VA per 1 ft where appliances are likely to be used at the same time

  • Banks and offices (120.14(K)) The larger of the 180 VA per outlet load after demand factors or 1 VA/ft²
  • Sign outlet (120.14(F)) At least 1,200 VA for each required sign or outline lighting outlet
  • Show windows (120.14(G), 120.43(A)) 200 VA per linear foot , measured horizontally along the base
  • Track lighting (120.43(B)) 150 VA per 2 ft of track, unless otherwise limited
  • Other outlets Nameplate rating of the equipment, or 180 VA for other outlets

Section 600.5(A) requires at least one sign outlet at each entrance to each tenant space of commercial buildings accessible to pedestrians, supplied by a branch circuit rated at least 20 A that supplies no other load.

Receptacle demand (Table 120.44)

Receptacle loads calculated at not more than 180 VA per outlet may be reduced:

  • Portion of receptacle load Demand factor
  • First 10 kVA or less 100%
  • Remainder over 10 kVA 50%
  • Converting to amperes
  • Single-phase 120/240 V: I = VA ÷ 240 I = \text{VA} \div 240 I = VA ÷ 240

Three-phase: I = VA ÷ ( E × 1.732 ) I = \text{VA} \div (E \times 1.732) I = VA ÷ ( E × 1.732 ) , such as VA ÷ 360.3 \text{VA} \div 360.3 VA ÷ 360.3 at 208 V or VA ÷ 831.4 \text{VA} \div 831.4 VA ÷ 831.4 at 480 V

Worked example: retail store

A 20,000 ft² retail store has 100 general-purpose receptacles, 60 linear feet of show window, and one sign outlet, supplied at 208Y/120 V, three-phase.

  • Line Calculation VA
  • General lighting 20,000 × 1.9 20{,}000 \times 1.9 20 , 000 × 1.9 38,000
  • Show windows 60 × 200 60 \times 200 60 × 200 12,000
  • Sign outlet minimum 1,200

Receptacles 100 × 180 = 18,000 100 \times 180 = 18{,}000 100 × 180 = 18 , 000 ; 10,000 + 8000 × 0.50 10{,}000 + 8000 \times 0.50 10 , 000 + 8000 × 0.50 14,000

Total 65,200

Feeder current: 65,200 ÷ ( 208 × 1.732 ) = 65,200 ÷ 360.3 = 181 65{,}200 \div (208 \times 1.732) = 65{,}200 \div 360.3 = 181 65 , 200 ÷ ( 208 × 1.732 ) = 65 , 200 ÷ 360.3 = 181 A. Conductor and OCPD sizing then apply 215.2 and 215.3 (or 230.42 for a service) to the continuous loads, together with any HVAC, motor, and equipment loads that a full calculation would add.

Worked example: office receptacles

A 15,000 ft² office has 60 general-purpose receptacles.

Calculated: 60 × 180 = 10,800 60 \times 180 = 10{,}800 60 × 180 = 10 , 800 VA; with Table 120.44: 10,000 + 800 × 0.5 = 10,400 10{,}000 + 800 \times 0.5 = 10{,}400 10 , 000 + 800 × 0.5 = 10 , 400 VA.

Minimum: 15,000 × 1 = 15,000 15{,}000 \times 1 = 15{,}000 15 , 000 × 1 = 15 , 000 VA.

Use the larger value: 15,000 VA .