Study guide
10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
Key Takeaways Explain This Topic AI
Standard locknuts or bushings may not be the only means of bonding service raceways and enclosures; use threaded connections, threadless fittings made up tight, or listed bonding locknuts, bushings, or jumpers (250.92(B)).
For circuits over 250 V to ground, such as 277 V circuits, metal raceway continuity at concentric or eccentric knockouts must be ensured by the service-type bonding methods or a listed bonding fitting (250.97).
A load-side equipment bonding jumper is sized from Table 250.122 using the largest OCPD of the circuits in the raceway, and one installed outside a raceway may not exceed 6 ft and must be routed with the raceway (250.102(D) and (E)).
A metal box needs a bonding jumper to the receptacle grounding terminal unless the box is surface mounted with direct metal-to-metal contact, the receptacle has a listed self-grounding yoke, or it is a listed floor box device (250.146).
Sheet-metal screws may not be used to connect equipment grounding conductors or bonding jumpers to enclosures (250.8).
Last updated: October 2026
Why bonding methods matter
Every metal raceway, box, fitting, and enclosure in the ground-fault return path must stay electrically continuous for the life of the installation. DLI's knowledge areas include bonding , equipment grounding , and grounding of receptacles and equipment . Exam questions often describe a fitting or knockout and ask whether the bonding is adequate.
Bonding service equipment (250.92)
Parts that must be bonded: all raceways, cable trays, cablebus framework, auxiliary gutters, and cable armor or sheaths that enclose service conductors, and all enclosures containing service conductors, including meter fittings and boxes.
Methods (250.92(B)): bonding must be done by one or more of these:
- bonding equipment to the grounded service conductor ;
- threaded couplings or threaded hubs on enclosures, made up wrenchtight ;
- threadless couplings and connectors made up tight for metal raceways and metal-clad cables; or
other listed devices, such as bonding-type locknuts, bonding bushings, or wedges, or bushings with bonding jumpers.
Bonding jumpers must be used around impaired connections such as reducing washers or oversized, concentric, or eccentric knockouts . Standard locknuts or bushings may not be the only means of bonding; they may provide the mechanical connection only.
Bonding other enclosures (250.96 to 250.98)
250.96(A): metal raceways, cable trays, cable armor, enclosures, frames, fittings, and other metal non-current-carrying parts that serve as EGCs must be bonded where necessary to ensure continuity and the capacity to carry any fault current. Nonconductive coatings such as paint must be removed at threads and contact surfaces, or fittings must be designed to make removal unnecessary (250.12).
250.96(B) Isolated grounding circuits: to reduce electromagnetic noise, an equipment enclosure supplied by a branch circuit may be isolated from the metal raceway by a listed nonmetallic raceway fitting at the point of attachment, if the enclosure is grounded by an internal insulated equipment grounding conductor .
250.97 Over 250 V: for circuits over 250 V to ground (such as 277 V lighting and 480Y/277 V motor circuits), raceway and cable continuity must be ensured by the 250.92(B) methods. Where oversized, concentric, or eccentric knockouts are not encountered, or the box is listed to provide reliable bonding through such knockouts, these are also permitted: threadless couplings and connectors for metal-sheathed cables; two locknuts , one inside and one outside, on RMC or IMC; fittings with shoulders that seat firmly against the box (such as EMT connectors) with one locknut inside; and listed fittings.
250.98 Loosely jointed raceways: expansion fittings and telescoping sections of metal raceways must be made electrically continuous with equipment bonding jumpers or other means.
250.106 Lightning protection: where a lightning protection system is installed, its grounding electrodes must be bonded to the building grounding electrode system.
Bonding conductors and jumpers (250.102)
Rule Requirement
Material (A) Copper, aluminum, copper-clad aluminum, or other corrosion-resistant material; the 2026 NEC lists wire, bus, screw, nonflexible metal raceway and fittings , or similar suitable conductor
Supply side (C) Sized from Table 250.102(C)(1) based on the largest ungrounded supply conductor (12.5% rule above 1100 kcmil copper)
Load side (D) Sized from Table 250.122 based on the rating of the OCPD; one common jumper for several circuits is sized for the largest OCPD supplying circuits in it
Installation (E) Inside or outside a raceway or enclosure; outside , the jumper may not exceed 6 ft and must be routed with the raceway or enclosure
- Equipment that must be grounded
- Fastened in place or permanently wired (250.110)
Exposed, normally non-current-carrying metal parts of fixed equipment likely to become energized must be connected to an EGC where any of these apply:
within 8 ft vertically or 5 ft horizontally of ground or grounded metal objects and subject to contact by persons;
- located in a wet or damp location and not isolated;
- in electrical contact with metal;
- in a hazardous (classified) location;
supplied by a wiring method that provides an EGC (metal-clad, metal-sheathed, metal raceway, or a wiring method with an EGC); or
operating with any terminal at over 150 V to ground , with limited exceptions.
Section 250.112 also lists equipment that must always be grounded, such as switchboard frames, motor frames, motor controller enclosures, elevator and crane equipment, and signs.
Cord-and-plug-connected equipment (250.114)
In residential occupancies, these must have an EGC: refrigerators, freezers, and air conditioners; clothes washers and dryers, dishwashers, ranges, and kitchen waste disposers; information technology equipment; sump pumps and electrical aquarium equipment; hand-held, stationary, and light industrial motor-operated tools; and motor-operated appliances such as hedge clippers, lawn mowers, snow blowers, and wet scrubbers. Listed tools and appliances protected by a system of double insulation are exempt where marked.
How fixed equipment is connected (250.134 and 250.136)
Equipment fastened in place or connected by a permanent wiring method is connected to an EGC of one of the 250.118 types , such as a qualifying metal raceway, qualifying cable armor, or a wire EGC. A wire-type EGC must be contained within the same raceway or cable, or otherwise run with the circuit conductors , which keeps the impedance of the fault path low. Equipment secured to and in electrical contact with a metal rack or structure that is provided for its support and connected to an EGC is considered connected to an EGC (250.136). The structural metal frame of a building may not be used as the required EGC for ac equipment.
Connection methods (250.8)
EGCs and bonding jumpers must be connected by listed pressure connectors, terminal bars, pressure connectors listed as grounding and bonding equipment, exothermic welding, machine screws that engage at least two threads or are secured with a nut, thread-forming machine screws that engage at least two threads in the enclosure, connections that are part of a listed assembly, or other listed means. Sheet-metal screws may not be used, and connections may not depend solely on solder .
- Boxes and receptacles
- EGCs in boxes (250.148)
Where circuit conductors are spliced or terminated in a box, all EGCs associated with those circuits must be connected within the box or to the box with devices suitable for the use. In a metal box, the connection is made with a grounding screw used for no other purpose , equipment listed for grounding, or a listed grounding device. The arrangement must be such that removing a receptacle or luminaire does not interrupt EGC continuity to other outlets.
Bonding the receptacle to the box (250.146)
An equipment bonding jumper must connect the receptacle grounding terminal to a grounded metal box, unless one of these applies:
Exception Condition
(A) Surface-mounted box Direct metal-to-metal contact between the device yoke and the box, with at least one insulating washer removed; a receptacle on a cover qualifies only if the cover and receptacle are listed for the purpose
(B) Self-grounding device Contact devices or yokes designed and listed to establish continuity with the box when the mounting screws are tightened
(C) Floor boxes Floor boxes designed and listed to provide satisfactory continuity
(D) Isolated ground receptacles The grounding terminal is intentionally isolated and connected to an insulated EGC run with the circuit conductors; that EGC may pass through panelboards without connecting to their grounding terminals, ending at the applicable derived system or service in the same building. Isolated ground receptacles are identified by an orange triangle
Replacing a nongrounding receptacle (250.130(C))
When a grounding-type receptacle replaces an old two-wire receptacle, or a branch circuit is extended, the new EGC may be connected to any accessible point on the grounding electrode system or grounding electrode conductor, the equipment grounding terminal bar in the enclosure where the branch circuit originates, an EGC of another branch circuit that originates from that same enclosure, or, for grounded systems, the grounded service conductor within the service equipment enclosure.
Worked example: a 277 V lighting circuit
A 277 V lighting circuit in EMT enters a junction box through an existing concentric knockout with some rings removed.
The circuit is over 250 V to ground , so 250.97 applies.
A concentric knockout is an impaired connection, and the box is not listed for bonding through it.
A standard EMT connector with one locknut is not enough. Bridge the knockout with a bonding bushing and bonding jumper , or install a wire-type EGC sized from Table 250.122 in the raceway and bond the box to it.