Study guide

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122)

Key Takeaways Explain This Topic AI

Under NEC 250.118, equipment grounding conductors (EGCs) are permitted to be either wire-type conductors (copper, aluminum, copper-clad aluminum) or listed metal raceways and cable armors such as RMC, IMC, EMT, and qualifying Type AC and Type MC cables.

Wire-type EGCs are sized strictly in accordance with NEC Table 250.122 based on the rating or setting of the overcurrent protective device (fuse or circuit breaker) protecting the circuit, but are never required to be larger than the circuit phase conductors.

Under NEC 250.119, insulated EGCs sized 6 AWG and smaller must have a continuous outer green finish (or green with yellow stripes) and cannot be permanently re-identified with tape in the field, whereas conductors 4 AWG and larger may be re-identified with green tape or paint at all accessible terminations.

Where multiple circuits share a common raceway, cable, or cable tray, NEC 250.122(C) permits a single common EGC sized according to the largest overcurrent device protecting any circuit contained within that raceway.

For parallel conductor runs installed in multiple raceways or cables, NEC 250.122(F)(1) requires a full-sized EGC sized per Table 250.122 to be routed in every parallel raceway; the required circular mil area cannot be divided or split among the raceways.

Last updated: October 2026

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122)

Quick Answer: An Equipment Grounding Conductor (EGC) is the low-impedance electrical path that connects normally non-current-carrying metal enclosures, raceways, and equipment frames back to the electrical source (system grounded conductor or grounding electrode conductor) per NEC Article 100 and 250.4(A)(3) . Wire-type EGCs are sized according to NEC Table 250.122 based on the rating of the overcurrent protective device (OCPD) protecting the circuit. EGCs sized 6 AWG and smaller must be manufactured with green insulation, green with yellow stripes, or bare (field tape re-identification is prohibited per NEC 250.119 ). For parallel runs in separate conduits, a full-sized EGC must be pulled in each raceway per NEC 250.122(F)(1) .

While grounding electrode conductors (GECs) connect an electrical system to the earth for voltage stabilization and lightning dissipation, the equipment grounding conductor (EGC) performs the everyday life-safety work of clearing electrical short circuits. If an ungrounded phase conductor frays and contacts a metallic junction box, motor frame, or appliance chassis, the EGC provides the mandatory, low-impedance return circuit that carries tens or hundreds of amperes of fault current back to the panelboard, instantaneously tripping the circuit breaker or blowing the fuse.

Permitted Types of Equipment Grounding Conductors: NEC 250.118

Electricians frequently assume an equipment grounding conductor must always be a separate green copper wire. In commercial and industrial construction, however, the National Electrical Code recognizes 14 distinct metallic wiring methods as qualifying equipment grounding conductors under NEC Section 250.118 .

Detailed Analysis of Permitted Types

Wire-Type Conductors (NEC 250.118): Copper, aluminum, or copper-clad aluminum conductors. They may be bare, covered, or insulated. When installed in nonmetallic raceways (such as Schedule 40/80 PVC or RTRC), a wire-type EGC is mandatory.

Rigid Metal Conduit (RMC) & Intermediate Metal Conduit (IMC) (NEC 250.118): Heavy-wall steel or aluminum threaded conduits provide an exceptional, low-resistance metallic fault path that easily satisfies all EGC requirements without pulling a supplemental wire.

Electrical Metallic Tubing (EMT) (NEC 250.118): Thin-wall steel EMT is one of the most widely used raceways in commercial facilities. When assembled with listed steel or die-cast compression or set-screw fittings wrench-tightened to manufacturer torque, EMT is recognized as a complete standalone EGC.

Flexible Metal Conduit (FMC) (NEC 250.118): Standard "Greenfield" flexible conduit is permitted to serve as the sole EGC only when all of the following conditions are met:

The conduit is terminated in fittings listed for grounding.

The conduit is not larger than trade size 1¼ .

The circuit conductors contained in the conduit are protected by an overcurrent device rated at 20 amperes or less .

The combined length of flexible metal conduit, flexible metallic tubing, and liquidtight flexible metal conduit in the same ground return path does not exceed 6 feet (1.8 m) .

The conduit is not installed to minimize vibration or to allow movement after installation; where flexibility is needed (for example, a vibrating motor hookup), a separate wire-type EGC is required.

Liquidtight Flexible Metal Conduit (LFMC) (NEC 250.118): Listed LFMC is permitted as the sole EGC only where the total length in the ground return path does not exceed 6 feet , listed fittings are used, and:

For 3/8-inch through 1/2-inch trade size, the circuit is protected at 20 amperes or less .

For 3/4-inch through 1-1/4-inch trade size, the circuit is protected at 60 amperes or less .

LFMC larger than trade size 1¼, or installed where flexibility is needed after installation, requires a separate wire-type EGC.

Type AC Armored Cable (NEC 250.118 & 320.108): Traditional Type AC (BX) cable has an interlocked metal armor with an internal aluminum bonding strip in intimate contact with the armor for its entire length (320.100). The armor and bonding strip together form the EGC path. At terminations, the bonding strip is typically folded back over the armor under the fitting, following the manufacturer's instructions.

Type MC Metal-Clad Cable (NEC 250.118): Standard interlocked metal-clad cable (MC) armor is not an approved EGC because the spiraled convolutions introduce high electrical resistance under fault surges. Standard MC cable relies on an internal green insulated copper conductor. However, interlocked MC cable whose combined armor and uninsulated grounding/bonding conductor is listed and identified as an EGC (often sold as MCAP or similar) qualifies under 250.118, as does smooth or corrugated tube-type MC whose sheath is listed and identified as an EGC.

Conductor Identification Rules: NEC 250.119

The National Electrical Code enforces strict conductor color-coding to prevent installers from accidentally energizing equipment grounding conductors or mistaking an ungrounded phase for a safety ground.

Conductor Size Permitted Factory Color Permitted Field Re-Identification Methods Code Section

6 AWG and Smaller Continuous green outer finish, green with one or more yellow stripes, or bare Strictly Prohibited (Must be manufactured green, green/yellow, or bare) NEC 250.119

4 AWG and Larger Continuous green, green with yellow stripes, or bare Permitted at terminations and accessible points via: 1) Stripping insulation, 2) Green tape, 3) Green paint/spray NEC 250.119(A)

The 6 AWG Cutoff Rule

A critical rule tested on state examinations is the cutoff between small and large conductors:

An electrician cannot take a black, white, or red 12 AWG or 10 AWG conductor and wrap green phase tape around the ends to make it an equipment grounding conductor. It is an immediate violation of NEC 250.119 . In conduit wiring 6 AWG and smaller, the wire insulation must be manufactured green or bare.

Narrow Exception (NEC 250.119(B)): In multiconductor cable assemblies (such as 12/2 or 10/3 NM or MC cable), an insulated conductor with a continuous green finish is strictly reserved for EGC use, but where qualified service personnel maintain an industrial installation, conductors in cables can be permanently marked with green tape.

For conductors 4 AWG and larger , field re-identification is fully permitted at the time of installation at every termination and point of access (junction boxes, pull boxes, disconnects) by applying green tape encircling the conductor, painting the exposed insulation green, or completely stripping the insulation from the entire exposed length.

Sizing Equipment Grounding Conductors: NEC Table 250.122

Wire-type equipment grounding conductors are sized based exclusively on the rating or setting of the overcurrent protective device (fuse or circuit breaker) protecting the circuit conductors, as codified in NEC Table 250.122 .

Rating or setting of OCPD ahead of the equipment, conduit, etc. (not exceeding) Copper Aluminum or copper-clad aluminum

  • 15 A 14 AWG 12 AWG
  • 20 A 12 AWG 10 AWG
  • 60 A 10 AWG 8 AWG
  • 100 A 8 AWG 6 AWG
  • 200 A 6 AWG 4 AWG
  • 300 A 4 AWG 2 AWG
  • 400 A 3 AWG 1 AWG
  • 500 A 2 AWG 1/0 AWG
  • 600 A 1 AWG 2/0 AWG
  • 800 A 1/0 AWG 3/0 AWG
  • 1000 A 2/0 AWG 4/0 AWG
  • 1200 A 3/0 AWG 250 kcmil
  • 1600 A 4/0 AWG 350 kcmil
  • 2000 A 250 kcmil 400 kcmil
  • 2500 A 350 kcmil 600 kcmil
  • 3000 A 400 kcmil 600 kcmil
  • 4000 A 500 kcmil 750 kcmil
  • 5000 A 700 kcmil 1200 kcmil
  • 6000 A 800 kcmil 1200 kcmil

Table 250.122 has no separate 30 A or 40 A rows; read the "not exceeding" column, so a 30 A or 40 A OCPD uses the 60 A row (10 AWG copper). The EGC also never has to be larger than the circuit conductors supplying the equipment.

Key Patterns in Table 250.122

Candidates must commit these foundational breakpoints to memory:

  • 15A: 14 AWG Cu
  • 20A: 12 AWG Cu

30A, 40A, and 60A: All three ratings use 10 AWG copper (or 8 AWG aluminum).

  • 100A: 8 AWG Cu
  • 200A: 6 AWG Cu
  • 400A: 3 AWG Cu
  • 800A: 1/0 AWG Cu
  • 1200A: 3/0 AWG Cu
  • Conductor Size Restriction: NEC 250.122(A)

Under NEC 250.122(A) , an equipment grounding conductor is never required to be larger than the circuit ungrounded conductors supplying the equipment. For example, if a 40-ampere overcurrent device supplies a circuit wired with 10 AWG copper conductors (permitted under specific motor or welder provisions), the EGC is not required to be larger than 10 AWG copper.

Multiple Circuits in the Same Raceway: NEC 250.122(C)

In commercial wiring, branch circuits are frequently bundled into a single home-run conduit back to the panelboard. For example, a 1-inch EMT run might contain four 20-ampere lighting circuits and one 50-ampere commercial appliance feeder.

Under NEC Section 250.122(C) :

Where a single equipment grounding conductor is run in a raceway, cable, or cable tray containing multiple circuits, it shall be sized for the largest overcurrent device protecting conductors in the raceway, cable, or cable tray.

The installer is not required to pull five separate green wires through the raceway.

A single common equipment grounding conductor satisfies the safety requirement.

In the example above, the largest overcurrent device is 50 amperes. Referring to Table 250.122, a 50-ampere overcurrent device requires a 10 AWG copper EGC. Therefore, a single 10 AWG copper wire protects all five circuits.

Parallel Feeders in Separate Raceways: NEC 250.122(F)

One of the most heavily tested and widely misunderstood sections of Article 250 is the sizing of equipment grounding conductors in parallel conductor installations.

The Mandatory Full-Size Rule (NEC 250.122(F)(1))

Where conductors are installed in parallel in multiple raceways or cables as permitted by 310.10(G) (2023 numbering):

An equipment grounding conductor, where installed, shall be installed in each raceway or cable .

Each equipment grounding conductor must be sized based on the full rating of the overcurrent protective device protecting the conductors in the raceway or cable, in accordance with Table 250.122.

Why Can't the EGC Be Split Proportionally?

Apprentices often calculate the total required EGC circular mils and divide by the number of parallel conduits. For a 1,200A breaker, Table 250.122 requires 3/0 AWG copper (167,800 cmil). Dividing 167,800 cmil by 3 gives 55,933 cmil (approx. 2 AWG).

The Catastrophic Physics: If a ground fault occurs inside Conduit 1, fault current will flow down the phase conductor in Conduit 1 directly into the faulted enclosure. Fault current does not divide equally across all three conduits; the vast majority of current seeks the immediate return path inside Conduit 1 due to mutual inductive coupling.

If Conduit 1 contains an undersized 2 AWG copper wire, the extreme ground-fault current (thousands of amperes) will melt and vaporize the 2 AWG wire before the 1,200-ampere breaker can magnetically trip, causing an catastrophic arc-blast fire.

Therefore, NEC 250.122(F)(1) mandates a complete, full-sized 3/0 AWG copper EGC inside EACH of the three parallel raceways .

Motor Branch Circuits & Table 250.122

Motor branch circuits present a unique sizing scenario because NEC Article 430 Part IV permits motor branch-circuit short-circuit and ground-fault protective devices (inverse-time circuit breakers) to be sized at up to 250% of motor full-load current (NEC Table 430.52).

Sizing Rule: The equipment grounding conductor must be sized per Table 250.122 based on the rating of that oversized branch-circuit breaker or fuse.

Example: A 15-horsepower, 208-volt, 3-phase motor has a full-load current of 46.2 amperes (Table 430.250). The branch circuit conductors are sized at 125% ( 46.2 A × 1.25 = 57.75 A 46.2\text{ A} \times 1.25 = 57.75\text{ A} 46.2 A × 1.25 = 57.75 A ), requiring 6 AWG THHN copper conductors. An inverse-time circuit breaker is sized at 250% ( 46.2 A × 2.50 = 115.5 A 46.2\text{ A} \times 2.50 = 115.5\text{ A} 46.2 A × 2.50 = 115.5 A ), leading to a standard 125-ampere circuit breaker per 240.6(A).

Sizing the EGC for the 125A breaker from Table 250.122 requires a 6 AWG copper EGC.

Under 250.122(A), if a calculation ever called for an EGC larger than the 6 AWG branch-circuit conductors, the EGC would not be required to exceed 6 AWG.