11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
Key Takeaways Explain This Topic AI
Under the 2026 NEC 300.13, ceiling grid support wires may not be the only support for wiring above a suspended ceiling unless they are independent support wires installed in addition to the grid wires and distinguishable from them.
Cable ties used to secure and support cables or flexible raceways must be listed and identified for securement and support (2026 NEC 300.13(E)).
No wiring of any type may be installed in ducts used to transport dust, loose stock, or flammable vapors (300.25(A) in the 2026 NEC).
Openings around electrical penetrations through fire-resistance-rated walls, floors, or ceilings must be firestopped by approved methods that maintain the fire resistance rating.
Copper conductors 6 AWG through 1/0 AWG in a vertical raceway need a support at least every 100 ft, and aluminum every 200 ft.
Last updated: October 2026
Securing and supporting (300.13, formerly 300.11)
Rule Requirement
(A) Secured in place Raceways, cable assemblies, boxes, cabinets, and fittings must be securely fastened in place
(B) Above suspended ceilings Ceiling-support wires that are part of the ceiling grid may not be the only support. Independent support wires added for the electrical work may serve as the sole support if secured at both ends. In fire-rated ceilings they must be distinguishable from the fire-rated design's wires by color, tagging, or other effective means
(C) Raceways as support A raceway may not support other raceways, cables, or nonelectrical equipment, unless it is identified as a means of support, or it supports Class 2 cables that control the equipment the raceway supplies, or boxes as permitted in Article 314
(D) Cables as support Cables may not be used to support other cables, raceways, or nonelectrical equipment
(E) Cable ties (2026) Cable ties used to secure and support cables, flexible conduit, and flexible tubing must be listed and identified for securement and support; any cable tie fixing device must also be listed. An Informational Note identifies Type 2S and 21S cable ties as evaluated for this use
Each wiring method article also sets its own support distances, such as within 3 ft of each box and every 10 ft for EMT, or within 12 in. of each box and every 4½ ft for NM cable.
Other Article 300 installation rules
Damaged wiring (300.4(C), new in 2026): conductors and wiring methods no longer suitable for use because of overheating, fire, corrosion, or water damage must be replaced . Informational Notes point to NEMA GD 1 (water-damaged equipment) and NEMA GD 2 (fire- and heat-damaged equipment).
Corrosion protection (300.6, 2023 numbering): ferrous raceways, boxes, and fittings must be protected against corrosion by an approved coating. In laundries, canneries, dairy processing, and other indoor wet locations , and where walls are frequently washed, the wiring system must be mounted with at least ¼ in. of airspace from the wall.
Wet locations above grade (300.11 in the 2026 NEC): the interior of these raceways is a wet location, so conductors must be listed for wet locations. The 2026 NEC adds a requirement for drainage in raceways installed in indoor wet locations.
Complete raceway systems (300.18, 2023 numbering): raceways must be installed complete between outlet, junction, or splicing points before conductors are installed. Welding to a raceway is not permitted unless it is designed for that use.
Bends (300.24, new in 2026): the limit of 360 degrees of bends between pull points applies to the whole run, even where it changes from one raceway type to another.
Induced currents (300.20, 2023 numbering): all conductors of a circuit, including the neutral and EGCs, must be grouped in the same ferrous raceway or enclosure. Where single conductors must pass through ferrous metal separately, slots cut between the holes reduce inductive heating.
Supporting conductors in vertical raceways (300.19, 2023 numbering)
Long vertical runs, such as risers in high-rise buildings, need intermediate support so the weight of the conductors does not pull them from their terminations:
- Conductor size Aluminum or copper-clad aluminum Copper
- 18 AWG through 8 AWG 100 ft 100 ft
- 6 AWG through 1/0 AWG 200 ft 100 ft
- 2/0 AWG through 4/0 AWG 180 ft 80 ft
- Over 4/0 AWG through 350 kcmil 135 ft 60 ft
- Over 350 kcmil through 500 kcmil 120 ft 50 ft
- Over 500 kcmil through 750 kcmil 95 ft 40 ft
- Over 750 kcmil 85 ft 35 ft
A support is required at the top of the vertical raceway or as close to the top as practical, plus intermediate supports at these intervals. Approved methods include clamping devices in insulating wedges and junction boxes with insulating supports.
Spread of fire (300.21, 2023 numbering)
Electrical installations in hollow spaces, vertical shafts, and ventilation or air-handling ducts must be made so the possible spread of fire or products of combustion is not substantially increased . Openings around penetrations into or through fire-resistance-rated walls, partitions, floors, or ceilings must be firestopped using approved methods to maintain the fire resistance rating. In practice, use a listed firestop system whose tested design matches the assembly, the penetrating item, and the annular space, and install it exactly per the system listing.
Ducts, plenums, and other air-handling spaces (300.25 in the 2026 NEC, formerly 300.22)
- Space What is permitted
- (A) Ducts for dust, loose stock, or vapor removal No wiring systems of any type
(B) Ducts specifically fabricated for environmental air Type MI cable without an overall nonmetallic covering; Type MC cable with a smooth or corrugated impervious metal sheath without a nonmetallic covering; or EMT, flexible metallic tubing, IMC, or RMC without a nonmetallic covering. Equipment is permitted only if necessary for direct action on, or sensing of, the contained air
(C) Other spaces used for environmental air (plenums), such as the space above a suspended ceiling used for return air Type MI, Type MC, and Type AC cable without nonmetallic coverings; other factory-assembled multiconductor cables listed for use in air-handling spaces ; and other cables and conductors installed in EMT, FMT, IMC, RMC, flexible metal conduit , or, where accessible, surface metal raceway or metal wireway with metal covers
(D) Information technology rooms Article 645 governs
Nonmetallic cable ties and other nonmetallic accessories used in plenum spaces must be listed as having low smoke and heat release properties . Limited-energy and communications cables in plenums must be plenum rated (for example, CL2P or CMP) under the Chapter 7 cable rules.
Worked example: an office ceiling
A contractor runs MC cable and EMT above a lay-in ceiling used as a return-air plenum in a fire-rated floor-ceiling assembly.
Support: fasten the EMT and MC cable to the structure, or to independent support wires secured at both ends and tagged or colored to distinguish them from the fire-rated ceiling wires. Do not hang them from the grid wires.
Plenum wiring: MC cable without a nonmetallic jacket and EMT are both permitted in the plenum. Any PVC-jacketed MC is not.
Cable ties: if ties secure the MC cable, they must be listed and identified for securement and support, and nonmetallic ties must also be listed for low smoke and heat release.
Penetrations: where the EMT passes through the rated floor above, seal the opening with a listed firestop system.