Study guide
12.3 Busways & Cable Tray Systems (Articles 368 & 392)
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
12.3 Busways & Cable Tray Systems (Articles 368 & 392)
Key Takeaways Explain This Topic AI
Busways must be supported at intervals not exceeding 5 ft unless otherwise designed and marked (368.30).
Overcurrent protection is required where a busway is reduced in ampacity, except in industrial establishments where the smaller busway is not over 50 ft long and has an ampacity of at least one-third of the upstream OCPD rating (368.17(B)).
A vertical busway passing through a dry floor must be totally enclosed (unventilated) where it passes through and for at least 6 ft above the floor, and ventilated risers need a curb around the floor opening to keep liquids out (368.10).
Cable trays may not be installed in hoistways or where subject to severe physical damage (392.12).
The 2026 NEC 392.18(F) requires at least 12 in. of access space above a cable tray, with four exceptions.
Last updated: October 2026
Busways (Article 368)
A busway is a factory-assembled raceway containing busbars, used as a feeder or to distribute power through plug-in units to machines in industrial plants.
Uses and installation
Rule Requirement
Uses permitted (368.10) Located in the open and visible; behind access panels if the busway is totally enclosed and nonventilated with accessible joints, and either the space is not used for air handling or, if it is, the busway has no plug-in provisions and its conductors are insulated
Uses not permitted (368.12) Where subject to severe physical damage or corrosive vapors; in hoistways; in hazardous locations unless specifically approved; outdoors or in wet or damp locations unless identified for the use
Through walls Permitted through dry walls in unbroken lengths
Through floors Through dry floors and platforms only if totally enclosed (unventilated) where it passes through and for at least 6 ft above the floor; riser busways with ventilating openings need a curb around the floor opening, within 12 in. of it, to keep liquids out
- Support (368.30) At intervals not exceeding 5 ft , unless otherwise designed and marked
- Dead ends (368.58) Closed
- Grounding (368.60) Busway enclosures are connected to an EGC as required by Article 250
- Overcurrent protection (368.17)
Rating: the OCPD protecting a busway is selected using the busway ampacity, under 240.4.
Reduction in size (368.17(B)): overcurrent protection is required where a busway is reduced in ampacity. The exception applies only in industrial establishments : a smaller busway may continue without additional protection if it is not over 50 ft long and its ampacity is at least one-third of the rating or setting of the OCPD next back on the line, and it is free from contact with combustible material.
Branches (368.17(C) and 368.56): where a busway is used as a feeder, plug-in devices or connections that tap off feeders or branch circuits must contain the required OCPD for those circuits, with limited exceptions such as cord-and-plug drops and fixed or semifixed luminaires within specific limits.
Busway feeders and plug-in devices must have interrupting ratings and short-circuit current ratings at least equal to the available fault current, which can be high near large transformers (110.9 and 110.10).
Cable trays (Article 392)
A cable tray system is a unit or assembly of units forming a rigid structural system used to securely fasten or support cables and raceways. It is not a raceway.
What may be installed (392.10)
Table 392.10(A) lists the wiring methods permitted in trays, including Types AC, MC, MI, MV, TC, ITC, PLTC, UF, USE, SE, NM (where permitted), power-limited and fire alarm cables, optical fiber cables, and raceways. In industrial establishments where conditions of maintenance and supervision ensure only qualified persons service the system, single-conductor cables 1/0 AWG and larger may be installed in ladder or ventilated trough trays, with smaller single conductors permitted in specific cases. Cable trays are also permitted in hazardous locations with the wiring methods allowed there, and nonmetallic trays in corrosive areas.
Not permitted (392.12): in hoistways or where subject to severe physical damage .
Installation
Rule Requirement
Complete system (392.18(A)) Installed as a complete system; field bends or modifications must keep electrical continuity and support
- Covers Permitted where protection is needed; solid unventilated covers affect ampacity
- Access (392.18(F), new in 2026) At least 12 in. of access space above the tray, with four exceptions
- Through partitions and walls Permitted, with penetrations firestopped as required for fire-rated assemblies
- Securing cables (392.30) Cables in other than horizontal runs must be securely fastened to transverse members
Over 1000 V Cables rated over 1000 V and those rated 1000 V or less may not share a tray unless separated by a solid fixed barrier or the higher-voltage cables are Type MC
Cable fill and ampacity (392.22 and 392.80)
Multiconductor cables 4/0 AWG and larger in ladder or ventilated trough trays: the sum of the cable diameters may not exceed the tray's inside width, and the cables are installed in a single layer .
Multiconductor cables smaller than 4/0 AWG: the total cross-sectional area may not exceed the allowable fill area in Table 392.22(A) for the tray width.
Ampacity of multiconductor cables: the Table 310.15(C)(1) adjustment factors apply only to the number of current-carrying conductors within each cable , not to the total number of conductors in the tray. Where a tray is covered for more than 6 ft with solid unventilated covers, ampacity is reduced to 95% .
Single-conductor cables have their own ampacity rules in 392.80(A)(2), based on free-air ampacities with reduction factors for uncovered and covered trays.
Cable tray as an equipment grounding conductor (392.60)
Metal cable trays may serve as EGCs where continuous maintenance and supervision ensure qualified persons service the system, the tray sections and fittings are identified for grounding, the tray has the cross-sectional area required by Table 392.60(A) for the largest OCPD of the circuits in the tray, and all sections are bonded with listed connectors or bonding jumpers. Otherwise, a separate EGC is run in or with the tray.
Worked example: a busway tap
An industrial plant has a 1600 A busway protected by a 1600 A breaker. A 600 A busway section continues 40 ft without its own OCPD.
Is it industrial? Yes.
Is the smaller busway 50 ft or less ? Yes, 40 ft.
Is its ampacity at least one-third of the upstream OCPD? 1600 ÷ 3 = 533 1600 \div 3 = 533 1600 ÷ 3 = 533 A, and 600 A is larger, so yes .
The reduced busway may continue without additional overcurrent protection. In a commercial office building, the exception would not apply, and an OCPD would be required at the size reduction.