14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

Key Takeaways Explain This Topic AI

A fixed storage-type water heater with a capacity of 120 gallons or less is a continuous load, so its branch-circuit rating must be at least 125% of the nameplate rating (422.13).

Appliances with resistance heating elements rated more than 48 A must have the elements subdivided, with each subdivided load not over 48 A and protected at not more than 60 A (422.11(F)).

Central heating equipment other than fixed electric space heating must be on an individual branch circuit; the 2026 NEC allows that circuit to also supply the required service receptacle and equipment lighting outlet (422.12).

A cord-and-plug connected waste disposer needs a cord 18 in. to 36 in. long, a built-in dishwasher 3 ft to 6.5 ft, a trash compactor 3 ft to 4 ft, and a range hood 18 in. to 4 ft (422.16(B)).

Fixed outdoor electric deicing and snow-melting equipment requires ground-fault protection of equipment, except mineral-insulated cable embedded in a noncombustible medium (426.28).

Last updated: October 2026

  • Appliances (Article 422)
  • Branch circuits and overcurrent protection

Rule Requirement

Branch-circuit rating (422.10) Not less than the appliance's marked rating; motor-operated appliances follow Article 430

Storage water heaters (422.13) Fixed storage-type water heaters of 120 gallons or less are continuous loads : branch-circuit rating at least 125% of the nameplate

Single nonmotor appliance (422.11(E)) OCPD not to exceed the rating marked on the appliance; if not marked, not over 20 A for an appliance rated 13.3 A or less, or not over 150% of its rated current for an appliance rated over 13.3 A , using the next higher standard size where needed

Resistance heating elements (422.11(F)) Elements rated more than 48 A must be subdivided; each subdivided load may not exceed 48 A and must be protected at not more than 60 A

Water heater controls (422.47) Each storage or instantaneous water heater needs a temperature-limiting means in addition to its control thermostat

Example: a 4,500 W, 240 V storage water heater draws 4500 ÷ 240 = 18.75 4500 \div 240 = 18.75 4500 ÷ 240 = 18.75 A. Its branch circuit must be rated at least 18.75 × 1.25 = 23.4 18.75 \times 1.25 = 23.4 18.75 × 1.25 = 23.4 A, so use a 25 A circuit with 10 AWG copper.

Central heating equipment (422.12)

Central heating equipment other than fixed electric space-heating equipment, such as a gas furnace, must be supplied by an individual branch circuit . Exceptions:

auxiliary equipment directly associated with the heating equipment, such as a pump, valve, humidifier, or electrostatic air cleaner, may be on the same circuit; and

new in the 2026 NEC: the circuit may also supply the HVAC service receptacle required by 210.63(A) and the lighting outlet for the service area required by 210.70(C).

DLI's 2026 review also describes the exception as broadened to cover similar associated equipment on the dedicated furnace circuit.

Cord-and-plug connection (422.16(B))

Appliance Cord length Other conditions

In-sink waste disposer 18 in. to 36 in. Grounding-type attachment plug (unless double insulated); receptacle located to avoid cord damage and accessible

Built-in dishwasher 3 ft to 6.5 ft , measured from the face of the plug to the plane of the rear of the appliance Receptacle in the space adjacent to the space the dishwasher occupies, and accessible

Trash compactor 3 ft to 4 ft , measured the same way Receptacle in the space occupied by the appliance or adjacent to it, and accessible

Range hood, and microwave with integral range hood 18 in. to 4 ft Cord identified in the manufacturer's instructions; receptacle accessible and supplied by an individual branch circuit

Wall-mounted oven and counter-mounted cooking unit As needed for servicing Cord-and-plug or permanent connection

Disconnecting means (422.31 to 422.34)

  • Appliance Disconnecting means
  • Rated not over 300 VA or ⅛ hp The branch-circuit OCPD may serve

Rated over 300 VA A switch or circuit breaker within sight of the appliance, or capable of being locked in the open position (110.25)

  • Motor-operated, over ⅛ hp Within sight, or lockable where not within sight
  • Cord-and-plug connected An accessible attachment plug and receptacle may serve

Unit switches with a marked "off" position May serve where another means is provided, such as the service disconnect in a single-family dwelling

Fixed electric space heating (Article 424)

Rule Requirement

Continuous load (424.4(B)) Fixed electric space-heating equipment and its motors are a continuous load ; branch circuits and conductors are sized at 125%

Branch circuits (424.4(A)) Individual branch circuits may supply any size of fixed heating; branch circuits supplying two or more outlets are rated 15, 20, 25, or 30 A (in nonresidential occupancies, fixed infrared heating may be on circuits up to 50 A )

Disconnecting means (424.19) A means to disconnect the heater, motor controller, and supplementary OCPDs from all ungrounded conductors, within sight or lockable

Overcurrent protection (424.22) Resistance elements subdivided so each load does not exceed 48 A , protected at not more than 60 A

Baseboard heaters (424.9) Listed baseboard heaters with factory-installed receptacles may serve as required receptacle outlets, but the receptacles may not be connected to the heater circuit; follow the listing, which often prohibits installing heaters below receptacle outlets

Thermostats (424.20) Indicating thermostats with an off position must open all ungrounded conductors when off, and may serve as the required disconnecting means only if they can be locked in the open position

Example: two 2,000 W, 240 V baseboard heaters on one circuit: 4000 ÷ 240 = 16.7 4000 \div 240 = 16.7 4000 ÷ 240 = 16.7 A; 16.7 × 1.25 = 20.8 16.7 \times 1.25 = 20.8 16.7 × 1.25 = 20.8 A. A 20 A circuit is too small, so use a 25 A or 30 A circuit with conductors sized to match.

Heating cables in ceilings, floors, and walls (Article 424, Part V)

Rule Requirement

GFCI (424.44(E)) GFCI protection for personnel is required for heating cables installed in electrically heated floors of bathrooms , kitchens , and hydromassage bathtub, spa, and hot tub locations

Wiring above heated ceilings (424.36) Wiring contained in thermal insulation above a heated ceiling must be at least 2 in. above the ceiling and is treated as operating in a 50°C (122°F) ambient for ampacity correction; wiring above at least 2 in. of thermal insulation needs no correction

Wiring in walls (424.37) Branch-circuit wiring in interior walls of rooms with heated ceilings is treated as operating at 40°C (104°F) ; wiring in exterior walls follows Article 300 and the 310.15 ampacity rules

Cable installation Heating cables may not extend beyond the room or area they heat, may not be installed in closets or over walls or partitions that extend to the ceiling, and must keep specified clearances from boxes and luminaires

Deicing, snow-melting, and pipeline heating (Articles 426 and 427)

Minnesota winters make heated sidewalks, ramps, roof and gutter deicing cable, and heat-traced pipes common:

GFPE (426.28): ground-fault protection of equipment is required for fixed outdoor electric deicing and snow-melting equipment, except equipment using mineral-insulated, metal-sheathed cable embedded in a noncombustible medium . A 30 mA equipment protective device is typical.

Pipeline and vessel heating (427.22): GFPE is required for electric heat tracing, with limited exceptions for industrial establishments with qualified maintenance.

Branch circuits: deicing and snow-melting equipment is a continuous load , sized at 125%.

Expansion and contraction (Article 426): embedded heating cables and their leads must be protected where they pass through expansion joints and where they leave the embedding material, so movement of the slab does not damage them.

Disconnecting means (426.50): a means to disconnect all ungrounded conductors simultaneously; it must be of the indicating type and lockable in the open position, and the branch-circuit switch or breaker may serve where readily accessible to the user.

Conductive pavement heating (new Part VI of Article 426, 2026): systems operating at not more than 30 V RMS or 60 V DC , used for snow and ice melting.

Outdoor receptacles: a receptacle that is not readily accessible and supplies only a dedicated snow-melting, deicing, or pipeline heating circuit is exempt from the dwelling GFCI requirement for outdoor receptacles, because the equipment already has GFPE.

Worked example: a garage with a heated driveway

A new home has a 4,500 W water heater, a gas furnace, and a 9,600 W heated driveway at 240 V.

Water heater: 25 A circuit as calculated above.

Furnace: individual branch circuit, which may also feed the required service receptacle and the equipment-area light under the 2026 exception.

Driveway: 9600 ÷ 240 = 40 9600 \div 240 = 40 9600 ÷ 240 = 40 A; continuous load, so 40 × 1.25 = 50 40 \times 1.25 = 50 40 × 1.25 = 50 A. Provide a 50 A circuit with GFPE , unless it uses MI cable embedded in concrete, and a lockable disconnecting means.