14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402)
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402)
Key Takeaways Explain This Topic AI
Flexible cords may not be used as a substitute for fixed wiring, run through walls, ceilings, floors, doorways, or windows, attached to building surfaces, or concealed behind walls or above suspended ceilings (400.12).
Cords used for portable equipment, frequent interchange, or appliances designed for ready removal must have an attachment plug and be energized from a receptacle or cord connector (400.10(B)).
Table 400.5(A)(1) gives 14 AWG cord an ampacity of 15 A with three current-carrying conductors and 18 A with two.
Hard-service and junior hard-service cords 14 AWG and larger may be repaired with splices that keep the cord's insulation, sheath, and usage characteristics (400.13).
Fixture wire ampacities are 6 A for 18 AWG, 8 A for 16 AWG, 17 A for 14 AWG, 23 A for 12 AWG, and 28 A for 10 AWG (Table 402.5).
Last updated: October 2026
Why cords are tested
Cords are the most abused wiring method on job sites and in buildings. DLI's knowledge areas include flexible cords and cables and fixture wires . Most questions ask whether a cord use is permitted, what type of cord is needed, or how much current it can carry.
Uses permitted (400.10)
Flexible cords and flexible cables are permitted only for:
- pendants;
- wiring of luminaires;
- connection of portable luminaires, portable and mobile signs, or appliances;
- elevator cables;
- wiring of cranes and hoists;
- connection of utilization equipment to facilitate frequent interchange ;
- prevention of the transmission of noise or vibration ;
appliances whose fastening means and mechanical connections are specifically designed to permit ready removal for maintenance and repair, where the appliance is intended or identified for cord connection;
- connection of moving parts;
- where specifically permitted elsewhere in the Code; and
between an existing receptacle outlet and an inlet that supplies an additional single receptacle outlet, under specific conditions.
For items 3, 6, and 8, the cord must have an attachment plug and be energized from a receptacle outlet or cord connector body (400.10(B)).
Uses not permitted (400.12)
Unless specifically permitted elsewhere, flexible cords and cables may not be used:
- as a substitute for the fixed wiring of a structure;
- where run through holes in walls, structural ceilings, suspended or dropped ceilings, or floors;
- where run through doorways, windows , or similar openings;
- where attached to building surfaces ;
- where concealed by walls, floors, or ceilings, or located above suspended or dropped ceilings ;
- where installed in raceways , except as otherwise permitted; or
where subject to physical damage .
A common inspection failure is a cord-connected appliance in a ceiling space, such as a projector or condensate pump plugged into a receptacle above a lay-in ceiling. That cord is located above a suspended ceiling, which 400.12 prohibits, unless another article specifically permits it.
Cord types (Table 400.4)
- Letter or type Meaning
- S Hard service (extra-hard usage), 600 V
- SJ Junior hard service (hard usage), 300 V
- E Thermoplastic elastomer
- O Oil-resistant outer jacket
- OO Oil-resistant insulation and outer jacket
- W Weather and water resistant, suitable for wet locations and sunlight
- SPT Parallel thermoplastic cord (lamp cord), not hard usage
For example, SJOOW is junior hard service, oil-resistant insulation and jacket, weather resistant. Construction-site cords for temporary power must be listed for hard or extra-hard usage (Article 590). Hard-service cords are marked with their type designation at intervals not exceeding 24 in.
Ampacity (Table 400.5(A)(1))
- Size Column A: three current-carrying conductors Column B: two current-carrying conductors
- 18 AWG 7 A 10 A
- 16 AWG 10 A 13 A
- 14 AWG 15 A 18 A
- 12 AWG 20 A 25 A
- 10 AWG 25 A 30 A
- 8 AWG 35 A 40 A
- 6 AWG 45 A 55 A
An equipment grounding conductor does not count as a current-carrying conductor. For more than three current-carrying conductors in a cord, adjustment factors from Table 400.5(A)(3) apply.
Splices, strain relief, and identification
Splices (400.13): cords must be used only in continuous lengths without splice or tap when initially installed. Hard-service and junior hard-service cords 14 AWG and larger may be repaired by splicing if the completed splice retains the insulation, outer sheath, and usage characteristics of the cord.
Strain relief (400.14): cords must be connected to devices and fittings so that tension is not transmitted to joints or terminal screws, for example with knots, cord clamps, or fittings designed for the purpose.
Identification (400.22 and 400.23): the grounded conductor is identified by a white or gray finish, a tracer, ribbing, or similar means; the equipment grounding conductor is green or green with yellow stripes.
Overcurrent protection (240.5): a flexible cord is considered protected when it is used within the listing of the appliance or portable lamp it supplies. Extension cord sets of 16 AWG and larger are considered protected when used with listed equipment.
Fixture wires (Article 402)
Fixture wires (such as TF, TFF, TFN, SF-2, and PTF) are used in luminaires and similar equipment, and to connect luminaires to branch-circuit conductors. They may not be used as branch-circuit conductors, except where another article permits it, such as for certain power-limited circuits. The minimum size is 18 AWG .
- Size Ampacity (Table 402.5)
- 18 AWG 6 A
- 16 AWG 8 A
- 14 AWG 17 A
- 12 AWG 23 A
- 10 AWG 28 A
Protection of fixture wire (240.5(B)(2)): on a 20 A circuit, 18 AWG fixture wire may run up to 50 ft and 16 AWG up to 100 ft ; 14 AWG and larger is permitted without a length limit. On 30 A circuits, 14 AWG and larger; on 40 A and 50 A circuits, 12 AWG and larger.
Worked example: a cord-connected shop machine
A woodworking machine is cord-and-plug connected so it can be moved for maintenance. Its nameplate is 12 A at 240 V, single phase.
The use is permitted for frequent interchange or ready removal, with an attachment plug and a receptacle.
The cord has two current-carrying conductors and an EGC, so use Column B : 16 AWG is 13 A, which carries 12 A, but a hard-usage cord of 14 AWG (18 A) is the practical choice for a shop.
The cord must have strain relief at both ends and may not be stapled along the wall or run through it.