14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406)
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406)
Key Takeaways Explain This Topic AI
The 2026 NEC moved snap switches, dimmers, and electronic control switches from Article 404 into Article 406, which is now titled Wiring Devices.
A general-use snap switch may control motor loads only up to 80% of its ampere rating at rated voltage.
All 15- and 20-ampere, 125- and 250-volt nonlocking receptacles in dwelling units must be listed tamper-resistant, and the 2026 NEC 406.26 adds park and recreation areas to the list of locations.
Receptacles may not be installed within 3 ft horizontally and 8 ft vertically of a bathtub rim or shower stall threshold, including the space directly over the tub or shower.
A nongrounding receptacle may be replaced with a GFCI receptacle marked "No Equipment Ground," or with a grounding-type receptacle protected by a GFCI and marked "GFCI Protected" and "No Equipment Ground."
Last updated: October 2026
What changed in 2026
DLI's 2026 NEC review lists these device changes:
Article 406 renamed "Wiring Devices": it now covers receptacles, cord connectors, attachment plugs, snap switches, dimmers, and electronic control switches . Article 404 keeps the requirements for other switches, such as safety switches and circuit breakers used as switches.
406.12(D)(3): the exception that lets a replacement receptacle skip GFCI protection when upstream protection is not feasible was rewritten to give installers more options.
406.14(G): receptacles may not be installed face up in laundry areas, such as a dryer receptacle mounted face up in the floor.
406.26: tamper-resistant receptacles are now also required in park and recreation areas .
Because the 2026 edition renumbered these articles, this section cites them by rule rather than by every old section number.
- Switches
- Connection and location
Ungrounded conductors only: switches and circuit breakers may not disconnect the grounded conductor unless all circuit conductors open simultaneously, or the arrangement prevents the grounded conductor from being opened by itself.
Grounded conductor at switch locations: where switches control lighting loads, a grounded (neutral) conductor must be provided at the switch location, with limited exceptions, such as a raceway that has room to add one later or a location with access to pull one in later. Occupancy sensors and other electronic controls need the neutral.
3-way and 4-way switching: all switching is done in the ungrounded conductor. In metal raceways or cable armor, the conductors of the switch loop must be grouped to avoid inductive heating.
Height: switches and circuit breakers used as switches must be installed so the center of the grip of the operating handle in its highest position is not more than 6 ft 7 in. above the floor or working platform.
Wet locations: switches in wet locations need a weatherproof enclosure, and switches may not be within the wet locations of tub or shower spaces unless part of a listed tub or shower assembly.
Faceplates: metal faceplates must be grounded; switches must be mounted so faceplates seat against the finished surface.
Voltage between adjacent devices: snap switches may not be grouped or ganged in one enclosure unless the voltage between adjacent switches does not exceed 300 V , or identified barriers are installed between them, such as when 277 V and 120 V switches share a box.
Enclosures not used as raceways: switch and circuit breaker enclosures may not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or overcurrent devices, unless designed with adequate space.
Ratings for general-use snap switches
Switch type Permitted loads
AC general-use snap switch Resistive and inductive loads up to its ampere rating at its voltage; tungsten-filament lamp loads up to its ampere rating at 120 V; motor loads up to 80% of its ampere rating at rated voltage
AC-DC general-use snap switch Resistive loads up to its rating; inductive loads up to 50% of its rating; tungsten-filament lamp loads only if marked T
Dimmers Only for permanently installed incandescent luminaires unless listed for the control of other loads, such as LED drivers
A 20 A, 120 V AC snap switch may control a motor drawing up to 20 × 0.80 = 16 20 \times 0.80 = 16 20 × 0.80 = 16 A.
- Receptacles
- Ratings and configurations
Receptacles must be rated for the circuit voltage and current. Typical NEMA configurations: 5-15 and 5-20 (125 V, grounding), 6-20 and 6-30 (250 V, grounding), 14-30 (dryer, 125/250 V, 4-wire), and 14-50 (range or EVSE, 125/250 V, 4-wire). Three-wire 10-30 and 10-50 receptacles, without an EGC, are permitted only for existing range and dryer branch circuits.
Tamper-resistant receptacles
Listed tamper-resistant receptacles are required for all nonlocking 15- and 20-ampere, 125- and 250-volt receptacles in:
- all areas of dwelling units , including garages and outdoors;
- hotel and motel guest rooms and guest suites, and dormitory units;
- child care facilities, preschools, and education facilities;
business offices, corridors, waiting rooms, and similar areas of clinics, medical, and dental offices, and outpatient facilities;
- the assembly occupancies of places of waiting transportation, gymnasiums, skating rinks, and auditoriums;
- assisted living facilities and agricultural buildings accessible to the public; and
park and recreation areas (new in 2026).
Exceptions: receptacles more than 5½ ft above the floor; receptacles that are part of a luminaire or appliance; a single receptacle or duplex receptacle for two appliances in a dedicated space where the appliances are not easily moved; and nongrounding receptacles used as replacements.
Damp and wet locations
Weather-resistant: all nonlocking 15- and 20-ampere, 125- and 250-volt receptacles in damp and wet locations must be listed weather-resistant (WR) .
Wet locations: 15- and 20-ampere receptacles in a wet location need an enclosure that is weatherproof whether or not an attachment plug is inserted , with an outlet box hood listed and identified as extra-duty .
Bathtubs and showers: receptacles may not be installed within a zone 3 ft horizontally and 8 ft vertically from the top of the bathtub rim or shower stall threshold. The zone includes the space directly over the tub or shower.
Face-up receptacles: not permitted in countertops or work surfaces unless listed for that use, and, under the 2026 NEC, not in laundry areas.
Isolated ground receptacles
An isolated ground receptacle has its grounding terminal insulated from the mounting yoke. It is identified by an orange triangle on its face, and its insulated EGC is installed as described in 250.146(D).
Replacing receptacles
- Situation Rule
- Grounding means exists Install a grounding-type receptacle and connect the EGC
No grounding means (1) a nongrounding receptacle; (2) a GFCI receptacle marked "No Equipment Ground" ; or (3) a grounding-type receptacle protected by a GFCI and marked "GFCI Protected" and "No Equipment Ground" ; an EGC may also be added under 250.130(C)
Location now requires GFCI Provide GFCI protection, subject to the rewritten 2026 exception where upstream protection is not feasible
Location now requires AFCI Provide AFCI protection, such as a listed outlet branch-circuit AFCI receptacle, a listed combination AFCI breaker, or a receptacle downstream of an OBC AFCI
- Location now requires TR or WR Use a tamper-resistant or weather-resistant replacement as required
- Worked example: replacing a two-wire bedroom receptacle
A homeowner asks for a three-prong receptacle in a 1950s bedroom with two-wire cable and no grounding conductor.
A grounding-type receptacle may not simply be installed with the grounding terminal unconnected.
Options: add an EGC under 250.130(C), or provide GFCI protection and mark the receptacle "No Equipment Ground" (plus "GFCI Protected" if it is protected by an upstream device).
The bedroom is an area where AFCI protection is now required, so the replacement must also have AFCI protection, such as a dual-function receptacle or breaker.
The replacement must be tamper-resistant , because it is in a dwelling unit.