15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24)
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24)
Key Takeaways Explain This Topic AI
Motor overload protection under NEC 430.32 is sized strictly from the motor nameplate full-load current rating, not the Table FLC values.
Overload protective devices must be sized at not more than 125% of nameplate FLC for motors with a marked Service Factor of 1.15 or greater or a marked temperature rise of 40°C or less, and not more than 115% for all other motors.
If the selected overload device is incapable of carrying the motor starting or running current, NEC 430.32(C) permits increasing the trip setting to a maximum of 140% (for SF ≥ \ge ≥ 1.15 or temp rise ≤ \le ≤ 40°C) or 130% (for all other motors).
Feeder conductors supplying multiple motors must have an ampacity of not less than 125% of the highest-rated motor FLC plus the sum of the full-load currents of all other motors on the feeder under NEC 430.24.
Under NEC 430.62(A), feeder short-circuit and ground-fault protective devices must not exceed the largest permitted branch-circuit protective device of any motor in the group plus the sum of all other motor FLCs, rounding DOWN to the next lower standard rating if non-standard.
Last updated: October 2026
15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24)
Quick Answer: Under NEC 430.32 , motor overload protection is sized strictly from the motor nameplate current rating , not table values: 125% of nameplate FLC for motors with a marked Service Factor of 1.15 or greater or a marked temperature rise of 40 ∘ C 40^\circ\text{C} 4 0 ∘ C or less , and 115% of nameplate FLC for all other motors. For multi-motor feeders under NEC 430.24 , feeder conductors must have an ampacity of not less than 125% of the highest-rated motor FLC plus the sum of the FLCs of all other motors ( 1.25 × I largest + ∑ I others 1.25 \times I_{\text{largest}} + \sum I_{\text{others}} 1.25 × I largest + ∑ I others ). Under NEC 430.62(A) , feeder short-circuit protection is sized from the largest branch SCGF device plus the sum of other motor FLCs , rounding DOWN to the next lower standard rating if non-standard.
Motor circuits present unique challenges both at the individual motor level (thermal overload protection) and at the distribution level (sizing feeders serving multiple motors). Overheating is the primary cause of motor insulation breakdown and winding fires, resulting from mechanical binding, extended acceleration cycles, low line voltage, or the loss of one phase on a three-phase system (single-phasing). At the feeder level, calculating conductor ampacity and selecting overcurrent protective devices requires a distinct mathematical procedure that accounts for diversity and starting transients.
Motor Overload Protection Fundamentals (NEC 430 Part III)
An overload is an operating condition in which current exceeds normal full-load rating due to mechanical overloading, locked rotor, or abnormal voltage, but does not involve a short circuit or ground fault. Overload currents typically range from 110 % 110\% 110% to 600 % 600\% 600% of rated current .
Overload Sizing: The Nameplate Exception (NEC 430.6(A)(1))
While conductors and fuses/breakers are sized from NEC Tables 430.247–430.250, NEC 430.6(A)(1) mandates that motor overload protection must be based on the actual motor nameplate full-load current :
The Two Sizing Tiers of NEC 430.32(A)(1)
For continuous-duty motors rated more than 1 horsepower, separate overload devices (such as thermal overload relay heaters or electronic overload relays) must be sized according to the two specific criteria of NEC 430.32(A)(1) :
The 125% Tier (High Thermal Resilience):
Motors marked with a Service Factor (SF) of 1.15 or greater ; OR
Motors marked with a temperature rise of 40 ∘ C 40^\circ\text{C} 4 0 ∘ C or less . Maximum Overload Trip Setting = Nameplate FLC × 1.25 \text{Maximum Overload Trip Setting} = \text{Nameplate FLC} \times 1.25 Maximum Overload Trip Setting = Nameplate FLC × 1.25
The 115% Tier (Standard Thermal Resilience):
All other motors (e.g., motors with a Service Factor of 1.0, or marked with a temperature rise greater than 40 ∘ C 40^\circ\text{C} 4 0 ∘ C ). Maximum Overload Trip Setting = Nameplate FLC × 1.15 \text{Maximum Overload Trip Setting} = \text{Nameplate FLC} \times 1.15 Maximum Overload Trip Setting = Nameplate FLC × 1.15
What Is Motor Service Factor?
The Service Factor (SF) represents a multiplier indicating the percentage of continuous mechanical overload a motor can safely deliver without sustaining thermal damage, assuming rated voltage and frequency. A motor with an SF of 1.15 1.15 1.15 can deliver 115 % 115\% 115% of its rated horsepower continuously. Because an SF 1.15 1.15 1.15 motor has greater copper mass and higher-grade insulation, the Code permits overload devices to be set higher ( 125 % 125\% 125% vs. 115 % 115\% 115% ).
Modifying Overload Protection (NEC 430.32(C))
If the overload relay selected according to the standard 125 % 125\% 125% or 115 % 115\% 115% limits is insufficient to start the motor or carry the load, NEC Section 430.32(C) permits installing the next higher size overload relay or setting the trip point up to the following absolute maximum modification caps :
Motors with SF ≥ 1.15 \ge 1.15 ≥ 1.15 or temp rise ≤ 40 ∘ C \le 40^\circ\text{C} ≤ 4 0 ∘ C : maximum 140 % 140\% 140% of nameplate FLC.
All other motors: maximum 130 % 130\% 130% of nameplate FLC.
Number of Overload Units Required (NEC Table 430.37)
Under NEC Table 430.37 , for any three-phase AC motor, three overload units (one in each ungrounded phase conductor) are required. In the past, older code editions permitted two overload units; however, if one phase opens on a wye-delta transformer supplying a three-phase motor, current in one winding can increase to 230 % 230\% 230% of normal. Three overload units guarantee detection regardless of system transformer connections.
Multi-Motor Feeder Conductor Sizing (NEC 430.24)
In industrial plants and commercial buildings, a single feeder raceway frequently supplies a motor control center (MCC) or distribution panel feeding multiple motors. How are the feeder conductors sized?
The 125% Largest Motor Rule (NEC 430.24)
Under NEC Section 430.24 , conductors supplying two or more motors shall have an ampacity not less than:
125 percent of the full-load current rating of the highest-rated motor in the group; plus
The sum of the full-load current ratings of all other motors in the group.
Feeder Minimum Ampacity = ( 1.25 × I largest, table ) + ∑ I other motors, table \text{Feeder Minimum Ampacity} = (1.25 \times I_{\text{largest, table}}) + \sum I_{\text{other motors, table}} Feeder Minimum Ampacity = ( 1.25 × I largest, table ) + ∑ I other motors, table
Critical Feeder Conductor Sizing Rules:
Highest-Rated Motor Is Based on Amperes, Not Horsepower: The "largest motor" is defined under NEC 430.17 as the motor with the highest Table FLC . If a feeder powers a 10 HP, 208V single-phase motor ( 55 A 55\text{ A} 55 A from Table 430.248) and a 15 HP, 460V three-phase motor ( 21 A 21\text{ A} 21 A ), the 10 HP motor is the "largest motor" ( 55 A > 21 A 55\text{ A} > 21\text{ A} 55 A > 21 A ).
Tied Highest Ratings: If two or more motors in the group have identical largest currents, only one motor is multiplied by 1.25 1.25 1.25 . All remaining motors are added at 100 % 100\% 100% .
Feeders Supplying Motors Plus Other Loads (NEC 430.24(1)–(3)): If the feeder also supplies non-motor loads (lighting, heating, receptacles), the ampacity must satisfy: Feeder Ampacity ≥ ( 1.25 × I largest motor ) + ∑ I other motors + ( 1.25 × I continuous loads ) + I noncontinuous loads \text{Feeder Ampacity} \ge (1.25 \times I_{\text{largest motor}}) + \sum I_{\text{other motors}} + (1.25 \times I_{\text{continuous loads}}) + I_{\text{noncontinuous loads}} Feeder Ampacity ≥ ( 1.25 × I largest motor ) + ∑ I other motors + ( 1.25 × I continuous loads ) + I noncontinuous loads
Multi-Motor Feeder Short-Circuit Protection (NEC 430.62)
Selecting the overcurrent protective device for a motor feeder is one of the most critical calculation skills tested on the Minnesota licensing exam. It differs sharply from branch circuit calculation.
The Sizing Formula (NEC 430.62(A))
Under NEC 430.62(A) , a feeder supplying a specific fixed motor load shall have a protective device with a rating or setting not greater than :
The largest rating or setting of the branch-circuit short-circuit and ground-fault protective device for any motor of the group (calculated under Table 430.52 and Section 430.52(C)(1) Exception No. 1); plus
The sum of the full-load currents of all other motors of the group.
Feeder OCPD Max = Largest Permitted Branch SCGF Device + ∑ I other motors, table \text{Feeder OCPD Max} = \text{Largest Permitted Branch SCGF Device} + \sum I_{\text{other motors, table}} Feeder OCPD Max = Largest Permitted Branch SCGF Device + ∑ I other motors, table
- THE CRITICAL DIFFERENCE: Rounding DOWN on Feeders
- Pay close attention to the language of NEC 430.62(A) : "shall not have a rating or setting greater than..."
On Branch Circuits (NEC 430.52(C)(1) Ex. 1) , if a calculation yields a non-standard rating, you are permitted to ROUND UP to the next higher standard rating.
On Feeders (NEC 430.62(A)) , you MUST ROUND DOWN to the next lower standard rating listed in NEC 240.6(A) if the calculation does not match a standard size! The Code does not provide a general "next size up" exception for motor feeders.
- Step-by-Step Worked Feeder & Overload Calculations
- Example 1: Motor Overload Relay Heater Sizing
A continuous-duty, 3-phase, 460-volt, 20 HP motor has a marked nameplate current of 25.0 A 25.0\text{ A} 25.0 A , a service factor of 1.15 1.15 1.15 , and a temperature rise of 40 ∘ C 40^\circ\text{C} 4 0 ∘ C . The Table 430.250 full-load current is 27.0 A 27.0\text{ A} 27.0 A . What is the maximum initial trip current setting for the separate overload protection device?
Step 1: Identify Governing Current
Under NEC 430.6(A)(1) , overload protection is sized from nameplate current ( 25.0 A 25.0\text{ A} 25.0 A ), NOT Table FLC ( 27.0 A 27.0\text{ A} 27.0 A ).
Step 2: Determine Overload Percentage (NEC 430.32(A)(1))
Marked Service Factor is 1.15 1.15 1.15 (meets the ≥ 1.15 \ge 1.15 ≥ 1.15 threshold).
Multiplier = 125 % 125\% 125% ( 1.25 1.25 1.25 ).
Step 3: Calculate Overload Setting
Max Overload Setting = 25.0 A × 1.25 = 31.25 A \text{Max Overload Setting} = 25.0\text{ A} \times 1.25 = \mathbf{31.25\text{ A}} Max Overload Setting = 25.0 A × 1.25 = 31.25 A
(Note: If the service factor had been 1.0 1.0 1.0 , the multiplier would be 115 % 115\% 115% , yielding 25.0 A × 1.15 = 28.75 A 25.0\text{ A} \times 1.15 = 28.75\text{ A} 25.0 A × 1.15 = 28.75 A .)
Example 2: Feeder Conductor Sizing for Multiple 3-Phase Motors
An industrial feeder supplies three 460-volt, 3-phase squirrel-cage induction motors:
- Motor 1: 30 HP ( I FLC = 40 A I_{\text{FLC}} = 40\text{ A} I FLC = 40 A from Table 430.250)
- Motor 2: 15 HP ( I FLC = 21 A I_{\text{FLC}} = 21\text{ A} I FLC = 21 A from Table 430.250)
- Motor 3: 10 HP ( I FLC = 14 A I_{\text{FLC}} = 14\text{ A} I FLC = 14 A from Table 430.250)
All terminals are rated for 75 ∘ C 75^\circ\text{C} 7 5 ∘ C . What is the minimum required feeder conductor ampacity and the smallest copper THHN conductor permitted?
Step 1: Identify the Highest-Rated Motor
Motor 1 has the largest full-load current: 40 A 40\text{ A} 40 A .
Step 2: Apply the NEC 430.24 Feeder Formula Feeder Ampacity ≥ ( 1.25 × I largest ) + ∑ I others = ( 1.25 × 40 A ) + 21 A + 14 A = 50 A + 35 A = 85.0 A \begin{aligned}
- \text{Feeder Ampacity} &\ge (1.25 \times I_{\text{largest}}) + \sum I_{\text{others}} \\
- &= (1.25 \times 40\text{ A}) + 21\text{ A} + 14\text{ A} \\
- &= 50\text{ A} + 35\text{ A} = \mathbf{85.0\text{ A}}
\end{aligned} Feeder Ampacity ≥ ( 1.25 × I largest ) + ∑ I others = ( 1.25 × 40 A ) + 21 A + 14 A = 50 A + 35 A = 85.0 A
Step 3: Select Conductor Size from NEC Table 310.16
Review 75 ∘ C 75^\circ\text{C} 7 5 ∘ C copper column:
4 AWG copper has an allowable ampacity of 85 A 85\text{ A} 85 A ( 85 A ≥ 85.0 A 85\text{ A} \ge 85.0\text{ A} 85 A ≥ 85.0 A — acceptable).
Conclusion: Sizing requires 4 AWG THHN copper conductors.
Example 3: Feeder Overcurrent Protective Device Sizing
For the three motors in Example 2, an inverse-time circuit breaker will be installed as the feeder overcurrent protective device. Each branch circuit is protected by an inverse-time circuit breaker sized at the maximum standard rating permitted by NEC 430.52(C)(1) Exception No. 1. What is the maximum standard rating permitted for the feeder circuit breaker?
Step 1: Calculate Branch SCGF Device for Each Motor (Table 430.52 @ 250%)
Motor 1 (40A): 40 A × 2.50 = 100 A 40\text{ A} \times 2.50 = 100\text{ A} 40 A × 2.50 = 100 A . (100A is a standard size under NEC 240.6(A)). Branch breaker = 100 A 100\text{ A} 100 A .
Motor 2 (21A): 21 A × 2.50 = 52.5 A 21\text{ A} \times 2.50 = 52.5\text{ A} 21 A × 2.50 = 52.5 A . Next standard size up under Exception 1 = 60 A 60\text{ A} 60 A .
Motor 3 (14A): 14 A × 2.50 = 35.0 A 14\text{ A} \times 2.50 = 35.0\text{ A} 14 A × 2.50 = 35.0 A . (35A is a standard size). Branch breaker = 35 A 35\text{ A} 35 A .
Step 2: Identify the Largest Permitted Branch Device
The largest branch protective device in the group is Motor 1's breaker: 100 A 100\text{ A} 100 A .
Step 3: Apply the NEC 430.62(A) Feeder Formula Feeder OCPD Max = Largest Branch Device + ∑ I other motors = 100 A + 21 A + 14 A = 100 A + 35 A = 135.0 A \begin{aligned}
- \text{Feeder OCPD Max} &= \text{Largest Branch Device} + \sum I_{\text{other motors}} \\
- &= 100\text{ A} + 21\text{ A} + 14\text{ A} \\
- &= 100\text{ A} + 35\text{ A} = \mathbf{135.0\text{ A}}
\end{aligned} Feeder OCPD Max = Largest Branch Device + ∑ I other motors = 100 A + 21 A + 14 A = 100 A + 35 A = 135.0 A
Step 4: Apply the Rounding DOWN Rule (NEC 430.62(A))
Review standard ratings in NEC 240.6(A): 100 , 110 , 125 , 150 , 175 A 100, 110, 125, 150, 175\text{ A} 100 , 110 , 125 , 150 , 175 A .
Sizing cannot exceed 135 A 135\text{ A} 135 A . Rounding up to 150A is strictly prohibited by Section 430.62(A).
The next lower standard rating is 125 A 125\text{ A} 125 A : Maximum Permitted Feeder Breaker = 125 A \text{Maximum Permitted Feeder Breaker} = \mathbf{125\text{ A}} Maximum Permitted Feeder Breaker = 125 A
- Practical Exam Scenarios & Trap Avoidance
- Trap 1: Multiplying All Motors by 125% on a Feeder
Exam Trap: Sizing a multi-motor feeder by multiplying the sum of all motor currents by 1.25: ( 40 + 21 + 14 ) × 1.25 = 75 × 1.25 = 93.75 A (40 + 21 + 14) \times 1.25 = 75 \times 1.25 = 93.75\text{ A} ( 40 + 21 + 14 ) × 1.25 = 75 × 1.25 = 93.75 A .
Correction: Under NEC 430.24 , only the single highest-rated motor is multiplied by 1.25 1.25 1.25 . All other motors are added at 100 % 100\% 100% .
Trap 2: Rounding UP the Feeder OCPD
Exam Trap: Calculating 135 A 135\text{ A} 135 A for a feeder breaker and selecting a 150A breaker.
Correction: Under NEC 430.62(A) , feeder protective devices must not exceed the calculated value. You must ROUND DOWN to 125A.
Trap 3: Using Table FLC for Overload Sizing
Exam Trap: A question gives both nameplate current and Table FLC and asks for the overload heater size.
Correction: Overload sizing is the ONLY calculation in Article 430 that uses nameplate current . Conductors and breakers use Table FLC.