Study guide

19.2 Elevators, Escalators & Platform Lifts (Article 620)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

19.2 Elevators, Escalators & Platform Lifts (Article 620)

Key Takeaways Explain This Topic AI

Each elevator must have a single means to disconnect all ungrounded main power supply conductors, lockable open, with no provision to open or close it from elsewhere in the premises except a sprinkler-related automatic opening (620.51).

A separate branch circuit is required for elevator car lights, receptacles, auxiliary lighting, and ventilation, with its own disconnecting means in the machine room or control room (620.22 and 620.53).

Each 125 V, single-phase, 15- and 20-ampere receptacle in elevator pits, hoistways, cars, machine rooms, and escalator wellways must be GFCI protected, except a single receptacle for a permanently installed sump pump (620.85).

Conductors in elevator wireways may fill up to 50% of the wireway's interior cross-sectional area (620.32).

The feeder demand factor for elevators is 1.00 for one elevator, 0.95 for two, 0.90 for three, and 0.85 for four (Table 620.14).

Last updated: October 2026

Why elevator rules matter to a journeyworker

Article 620 covers elevators, dumbwaiters, escalators, moving walks, platform lifts, and stairway chairlifts. In Minnesota, the elevator equipment itself is installed by licensed elevator constructors under the state elevator code, but electricians install the feeders, disconnects, branch circuits, lighting, and receptacles in machine rooms, pits, and hoistways. DLI lists several Article 620 knowledge areas for the journeyworker exam.

Live parts and working space

Live parts enclosed (620.4): all live parts of electrical apparatus in hoistways, at landings, in or on cars, in escalator wellways, and in machine rooms must be enclosed to protect against accidental contact.

Working clearances (620.5): working space must be provided around controllers, disconnecting means, and other electrical equipment as required by 110.26, with limited exceptions for flexible connections and equipment guarded or with limited voltages.

Conductors

Rule Requirement

Insulation (620.11) Hoistway door interlock wiring must be flame retardant and suitable for at least 200°C; traveling cables must be of types listed in Table 400.4 or other approved types

Minimum size, traveling cables (620.12(A)) Lighting circuits: 14 AWG copper , or 20 AWG copper or larger in parallel with an ampacity equivalent to 14 AWG; other circuits: 20 AWG copper

Minimum size, other wiring (620.12(B)) 24 AWG copper for control and signaling circuits, and smaller where permitted for Class 2 circuits

Feeder and branch-circuit conductors (620.13) Sized from the motor nameplate current and the duty rating using 430.22(E), or from the controller's input current for drives

Feeder demand factors (Table 620.14) Multiply the sum of the motor ratings by: 1 elevator 1.00 ; 2 0.95 ; 3 0.90 ; 4 0.85 ; 5 0.82 ; 6 0.79 ; 7 0.77 ; 8 0.75 ; 9 0.73 ; 10 or more 0.72

Wiring methods in hoistways and machine rooms (620.21 to 620.37)

Conductors and optical fibers in hoistways, escalator wellways, machine rooms, and control rooms must be installed in RMC, IMC, EMT, PVC, RTRC, wireways , or be Type MC, MI, or AC cable , unless otherwise permitted, such as flexible connections of limited length between risers and limit switches, interlocks, and similar devices.

Wireway fill (620.32): the total cross-sectional area of conductors in a wireway may not exceed 50% of its interior area, which is more generous than the 20% allowed in general-purpose wireways.

Raceways and cables in hoistways must be securely fastened to the hoistway construction or elevator structure.

Traveling cables must be suspended at the car and hoistway ends so strain on individual conductors is minimized, and protected against damage from the hoistway construction.

Only elevator wiring: only the electrical wiring, raceways, and cables used directly in connection with the elevator, including signal and communications wiring, may be installed inside the hoistway, machine room, or control room.

Branch circuits for auxiliary systems

Location Requirement

Car lighting, receptacles, and ventilation (620.22) A separate branch circuit for car lights, receptacles, auxiliary lighting power source, and ventilation on each car, with the OCPD in the machine room or control room; a required lighting circuit may not be GFCI protected

Machine rooms and control rooms (620.23) A separate branch circuit supplying the room's lighting and receptacles; the lighting switch at the point of entry; at least one 125 V, single-phase, 15- or 20-ampere duplex receptacle ; lighting not connected to the load side of a GFCI

Hoistway pits (620.24) A separate branch circuit for pit lighting and receptacles; the light switch readily accessible from the pit access door ; at least one 125 V, 15- or 20-ampere duplex receptacle in the pit; pit lighting not on the load side of a GFCI

Other utilization equipment (620.25) Additional branch circuits for other utilization equipment, such as sump pumps, as needed

Disconnecting means (620.51 to 620.55)

Disconnect Requirement

Main power (620.51) A single listed means for each elevator to disconnect all ungrounded main power supply conductors; an enclosed externally operable fused motor-circuit switch or circuit breaker, lockable open ; no provision may be made to open or close it from any other part of the premises, except that where sprinklers protect the hoistway or machine room it may be arranged to open automatically before water is applied, and it may never close automatically

Location Readily accessible to qualified persons, and within sight of the motor controller (or as otherwise permitted for machine-room-less elevators)

Identification Marked to identify the location of the supply-side OCPD; where more than one elevator, each disconnect numbered to match its machine and controller

Car lighting, receptacles, and ventilation (620.53) A separate single means for each car to disconnect all ungrounded conductors of that branch circuit, located in the machine room or control room, lockable open

  • Heating and air conditioning (620.54) A separate disconnecting means for the car's HVAC supply
  • GFCI protection (620.85)

Each 125 V, single-phase, 15- and 20-ampere receptacle installed in pits, hoistways, on cars , on platform lift platforms or runways, and in escalator and moving walk wellways must be of the GFCI type.

Each 125 V, single-phase, 15- and 20-ampere receptacle in machine rooms, control rooms, machinery spaces, and control spaces must have GFCI protection.

A single receptacle supplying a permanently installed sump pump does not require GFCI protection.

Grounding and coordination

Grounding (620.81 to 620.84): metal raceways, Type MC cable, and Type AC cable attached to cars must be bonded to grounded metal parts of the car; frames of motors, machines, controllers, and metal enclosures must be grounded under Article 250.

Selective coordination (620.62): where more than one driving machine disconnecting means is supplied by a single feeder, the OCPDs in each disconnect must be selectively coordinated with any other supply-side OCPDs. The 2026 NEC requires the coordination to be re-evaluated when OCPDs are replaced or the elevator system is modified, added to, or reduced.

Worked example: a three-elevator feeder

Three elevators have motor controller input ratings of 40 A each at 480 V. Under Table 620.14, the demand factor for three elevators is 0.90: 3 × 40 × 0.90 = 108 3 \times 40 \times 0.90 = 108 3 × 40 × 0.90 = 108 A. The feeder must also be sized for the duty rating under 620.13, and the feeder OCPDs must be selectively coordinated with each elevator's disconnect.