Study guide

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675)

Key Takeaways Explain This Topic AI

Branch circuits supplying signs and outline lighting are limited to 20 A, except circuits supplying only neon tubing installations, which may be rated up to 30 A (600.5(B)).

Each sign must have a disconnecting means that opens all ungrounded conductors and is within sight of the sign, or lockable in the open position if not within sight (600.6).

Cord-and-plug connected freestanding office partitions may use a single extra-hard-usage cord of 12 AWG or larger, not over 2 ft long, supplying no more than thirteen 15 A, 125 V receptacles and no multiwire circuits (605.9).

In an information technology room qualifying under Article 645, a disconnecting means for the ITE and the dedicated HVAC must be controllable from a readily accessible location at the principal exit doors (645.10).

A center-pivot irrigation machine needs a grounding electrode system connected to the machine at its stationary point for lightning protection (675.15).

Last updated: October 2026

  • Electric signs and outline lighting (Article 600)
  • Branch circuits (600.5)

Required sign outlet: each commercial building and each commercial occupancy accessible to pedestrians must have at least one sign outlet in an accessible location at each entrance to each tenant space , supplied by a branch circuit rated at least 20 A that supplies no other load. Service hallways and corridors used only for service are not considered entrances.

Ratings: branch circuits supplying neon tubing installations may be rated up to 30 A ; circuits supplying all other signs and outline lighting may be rated up to 20 A .

Load: each required sign outlet counts at least 1,200 VA in the load calculation (120.14(F)).

Disconnecting means (600.6)

Rule Requirement

Required Each sign and outline lighting system, or feeder or branch circuit supplying it, must have an externally operable disconnecting means that opens all ungrounded conductors and controls no other load

Location At the point where the supply enters the sign enclosure or sign body, or within sight of the sign; where not within sight, the disconnect must be lockable in the open position (110.25)

Control switch rating (600.6(B)) Switches, flashers, and similar devices controlling transformers and power supplies must be rated for inductive loads, or have an ampere rating at least twice the ampere rating of the transformer

Ballasts, transformers, and power supplies

Attics and soffits (600.21(E)): permitted where there is an access door at least 3 ft by 22½ in. , and a passageway at least 3 ft high by 2 ft wide with a suitable permanent walkway at least 12 in. wide from the point of entry to each component.

Suspended ceilings (600.21(F)): permitted above suspended ceilings if the enclosures are securely fastened in place and do not depend on the ceiling grid for support; they may not be connected to the branch circuit by flexible cord.

Accessibility: ballasts, transformers, and electronic power supplies must be accessible and securely fastened in place.

Neon secondary wiring over 1000 V (600.32)

Neon secondary circuit conductors must be listed and insulated for the voltage and installed in raceway or listed for the use. The length of secondary conductors from the high-voltage terminal of the transformer or power supply to the first neon tube electrode may not exceed 20 ft in metal conduit or tubing, or 50 ft in nonmetallic conduit.

Other sign rules

Signs must be listed and marked with the manufacturer, voltage, and current (600.3 and 600.4).

Metal parts of signs and outline lighting must be grounded and bonded (600.7), and remote metal parts are bonded with listed bonding means.

Signs and outline lighting located where they could be struck by vehicles must be at least 14 ft above areas accessible to vehicles, unless protected from physical damage (600.9).

Office furnishings (Article 605)

Article 605 covers electrical equipment, lighting accessories, and wiring systems used to connect, or contained within, office furnishings such as wired partitions.

Cord-and-plug connected freestanding partitions (605.9): individual partitions, or groups of interconnected partitions not exceeding 30 ft when assembled, may be connected to the building wiring by a single flexible cord and plug only if all of these are met:

the cord is extra-hard usage , 12 AWG or larger , with an insulated EGC, and not longer than 2 ft ;

the receptacle supplying it is on a separate circuit serving only panels, with no other loads, and is located not more than 12 in. from the partition it connects to;

the partitions contain not more than thirteen 15 A, 125 V receptacle outlets ; and

the partitions contain no multiwire circuits .

Partitions that are permanently connected to the building wiring use a Chapter 3 wiring method.

Information technology equipment rooms (Article 645)

Article 645 provides optional alternative wiring rules for an ITE room that meets all the conditions of 645.4 : a disconnecting means complying with 645.10; a dedicated HVAC system or one with fire and smoke dampers; listed information technology equipment; occupation only by personnel needed to operate and maintain the equipment; and separation from other occupancies by fire-resistant-rated walls, floors, and ceilings with protected openings.

Rule Requirement

Branch circuits (645.5) Conductors supplying one or more ITE units must have an ampacity of at least 125% of the total connected load

Power-supply cords ITE may be connected by listed cords; flexible cords and interconnecting cables run under a raised floor must be listed for the use

Under raised floors (645.5(E)) Branch circuits in raceways or listed cables, with the space under the floor accessible and used for wiring; ventilation of the underfloor area limited to the ITE room

Disconnecting means (645.10) Remote disconnect controls for the ITE and the dedicated HVAC systems, located at an approved location readily accessible at the principal exit doors; a single means may control both; critical operations data systems may use alternative arrangements

Grounding (645.15) All exposed non-current-carrying metal parts of the ITE system must be connected to an EGC, and signal reference structures bonded

Electrically driven or controlled irrigation machines (Article 675)

Center-pivot and lateral-move irrigation machines are common on Minnesota farms. Article 675 covers machines with electrically driven towers or electric controls.

Rule Requirement

Ratings (675.7) The machine's conductors and controller are sized from an equivalent continuous-current rating based on the motor loads and their duty cycle

Main controller and disconnect (675.8) A main controller, plus a main disconnecting means at the point where power connects to the machine, or within sight and not more than 50 ft from the machine; the disconnect must be readily accessible and lockable in the open position, with a horsepower rating at least equal to the equivalent rating

Grounding (675.12) The electrical equipment on the machine, its junction boxes, control panels, and motor enclosures must be connected to an EGC

Methods of grounding (675.13) A machine with a stationary point (center pivot) is grounded by an EGC run with the supply conductors and connected to an equipment grounding terminal at the stationary point

Bonding (675.14) The machine's metallic structure and metal conduit or cable sheaths are connected to the EGC; metal-to-metal contact with a part connected to the EGC is an acceptable bonding path

Lightning protection (675.15) Where the machine has a stationary point, a grounding electrode system (Article 250, Part III) is connected to the machine at the stationary point

Worked example: a retail tenant sign

A new retail tenant needs a 6 A LED channel-letter sign above its entrance.

The required sign outlet at the tenant entrance is on a 20 A circuit that supplies no other load.

The sign's disconnect is at the sign or within sight of it; if the switch is inside the store and out of sight, it must be lockable.

The LED power supplies mounted above a suspended ceiling must be fastened to the structure, not hung from the grid.