Study guide

19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

Minnesota Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Minnesota Exam, Licensing & Electrical Law

1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement

2 Electrical Theory, Math & Power Calculations

2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting

3 NEC Structure & General Requirements

3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)

4 Conductors, Identification & Ampacity

4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors

5 Branch Circuits, GFCI/AFCI & Required Outlets

5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)

6 Load Calculations (2026 NEC Article 120)

6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)

7 Feeders, Outside Wiring & Services

7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)

8 Overcurrent Protection

8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

9 System Grounding & Grounding Electrodes

9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems

10 Bonding & Equipment Grounding

10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding

11 General Wiring Methods & Underground Installations

11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)

12 Raceways, Cables & Conduit Fill

12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

13 Boxes, Conduit Bodies & Cabinets

13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)

14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances

14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)

15 Motors, Controllers & Air Conditioning

15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)

16 Transformers, Generators & Equipment Over 1000 Volts

16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

17 Hazardous (Classified) Locations

17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)

18 Health Care, Assembly, Agricultural & Mobile Occupancies

18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)

19 Signs, Elevators, Pools, Solar & Other Specific Equipment

19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

20 Emergency, Standby & Interconnected Power Sources

20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)

21 Limited-Energy, Fire Alarm & Communications Systems

21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)

Key Takeaways Explain This Topic AI

Fire pump OCPDs must be selected or set to carry indefinitely the sum of the locked-rotor currents of the fire pump and pressure maintenance motors plus the full-load current of the associated accessory equipment (Article 695).

Voltage at the fire pump controller line terminals may not drop more than 15% below normal when the motor starts, and voltage at the motor terminals may not drop more than 5% below the motor's rated voltage when running at 115% of full-load current (Article 695).

Each outlet installed to supply EVSE must be on an individual branch circuit with no other outlets, and EVSE is a continuous load sized at 125% (625.40 and 625.42).

Under the 2026 NEC 625.43(D), EVSE in other than one- and two-family dwellings needs an emergency shutoff readily accessible, within sight, and at least 20 ft but not more than 100 ft from the equipment.

Under the 2026 NEC 625.4, permanently installed electric vehicle power transfer equipment must be installed by qualified persons.

Last updated: October 2026

Small wind electric systems (Article 694)

Article 694 covers wind turbines of 100 kW or less that supply power to premises wiring, alone or with other sources.

Rule Requirement

Listing Wind turbines and associated equipment, such as inverters and charge controllers, must be listed or field evaluated

Disconnecting means A means to disconnect the turbine from all other conductors in the building, readily accessible , lockable, and marked; it may be the same as the inverter disconnect

Shutdown A manual means to stop the turbine (and a readily accessible shutdown switch for emergencies), since an open circuit alone can let a turbine overspeed

Surge protection A surge protective device between the wind electric system and the loads it serves

Towers Metal towers and guy wires must be grounded and bonded; tower conductors must be in raceways or suitable cables and supported

  • Interconnection Connection to other sources follows Article 705
  • Fire pumps (Article 695)

Fire pumps must keep running during a fire even if that damages the motor, so the usual protection rules are reversed.

Power sources and supervision

Reliable source: a separate service , an on-site power production facility, a dedicated feeder from a separate source, or a combination of sources as required.

Disconnecting means in the supply must be identified as suitable for service equipment, lockable in the closed position (or supervised), located sufficiently remote from other disconnects so inadvertent operation is unlikely, and marked "FIRE PUMP DISCONNECTING MEANS" in letters at least 1 in. high.

Overcurrent protection: OCPDs must be selected or set to carry indefinitely the sum of the locked-rotor currents of the fire pump motor(s) and pressure maintenance pump motor(s), plus 100% of the associated fire pump accessory equipment.

Meter sockets (230.68, 2026): a new exception lets the fire pump meter socket be sized to the circuit rating rather than the fire pump service current.

Conductors

Rule Requirement

Ampacity At least 125% of the sum of the fire pump motor and pressure maintenance motor full-load currents, plus 100% of the accessory loads

Routing Supply conductors run outside the building, or protected inside by encasement in at least 2 in. of concrete, a listed fire-resistive cable system, or a 2-hour fire-rated assembly. The 2026 NEC requires the 2 in. concrete encasement to also provide a 2-hour fire rating documented by a professional engineer, and adds a 5 in. concrete encasement option measured from the surface of the raceway or cable

Overload protection Power circuits may not have automatic protection against overloads ; the motor's protection is the controller's locked-rotor protection

  • GFPE Ground-fault protection of equipment is not permitted for fire pumps (Article 695 and 230.95)
  • Fire pump wiring Must be kept independent of all other wiring
  • Voltage drop

When the motor starts , the voltage at the fire pump controller line terminals may not drop more than 15% below normal.

When the motor runs at 115% of full-load current, the voltage at the motor terminals may not drop more than 5% below the motor's rated voltage.

  • Electric vehicle power transfer systems (Article 625)
  • Branch circuits and loads

Rule Requirement

Individual branch circuit (625.40) Each outlet installed for EVSE must be supplied by an individual branch circuit with no other outlets

Continuous load (625.41 and 625.42) EVSE is a continuous load ; the branch circuit and OCPD are sized at 125% of the maximum load; adjustable EVSE may be sized for its field-set rating, and a power control system may limit the load; the 2026 NEC clarifies that the service, feeder, and branch circuit must have a sufficient rating for the load served

Load calculation (120.57) 7,200 W (VA) or the nameplate rating, whichever is larger

GFCI (625.54) All receptacles installed for EV charging must be GFCI protected; the 2026 NEC adds GFCI and SPGFCI requirements for permanently wired equipment

Disconnecting means (625.43) EVSE rated more than 60 A or more than 150 V to ground needs a disconnecting means installed in a readily accessible location, lockable open

2026 NEC changes

625.4 Qualified persons: permanently installed EV power transfer system equipment, such as Level 2 chargers, must be installed by qualified persons . An Informational Note points to NECA 413.

625.5 Field markings: EVSE must have permanent field markings on the outside of the enclosure showing the supply voltage, number of phases, frequency, full-load current , and the short-circuit current rating , so the circuit sizing and fault rating can be checked before energizing.

625.43(D) Emergency shutoff: for other than one- and two-family dwellings, an emergency shutoff for EVSE must be readily accessible , located at least 20 ft and not more than 100 ft from the equipment and within sight of it, marked "EVSE EMERGENCY DISCONNECT" and "WARNING: ELECTRIC VEHICLES WILL REMAIN ENERGIZED," be manual reset, and open all phase conductors simultaneously. The equipment disconnect may serve if it meets these requirements.

625.44 Receptacles: cord-and-plug connected EVSE on 30 A, 50 A, or 60 A receptacles requires receptacles listed for EVSE use, because standard receptacles can overheat under long continuous loads.

Article 624 (new): electric self-propelled vehicles that are not "electric vehicles," such as forklifts, golf carts, airport ground equipment, construction machinery, lawnmowers, and electric boats, are covered by new Article 624.

Worked example: a Level 2 charger in a garage

A homeowner installs a hard-wired 48 A EVSE in an attached garage at 240 V.

Circuit: individual branch circuit, 125% of 48 A = 60 A ; 6 AWG copper (65 A at 75°C) on a 60 A breaker.

Disconnect: the EVSE is rated not more than 60 A and 150 V to ground, so 625.43 does not require a separate disconnecting means.

Installer: a qualified person, under the 2026 NEC 625.4; in Minnesota, a licensed electrician or the homeowner under the owner exemption, with a permit.

Load calculation: the EVSE nameplate is 48 × 240 = 11,520 48 \times 240 = 11{,}520 48 × 240 = 11 , 520 VA, which is larger than 7,200 VA, so the dwelling service calculation includes 11,520 VA (120.57).