21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725)
Minnesota Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Minnesota Exam, Licensing & Electrical Law
1.1 Exam Format, Provided References, Scoring & Scheduling 1.2 The Minnesota Electrical Act, Board of Electricity & Code Adoption 1.3 Personal Licenses, Scope of Work & Electrical Contractors 1.4 Experience Credit, Registration, Reciprocity, Renewal & Continuing Education 1.5 Direct Supervision, Ratios & Licensing Exemptions 1.6 Electrical Permits, Inspections, Condemnation & Enforcement
2 Electrical Theory, Math & Power Calculations
2.1 Exam Math, Ohm's Law, Watt's Law & Series/Parallel Circuits 2.2 AC Fundamentals: Reactance, Impedance & Power Factor 2.3 Three-Phase Systems: Wye vs. Delta Calculations 2.4 Voltage Drop Calculations & Chapter 9 Conductor Properties 2.5 Transformer Ratios, Connections, Taps & Available Fault Current 2.6 Motor Connections, Control Circuits & Troubleshooting
3 NEC Structure & General Requirements
3.1 Navigating the 2026 NEC: Article 90, Code Structure & Article 100 Definitions 3.2 NEC Article 110: Working Clearances, Dedicated Space & Termination Ratings 3.3 Over-1000-Volt Installations, Guarding & Manholes (Article 110, Parts III–V)
4 Conductors, Identification & Ampacity
4.1 Conductor Insulation Types, Copper vs. Aluminum & Table 310.16 Allowable Ampacities 4.2 Ampacity Derating: Ambient Temperature Correction & Raceway Bundling Adjustments 4.3 Conductor Identification, Splices & Parallel Conductors
5 Branch Circuits, GFCI/AFCI & Required Outlets
5.1 Branch Circuit Sizing, Overcurrent Ratings & Multiwire Branch Circuits 5.2 GFCI & AFCI Protection Requirements (NEC 210.8 & 210.12) 5.3 Dwelling Receptacle Outlets, Required Circuits & Lighting Outlets (NEC 210.11, 210.52, 210.63 & 210.70)
6 Load Calculations (2026 NEC Article 120)
6.1 Article 120 Basics: Dwelling Lighting, Small-Appliance & Laundry Loads 6.2 Dwelling Standard Method: Appliances, Dryers, Ranges, Heating, EVSE & Neutral 6.3 Optional Methods: Single Dwelling, Existing Dwelling & Multifamily (2026 NEC 120.82–120.85) 6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44) 6.5 Commercial Kitchens, Schools & Restaurants (2026 NEC 120.56, 120.86 & 120.88) 6.6 Farm Load Calculations (2026 NEC 120.102 & 120.103) 6.7 Feeder & Service Neutral Sizing (2026 NEC 120.61)
7 Feeders, Outside Wiring & Services
7.1 Feeder Design & Sizing Requirements (NEC Article 215) 7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32) 7.3 Service Clearances, Overhead Drops & Underground Service Laterals 7.4 Service Equipment, Disconnecting Means, Surge Protection & GFPE (2026 NEC Article 230)
8 Overcurrent Protection
8.1 Overcurrent Protective Devices: Fuses, Breakers & Standard Ampere Ratings 8.2 Conductor Overcurrent Protection & Feeder Tap Rules (NEC 240.4 & 240.21) 8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction
9 System Grounding & Grounding Electrodes
9.1 Grounding vs. Bonding Principles & System Grounding (NEC Article 250 Parts I-II) 9.2 Grounding Electrode System: Permitted Electrodes & Installation (NEC 250.50 & 250.52) 9.3 Grounding Electrode Conductor (GEC) Sizing & Protection (NEC Table 250.66) 9.4 Main Bonding Jumper, System Bonding Jumper & Separately Derived Systems
10 Bonding & Equipment Grounding
10.1 Equipment Grounding Conductor (EGC) Types, Identification & Sizing (NEC Table 250.122) 10.2 Proportional Upsizing of EGC for Voltage Drop (NEC 250.122(B)) 10.3 Bonding of Interior Metal Piping, Structural Steel & Other Systems (NEC 250.104) 10.4 Bonding Methods, Equipment Requiring Grounding & Receptacle Grounding
11 General Wiring Methods & Underground Installations
11.1 General Wiring Methods & Mechanical Protection (NEC Article 300) 11.2 Underground Wiring Cover Requirements (NEC Table 300.7) 11.3 Securing & Supporting, Plenums, Firestopping & Raceway Installation (Article 300)
12 Raceways, Cables & Conduit Fill
12.1 Metal (RMC, IMC, EMT) & Nonmetallic (PVC, RTRC, LFNC) Raceways 12.2 Flexible Conduits, ENT, Wireways, Auxiliary Gutters & Surface Raceways 12.3 Busways & Cable Tray Systems (Articles 368 & 392) 12.4 Cable Assemblies (NM, UF, MC) & Minnesota Cold-Weather Installation Rules 12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
13 Boxes, Conduit Bodies & Cabinets
13.1 Box Installation, Support, Accessibility & Luminaire and Fan Boxes (Article 314) 13.2 Outlet, Switch & Junction Box Fill Calculations (NEC 314.16) 13.3 Pull and Junction Box Sizing for Conductors 4 AWG & Larger (NEC 314.28) 13.4 Cabinets, Cutout Boxes & Wire Bending Space (NEC Article 312)
14 Cords, Wiring Devices, Panelboards, Luminaires & Appliances
14.1 Flexible Cords, Flexible Cables & Fixture Wires (Articles 400 & 402) 14.2 Switches, Receptacles & Wiring Devices (Articles 404 & 406) 14.3 Panelboards, Switchboards & Switchgear (NEC Article 408) 14.4 Luminaires, Lampholders, Lighting Track & Low-Voltage Lighting (Articles 410 & 411) 14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
15 Motors, Controllers & Air Conditioning
15.1 Motor Full-Load Current Determination & Conductor Sizing (NEC 430.6 & 430.22) 15.2 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Table 430.52) 15.3 Motor Overload Protection & Feeder Calculations for Multiple Motors (NEC 430.32 & 430.24) 15.4 Motor Controllers, Disconnecting Means, Drives & Motor Control Centers (Article 430 Parts VII–XI) 15.5 Air Conditioning & Refrigeration Equipment (NEC Article 440)
16 Transformers, Generators & Equipment Over 1000 Volts
16.1 Transformer Overcurrent Protection & Sizing (NEC Article 450) 16.2 Generators & Transfer Switches (NEC Article 445) 16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)
17 Hazardous (Classified) Locations
17.1 Hazardous (Classified) Locations: Classes, Divisions & Zones (NEC Articles 500-506) 17.2 Class I Locations: Wiring Methods & Conduit Seal-Offs (NEC Article 501) 17.3 Class II & Class III Locations and the Zone System (Articles 502, 503, 505 & 506) 17.4 Commercial Garages & Motor Fuel Dispensing Facilities (NEC Articles 511 & 514) 17.5 Spray Areas, Aircraft Hangars, Hazardous-Location Bonding & Intrinsic Safety (Articles 500, 504, 513 & 516)
18 Health Care, Assembly, Agricultural & Mobile Occupancies
18.1 Health Care Facilities: Patient Care Spaces & Redundant Grounding (NEC Article 517) 18.2 Places of Assembly, Carnivals & Fairs, and Temporary Installations (Articles 518, 525 & 590) 18.3 Agricultural Buildings, Equipotential Planes & Farm Distribution Points (Article 547) 18.4 Mobile & Manufactured Homes, RV Parks, and Marinas & Docks (Articles 550, 551 & 555)
19 Signs, Elevators, Pools, Solar & Other Specific Equipment
19.1 Signs & Outline Lighting, Office Partitions, IT Rooms & Irrigation Machines (Articles 600, 605, 645 & 675) 19.2 Elevators, Escalators & Platform Lifts (Article 620) 19.3 Swimming Pools, Spas & Water Features: Equipotential Bonding & GFCI (NEC Article 680) 19.4 Spas, Hot Tubs, Hydromassage Bathtubs, Fountains & Natural Bodies of Water (Article 680 Parts IV–VII & Article 682) 19.5 Solar Photovoltaic Systems (Article 690) 19.6 Small Wind Systems, Fire Pumps & Electric Vehicle Charging (Articles 694, 695 & 625)
20 Emergency, Standby & Interconnected Power Sources
20.1 Emergency Systems vs. Legally Required vs. Optional Standby (NEC Articles 700, 701, 702) 20.2 Interconnected Power Sources, Energy Storage & Power Control Systems (Articles 705, 706, 480 & 130)
21 Limited-Energy, Fire Alarm & Communications Systems
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725) 21.2 Class 4 Fault-Managed Power, Tray Cables, Fire-Resistive Cable Systems & Limited-Energy Grounding (Articles 726, 727, 742, 750 & 772) 21.3 Fire Alarm Systems: NPLFA vs. PLFA Wiring & Overcurrent Protection (NEC Article 760) 21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)
21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725)
Key Takeaways Explain This Topic AI
In the 2026 NEC, general rules for limited-energy wiring methods are in Article 720, power sources in 721, cables in 722, and raceways and cable trays in 723, while Class 2 and 3 circuit rules are in Article 725.
Class 2 and Class 3 circuits must be supplied by a listed power source, such as a Class 2 transformer or power supply marked for the class.
Class 2 and 3 conductors may not share a raceway, cable, enclosure, or cable tray with electric light, power, Class 1, or nonpower-limited fire alarm conductors unless separated by a barrier or a permitted exception applies.
Accessible portions of abandoned Class 2 and Class 3 cables must be removed, unless tagged for future use.
Remote-control circuits for safety-control equipment are classified as Class 1 when their failure would introduce a direct fire or life hazard; room thermostats for household heating and cooling are not safety-control equipment.
Last updated: October 2026
The 2026 reorganization
DLI's knowledge areas list Class 1, 2, and 3 remote-control, signaling, and power-limited circuits and the general requirements for limited-energy system wiring methods . The 2026 NEC moved these rules into a new structure so the same requirements are not repeated in every article:
- Article Covers
- 206 Non-power-limited remote-control and signaling circuits (formerly Class 1 non-power-limited)
- 720 General requirements for limited-energy system wiring methods and materials
- 721 Power sources for limited-energy systems
- 722 Limited-energy cables: listing, marking, and permitted uses and substitutions
- 723 Raceways, cable routing assemblies, and cable trays for limited-energy systems
- 724 Class 1 power-limited circuits
- 725 Class 2 and Class 3 power-limited circuits
- 742 Overvoltage protection of limited-energy systems
- 750 Grounding and bonding of limited-energy systems
Chapter 8 now covers only communications circuits outside and entering buildings; inside the building, communications wiring follows the Chapter 7 limited-energy rules.
Circuit classes
Class What limits it Typical uses
Class 1 non-power-limited (Article 206) Ordinary OCPDs; up to 600 V Motor control circuits, relay coils, interlocks
Class 1 power-limited (Article 724) Source limited to 30 V and 1000 VA Some control circuits
Class 2 (Article 725) Listed power source limits voltage and power, so the circuit is safe from fire and, at lower voltages, from shock Thermostats, doorbells, security, low-voltage lighting controls, PoE
Class 3 (Article 725) Listed source with higher voltage limits than Class 2; safe from fire but may present a shock hazard Some sound systems, nurse call, certain controls
Class 1 rules
Conductors: 18 AWG and 16 AWG Class 1 conductors are permitted where protected at 7 A and 10 A ; larger conductors follow Table 310.16 and 240.4.
Same raceway with power: Class 1 circuit conductors may share a raceway or enclosure with power-supply conductors only where functionally associated with the equipment they supply.
Safety-control circuits: remote-control circuits for safety-control equipment are Class 1 where failure of the equipment to operate would introduce a direct fire or life hazard . Where physical damage to such circuits would create a hazard, all their conductors must be in RMC, IMC, PVC, EMT, Type MI or MC cable, or otherwise protected. Room thermostats, water temperature regulators, and similar household heating and air-conditioning controls are not safety-control equipment.
- Class 2 and Class 3 circuits
- Power sources (Article 721)
A Class 2 or Class 3 circuit must be supplied by a listed power source: a Class 2 or 3 transformer, a Class 2 or 3 power supply, other listed equipment marked to identify the Class 2 or 3 power source, listed ITE equipment, or a dry-cell battery for Class 2. The outputs of Class 2 and 3 power sources may not be paralleled or otherwise interconnected unless listed for that use, because combining them can exceed the class limits.
Power source limits (Chapter 9, Tables 11(A) and 11(B))
Chapter 9 Table 11(A) (ac) and Table 11(B) (dc) set the maximum voltage, current, and power for Class 2 and Class 3 power sources. Each table has two halves: inherently limited sources, which need no overcurrent protection, and sources not inherently limited , which require overcurrent protection. Two values are worth remembering: an inherently limited Class 2 ac source over 20 V and up to 30 V has a maximum nameplate rating of 100 VA , and an inherently limited Class 3 ac source over 30 V and up to 100 V is also limited to 100 VA . Equipment listed and marked as Class 2 or Class 3 already meets these limits, so in the field you verify the marking rather than calculating.
Separation from other systems
Class 2 and 3 conductors may not be placed in any raceway, cable, compartment, outlet box, junction box, or cable tray with conductors of electric light, power, Class 1, nonpower-limited fire alarm , or medium-power network-powered broadband circuits, unless separated by a barrier or the Code specifically permits it.
In enclosures where power conductors enter only to connect to the same equipment, Class 2 and 3 conductors must keep at least ¼ in. of separation or be routed to avoid the power conductors.
In other installations, such as open wiring in a building, Class 2 and 3 conductors must be kept at least 2 in. from power, Class 1, and NPLFA conductors, unless the power conductors are in raceway or in metal-sheathed, metal-clad, nonmetallic-sheathed, Type TC, or Type UF cable, or the Class 2 and 3 conductors are in raceway.
Class 2 and Class 3 circuits may share a cable or raceway with each other where the Class 2 conductors are insulated for Class 3 use, and with communications and power-limited fire alarm circuits where permitted.
Cable types and substitutions (Article 722)
- Space Class 2 / Class 3 cable May substitute
- Plenums and other spaces for environmental air CL2P / CL3P CMP (and CL3P for CL2P)
- Risers CL2R / CL3R Plenum types above, CMR, and CL3R for CL2R
- General use CL2 / CL3 Any of the above, CM (CMG), PLTC, and CL3 for CL2
- Limited use (dwellings, raceways, and short exposed lengths) CL2X / CL3X Any of the above, and CMX
Class 3 cable may substitute for Class 2 cable, and a higher-rated cable (plenum over riser over general purpose) may always substitute for a lower-rated one, never the reverse.
Power over Ethernet and other power on data cable
Class 2 and Class 3 circuits that carry power over communications cables, such as PoE to cameras, access points, and LED luminaires, have ampacity limits that depend on conductor size, temperature rating, and bundle size. For larger bundles and higher power levels, use cables marked "-LP" (limited power) with the marked current rating, or the ampacity table for the bundle size.
Installation rules (Article 720 and Article 300)
Access to equipment (formerly 725.21): cables and equipment may not be installed in a way that prevents removal of panels, including suspended ceiling panels , needed to reach electrical equipment.
Workmanship and support (formerly 725.24): cables must be installed in a neat and workmanlike manner, supported by the building structure with straps, staples, hangers, or cable ties listed and identified for securement and support , and not damaged. They may not be supported by ceiling grids or ceiling-support wires, or strapped to the outside of raceways (except Class 2 cables supported by a raceway that supplies power to the equipment they control).
Penetrations: openings through fire-resistant-rated walls, floors, and ceilings must be firestopped .
Abandoned cables (formerly 725.25): the accessible portion of abandoned Class 2, Class 3, and PLTC cables must be removed . Cables identified for future use with a tag of sufficient durability are not considered abandoned.
Worked example: a commercial ceiling
A security contractor runs CL2 cable above a suspended ceiling used as a return-air plenum.
Cable type: the space is a plenum, so the cable must be CL2P (or a permitted substitute such as CMP or CL3P).
Support: fasten the cable to the structure with listed supports or J-hooks; do not lay it on the ceiling tiles or tie it to grid wires.
Separation: do not pull the CL2P cable into the same raceway or box as 120 V lighting conductors.
Old cable: remove the accessible portions of the abandoned alarm cable that the new system replaced, or tag any cable kept for future use.