Study guide
13.3 Electrical Safety, Arc Flash, and NFPA 70E
NABCEP PV Installation Professional PVIP
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
About the NABCEP PVIP Exam Using the 2017 NEC on Exam Day
2 Chapter 1: Solar Resource & Site Assessment
1.1 Sun Position, Irradiance, and Insolation 1.2 Site Survey and Roof Condition Assessment 1.3 Shading Analysis and Solar Access 1.4 Array Layout and Fire Code Setbacks
3 Chapter 2: Photovoltaic Modules & Cell Technology
2.1 PV Cell Technologies and Manufacturing 2.2 Electrical Performance Characteristics & I-V Curves 2.3 Module Degradation, Testing Standards, and Warranties
4 Chapter 3: Inverters & System Architectures
3.1 Inverter Types and Topologies 3.2 Inverter Efficiency, Features, and Grid Interaction 3.3 System Configurations: Grid-Direct vs Stand-Alone 3.4 Hybrid and AC-Coupled vs DC-Coupled Architectures
5 Chapter 4: Mechanical Mounting & Roofing Systems
4.1 Sloped Roof Mounting and Flashing Methods 4.2 Low-Slope Ballasted and Penetrating Systems 4.3 Ground Mounts and Tracking Systems
6 Chapter 5: Structural Loading & Mechanical Assembly
5.1 Structural Load Calculations and Engineering 5.2 Mechanical Assembly and Hardware Specifications 5.3 Wire Management and Array Mechanical Protection
7 Chapter 6: Electrical Calculations & Sizing
6.1 Maximum System Voltage and Temperature Calculations 6.2 Maximum Circuit Current and Overcurrent Protection 6.3 Conductor Sizing and Ampacity Derating 6.4 Voltage Drop Analysis and Sizing in PV Systems
8 Chapter 7: Electrical Equipment & Safety Disconnects
7.1 PV Disconnecting Means and Isolation 7.2 Wiring Methods, Raceways, and Connectors 7.3 Combiner Boxes and DC Balance of System 7.4 Monitoring, Controls, and Communications
9 Chapter 8: Grounding, Bonding & Fire Safety
8.1 Equipment Grounding and System Bonding 8.2 Ground-Fault Protection and Arc-Fault Interrupters 8.3 Rapid Shutdown Systems
10 Chapter 9: Utility Interconnection & Grid Integration
9.1 Utility Interconnection Standards & Permitting 9.2 Load-Side Interconnection and the 120% Rule 9.3 Supply-Side Interconnection and Alternative Connections
11 Chapter 10: Energy Storage Systems (ESS)
10.1 Battery Chemistries, Characteristics, and Ratings 10.2 Energy Storage System Sizing and Autonomy 10.3 NEC Article 706 and Electrical Storage Rules 10.4 ESS Safety Standards, NFPA 855, and Fire Codes
12 Chapter 11: System Commissioning & Acceptance Testing
11.1 Visual Inspection and Pre-Power Verification 11.2 Voltage and Current Commissioning Tests 11.3 Insulation Resistance Testing and Megohmmeter Procedures 11.4 I-V Curve Tracing and Performance Analysis
13 Chapter 12: Operations, Maintenance & Troubleshooting
12.1 Preventive Maintenance and Monitoring 12.2 Thermal Imaging and Infrared Inspection 12.3 Electrical Fault Troubleshooting and Diagnostics 12.4 Corrective Maintenance and Component Replacement
14 Chapter 13: Workplace Safety, OSHA & NFPA 70E
13.1 OSHA Regulations and Personal Protective Equipment 13.2 Fall Protection Systems and Ladder Safety 13.3 Electrical Safety, Arc Flash, and NFPA 70E 13.4 Lockout/Tagout (LOTO) and Hazardous Energy Control
15 Chapter 14: Project Management, Codes & Documentation
14.1 AHJ Permitting, Building Codes, and Plan Sets 14.2 System Labeling and Signage Requirements 14.3 Project Closeout, Commissioning Reports, and PTO 14.4 Customer Expectations, Value Engineering, and Design Adaptation
13.3 Electrical Safety, Arc Flash, and NFPA 70E
Key Takeaways Explain This Topic AI
NFPA 70E mandates establishing an Electrically Safe Work Condition (ESWC) through positive disconnection, lockout/tagout, and testing for absence of voltage prior to beginning work on electrical systems.
Shock hazard approach boundaries define mandatory protection zones: the Limited Approach Boundary prevents unqualified access, while the Restricted Approach Boundary allows entry only by qualified persons wearing voltage-rated PPE and using insulated tools.
Insulated hand tools must comply with ASTM F1505 and IEC 60900, rated for 1,000 Vac and 1,500 Vdc, featuring dual-color contrasting insulation layers to visually indicate structural insulation compromise.
Arc flash risk assessments establish the Arc Flash Boundary where incident energy equals 1.2 cal/cm², mandating Arc Flash PPE Categories (Category 1 through 4) based on calculated thermal exposure.
Last updated: October 2026
Electrical Safety, Arc Flash, and NFPA 70E
Solar photovoltaic installations present a dual electrical environment: high-voltage direct-current (DC) array circuits operating at 600 V d c 600\text{ V}_{dc} 600 V d c , 1 , 000 V d c 1,000\text{ V}_{dc} 1 , 000 V d c , or 1 , 500 V d c 1,500\text{ V}_{dc} 1 , 500 V d c operating alongside commercial alternating-current (AC) utility service entrances operating at 208 V a c 208\text{ V}_{ac} 208 V a c , 240 V a c 240\text{ V}_{ac} 240 V a c , or 480 V a c 480\text{ V}_{ac} 480 V a c . Electrical safety standards across this dual domain are established by NFPA 70E ( Standard for Electrical Safety in the Workplace ) and OSHA 29 CFR 1910 Subpart S / 1926 Subpart K. Technicians must understand the physical behaviors of AC and DC electrical faults, master the protocol for establishing an Electrically Safe Work Condition, observe approach boundaries, utilize certified insulated hand tools, and wear appropriate arc-rated PPE.
1. NFPA 70E Framework and Establishing an Electrically Safe Work Condition (ESWC)
The fundamental premise of NFPA 70E is that electrical conductors and circuit parts must be placed into an Electrically Safe Work Condition (ESWC) before any employee performs work within the Limited Approach Boundary, unless the employer can demonstrate that de-energizing introduces additional or increased hazards (e.g., deactivating ventilation systems in toxic atmospheres) or is infeasible due to equipment design or operational limitations (e.g., live diagnostic testing, voltage measurements, thermal imaging, and phase rotation checks).
The Eight-Step ESWC Process (NFPA 70E 120.5 in 2018; 120.6 in 2021 and 2024)
Determine All Sources: Review up-to-date single-line diagrams, schematics, and manuals to identify every source of electrical energy feeding the equipment (utility feeds, dc string combiners, energy storage, auxiliary control power).
Interrupt Load Current, Then Open the Disconnects: Shut down the load (for an inverter, through its controls) and open the disconnecting device for each source.
Visually Verify the Open Point: Wherever possible, confirm that all blades of disconnect switches are fully open or that drawout breakers are withdrawn to the fully disconnected position.
Release Stored Electrical Energy: Allow inverter dc bus capacitors to discharge through their bleed resistors (or discharge them with proper equipment), and isolate battery strings.
Block or Relieve Stored Nonelectrical Energy: Pin tracker drives, release spring or hydraulic energy, and secure anything that could move.
Apply Lockout/Tagout Devices: Apply locks and tags per the employer's documented energy control procedure.
Test for Absence of Voltage: Using an adequately rated portable test instrument, test each phase conductor or circuit part phase-to-phase and phase-to-ground, verifying the instrument on a known source before and after the test.
Ground If Needed: Where induced voltages or stored electrical energy could be present, apply temporary protective grounding equipment rated for the available fault current.
The Live-Dead-Live Three-Point Test Method
Technicians must never assume a circuit is dead simply because a switch handle is in the open position. Switch linkages can snap internally, leaving contacts welded closed while the external handle displays "OFF". To verify absence of voltage safely, technicians must execute the Live-Dead-Live verification sequence:
Live Check #1: Check the digital multimeter on a known energized voltage source (or an approved portable proving unit) to verify the meter, internal fuse, and test leads are functioning properly.
Dead Check: Test the de-energized target equipment across all combinations: phase-to-phase (L1-L2, L2-L3, L1-L3), phase-to-neutral, and phase-to-ground on AC circuits; and positive-to-negative, positive-to-ground, and negative-to-ground on DC circuits. All readings must register zero voltage ( 0.0 V 0.0\text{ V} 0.0 V ).
Live Check #2: Immediately re-test the multimeter on the known energized source or proving unit to confirm the test instrument did not fail during the test sequence.
Note on Non-Contact Voltage Testers: Inductive non-contact "voltage pens" or "tic tracers" operate by sensing alternating electrostatic fields; they are completely incapable of detecting direct current (DC) voltage and are strictly prohibited by NFPA 70E for verifying the absence of voltage.
2. Shock Hazard Approach Boundaries (AC and DC)
NFPA 70E defines shock hazard approach boundaries around exposed energized electrical conductors to safeguard personnel based on system voltage and conductor mobility:
Boundary Definitions
Limited Approach Boundary: An approach limit at a distance from an exposed energized electrical conductor or circuit part within which a shock hazard exists. Unqualified persons are prohibited from entering unless continuously escorted by a qualified person and wearing appropriate PPE.
Restricted Approach Boundary: An approach limit at a distance from an exposed energized electrical conductor or circuit part within which there is an increased likelihood of electric shock due to electrical arc-over combined with inadvertent movement. Only qualified persons wearing rated insulating PPE and utilizing insulated tools are permitted within this boundary.
Standard Approach Boundaries (NFPA 70E Table 130.4(E)(a) AC & Table 130.4(E)(b) DC)
System Type & Nominal Voltage Range Limited Approach Boundary (Exposed Movable Conductor) Limited Approach Boundary (Exposed Fixed Circuit Part) Restricted Approach Boundary (Includes Inadvertent Movement Adder)
AC: 50 V − 150 V 50\text{ V} - 150\text{ V} 50 V − 150 V (120 V circuits) 10 ft 0 in 10\text{ ft } 0\text{ in} 10 ft 0 in ( 3.0 m 3.0\text{ m} 3.0 m ) 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) Avoid Contact
AC: 151 V − 750 V 151\text{ V} - 750\text{ V} 151 V − 750 V (208 V, 240 V, and 480 V systems) 10 ft 0 in 10\text{ ft } 0\text{ in} 10 ft 0 in ( 3.0 m 3.0\text{ m} 3.0 m ) 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) 1 ft 0 in 1\text{ ft } 0\text{ in} 1 ft 0 in ( 0.3 m 0.3\text{ m} 0.3 m )
AC: 751 V − 15 kV 751\text{ V} - 15\text{ kV} 751 V − 15 kV (Medium-Voltage Interconnection) 10 ft 0 in 10\text{ ft } 0\text{ in} 10 ft 0 in ( 3.0 m 3.0\text{ m} 3.0 m ) 5 ft 0 in 5\text{ ft } 0\text{ in} 5 ft 0 in ( 1.5 m 1.5\text{ m} 1.5 m ) 2 ft 2 in 2\text{ ft } 2\text{ in} 2 ft 2 in ( 0.7 m 0.7\text{ m} 0.7 m )
DC: 100 V − 300 V 100\text{ V} - 300\text{ V} 100 V − 300 V (Low-Voltage DC Strings) 10 ft 0 in 10\text{ ft } 0\text{ in} 10 ft 0 in ( 3.0 m 3.0\text{ m} 3.0 m ) 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) Avoid Contact
DC: 301 V − 1 , 000 V 301\text{ V} - 1,000\text{ V} 301 V − 1 , 000 V (Commercial 1000V DC Systems) 10 ft 0 in 10\text{ ft } 0\text{ in} 10 ft 0 in ( 3.0 m 3.0\text{ m} 3.0 m ) 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) 1 ft 0 in 1\text{ ft } 0\text{ in} 1 ft 0 in ( 0.3 m 0.3\text{ m} 0.3 m )
DC: 1 , 001 V − 1 , 500 V 1,001\text{ V} - 1,500\text{ V} 1 , 001 V − 1 , 500 V (Utility-Scale Solar Power Plants) 10 ft 0 in 10\text{ ft } 0\text{ in} 10 ft 0 in ( 3.0 m 3.0\text{ m} 3.0 m ) 5 ft 0 in 5\text{ ft } 0\text{ in} 5 ft 0 in ( 1.5 m 1.5\text{ m} 1.5 m ) 1 ft 5 in 1\text{ ft } 5\text{ in} 1 ft 5 in ( 0.43 m 0.43\text{ m} 0.43 m )
Rule on Enclosure Doors: When an electrical enclosure door is closed, latched, and bolted, the approach boundaries do not apply. The moment an authorized technician unlatches and opens an enclosure door exposing energized terminals (such as a live combiner box or inverter terminal compartment), the Limited and Restricted approach boundaries project outward into the workspace.
3. Insulated Hand Tools (ASTM F1505 / IEC 60900)
When a qualified technician performs work inside the Restricted Approach Boundary (e.g., torquing live DC combiner lugs, replacing string fuses, or testing terminal blocks), OSHA 1910.335 and NFPA 70E mandate the use of insulated hand tools conforming to ASTM F1505 ( Standard Specification for Insulated and Insulating Hand Tools ) and IEC 60900 :
Dielectric Voltage Ratings: Certified insulated tools are proof-tested in a water bath at 10 , 000 V a c 10,000\text{ V}_{ac} 10 , 000 V a c and officially rated for continuous operation up to 1 , 000 V a c 1,000\text{ V}_{ac} 1 , 000 V a c and 1 , 500 V d c 1,500\text{ V}_{dc} 1 , 500 V d c . Compliant tools are permanently laser-etched with the international double-triangle symbol and " 1000 V 1000\text{V} 1000 V ".
Dual-Layer Insulation Technology: High-grade insulated tools feature two contrasting colored layers of insulating elastomer: an outer flame-retardant impact layer (typically safety orange or red) over an inner high-dielectric indicator layer (typically bright yellow or white). If the tool is dropped, gouged, or abraded such that the yellow indicator layer becomes visible through the outer orange jacket, the tool's dielectric integrity is broken. The tool must be removed from service immediately and destroyed.
Prohibited Tooling: Mechanics' chrome-vanadium sockets, bare steel screwdrivers, slip-joint pliers, and hand tools with aftermarket dipped vinyl "cushion grips" provide zero certified dielectric protection. Dropping an uninsulated wrench across energized busbars instantly triggers an explosive phase-to-phase arc flash.
- 4. Arc Flash Hazards, Incident Energy, and NFPA 70E PPE Categories
- The Physics of Arc Flash and Arc Blast
An electric arc flash is an explosive short-circuit release of thermal and acoustic energy traveling through ionized air:
Extreme Thermal Energy: The arc plasma temperature reaches 35 , 000 ∘ F 35,000^\circ\text{F} 35 , 00 0 ∘ F ( 19 , 400 ∘ C 19,400^\circ\text{C} 19 , 40 0 ∘ C ) —four times hotter than the surface of the sun. Radiant heat incinerates non-arc-rated clothing instantly, welding synthetic polyester or nylon fibers directly into human flesh.
Volumetric Arc Blast: As solid copper busbars vaporize into gas, copper expands 67,000 times in volume . This instantaneous volumetric expansion generates a supersonic explosive pressure wave (the arc blast ) exceeding 2 , 000 lbs/ft 2 2,000\text{ lbs/ft}^2 2 , 000 lbs/ft 2 ( 100 kPa 100\text{ kPa} 100 kPa ), launching molten shrapnel, rupturing technician eardrums (sound pressure > 140 dB >140\text{ dB} > 140 dB ), and collapsing human lungs.
The Arc Flash Boundary
The Arc Flash Boundary is defined by NFPA 70E as the distance from exposed energized parts where incident energy drops to 1.2 cal/cm 2 1.2\text{ cal/cm}^2 1.2 cal/cm 2 ( 5.0 J/cm 2 5.0\text{ J/cm}^2 5.0 J/cm 2 ) . An incident energy of 1.2 cal/cm 2 1.2\text{ cal/cm}^2 1.2 cal/cm 2 represents the threshold of thermal exposure that causes the onset of a second-degree (curable) burn on unprotected bare human skin. Anyone crossing inside the Arc Flash Boundary must wear certified arc-rated PPE.
NFPA 70E Arc Flash PPE Categories
When an incident energy analysis has not been performed, technicians may utilize the NFPA 70E PPE Category Method (provided system fault current and clearing times are within table limits):
PPE Category Minimum Arc Rating ( c a l / c m 2 cal/cm^2 c a l / c m 2 ) Required Arc-Rated Clothing & Head Protection Required Hand, Eye & Foot Protection
Category 1 4 cal/cm 2 4\text{ cal/cm}^2 4 cal/cm 2 Arc-rated long-sleeve shirt and pants (or coverall) rated ≥ 4 cal/cm 2 \ge 4\text{ cal/cm}^2 ≥ 4 cal/cm 2 ; arc-rated face shield or hood ANSI Z87+ safety glasses; ear canal inserts; heavy-duty leather work gloves; leather footwear
Category 2 8 cal/cm 2 8\text{ cal/cm}^2 8 cal/cm 2 Arc-rated shirt and pants (or coverall) rated ≥ 8 cal/cm 2 \ge 8\text{ cal/cm}^2 ≥ 8 cal/cm 2 ; arc-rated balaclava paired with arc-rated face shield (or hood) ANSI Z87+ safety glasses; ear canal inserts; ASTM D120 rubber gloves with leather protectors; leather footwear
Category 3 25 cal/cm 2 25\text{ cal/cm}^2 25 cal/cm 2 Arc-rated flash suit jacket and pants rated ≥ 25 cal/cm 2 \ge 25\text{ cal/cm}^2 ≥ 25 cal/cm 2 ; arc-rated flash suit hood ANSI Z87+ safety glasses; ear canal inserts; ASTM D120 rubber gloves with leather protectors; leather footwear
Category 4 40 cal/cm 2 40\text{ cal/cm}^2 40 cal/cm 2 Arc-rated flash suit jacket and pants rated ≥ 40 cal/cm 2 \ge 40\text{ cal/cm}^2 ≥ 40 cal/cm 2 ; arc-rated flash suit hood ANSI Z87+ safety glasses; ear canal inserts; ASTM D120 rubber gloves with leather protectors; leather footwear
Direct Current (DC) Arc Flash Dynamics in Solar and Energy Storage
In AC power systems, alternating current naturally passes through zero voltage 120 times every second (at 60 Hz 60\text{ Hz} 60 Hz ), assisting circuit breakers in quenching arcs. In direct current (DC) systems, there is zero natural current-crossing . Once established, a DC arc is continuous, highly stable, and self-sustaining across wide air gaps. In commercial PV combiner boxes and battery energy storage systems (BESS), massive parallel DC currents and battery banks capable of tens of thousands of amperes of short-circuit current create extreme arc flash hazards that persist until overcurrent protective devices fully clear the circuit.
- 5. Qualified Person vs. Unqualified Person and Job Safety Analysis (JSA)
- Qualified Person Definition (NFPA 70E / OSHA 1910.399)
A Qualified Person is officially defined as:
"One who has demonstrated skills and knowledge related to the construction and operation of electrical equipment and installations and has received safety training to identify and avoid the electrical hazards involved."
To be deemed qualified to perform live electrical diagnostic testing on solar equipment, a technician must have verifiable training in:
Distinguishing exposed energized electrical parts from de-energized components.
Determining the nominal system voltage of AC and DC circuits.
Understanding and calculating Limited, Restricted, and Arc Flash approach boundaries.
Selecting, inspecting, and donning appropriate voltage-rated rubber gloves, arc-rated face shields, and ASTM F1505 insulated tools.
Executing the Live-Dead-Live three-point test method.
Performing emergency release protocols and certified Cardiopulmonary Resuscitation (CPR) and Automated External Defibrillator (AED) administration.
An Unqualified Person is any individual lacking these verified electrical skills. Unqualified personnel must remain strictly outside the Limited Approach Boundary unless continuously escorted by a qualified person and equipped with suitable PPE.
Job Safety Analysis (JSA) and Pre-Work Toolbox Briefing
Prior to commencing any electrical installation, commissioning, or troubleshooting task, the qualified person in charge must conduct a documented Job Safety Analysis (JSA) and pre-work briefing with the entire crew:
Task Scope & Energy Status: Identify the specific electrical circuits to be serviced and whether the task involves energized diagnostic testing or de-energized maintenance.
Hazard Identification: Review shock approach boundaries and calculate the arc flash boundary based on available fault current.
PPE Verification: Physically audit each technician's PPE, ensuring glove dielectric test stamps are valid within 6 months and arc-rated clothing meets or exceeds required incident energy ratings.
Emergency Protocols: Designate the exact physical location of emergency disconnect switches, verify cell phone emergency signal coverage, designate the primary first-aid and CPR/AED responders, and identify the nearest emergency medical trauma facility.
6. Electrical Safety, Approach Boundaries, and Tool Standards Matrix
The following matrix summarizes the boundary thresholds, tool certifications, and PPE requirements across typical solar installation operating voltages:
Operating Voltage Subsystem Limited Approach Boundary Restricted Approach Boundary Arc Flash Boundary (Typical) Minimum Tool Specification Minimum Mandatory Electrical PPE
120/240V AC Residential Output 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) 1 ft 0 in 1\text{ ft } 0\text{ in} 1 ft 0 in ( 0.3 m 0.3\text{ m} 0.3 m ) Calculated per label (typically 1 − 3 ft 1-3\text{ ft} 1 − 3 ft ) ASTM F1505 rated 1 , 000 V a c 1,000\text{ V}_{ac} 1 , 000 V a c Category 1 or 2 ( 4 − 8 cal/cm 2 4-8\text{ cal/cm}^2 4 − 8 cal/cm 2 ); Class 00 gloves
480V AC Commercial Switchgear 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) 1 ft 0 in 1\text{ ft } 0\text{ in} 1 ft 0 in ( 0.3 m 0.3\text{ m} 0.3 m ) Calculated per label (typically 4 − 10 ft 4-10\text{ ft} 4 − 10 ft ) ASTM F1505 rated 1 , 000 V a c 1,000\text{ V}_{ac} 1 , 000 V a c Category 2 or 4 ( 8 − 40 cal/cm 2 8-40\text{ cal/cm}^2 8 − 40 cal/cm 2 ); Class 0 gloves
600V DC Residential String Circuits 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) 1 ft 0 in 1\text{ ft } 0\text{ in} 1 ft 0 in ( 0.3 m 0.3\text{ m} 0.3 m ) Calculated per label (typically 2 − 4 ft 2-4\text{ ft} 2 − 4 ft ) ASTM F1505 rated 1 , 500 V d c 1,500\text{ V}_{dc} 1 , 500 V d c Category 2 ( 8 cal/cm 2 8\text{ cal/cm}^2 8 cal/cm 2 ); Class 00 or 0 gloves
1000V DC Commercial PV Arrays 3 ft 6 in 3\text{ ft } 6\text{ in} 3 ft 6 in ( 1.0 m 1.0\text{ m} 1.0 m ) 1 ft 0 in 1\text{ ft } 0\text{ in} 1 ft 0 in ( 0.3 m 0.3\text{ m} 0.3 m ) Calculated per label (typically 3 − 6 ft 3-6\text{ ft} 3 − 6 ft ) ASTM F1505 rated 1 , 500 V d c 1,500\text{ V}_{dc} 1 , 500 V d c Category 2 ( 8 cal/cm 2 8\text{ cal/cm}^2 8 cal/cm 2 ); Class 0 gloves
1500V DC Utility-Scale Solar Arrays 5 ft 0 in 5\text{ ft } 0\text{ in} 5 ft 0 in ( 1.5 m 1.5\text{ m} 1.5 m ) 1 ft 5 in 1\text{ ft } 5\text{ in} 1 ft 5 in ( 0.43 m 0.43\text{ m} 0.43 m ) Calculated per label (typically 5 − 12 ft 5-12\text{ ft} 5 − 12 ft ) ASTM F1505 rated 1 , 500 V d c 1,500\text{ V}_{dc} 1 , 500 V d c Category 2 or 4 ( 8 − 40 cal/cm 2 8-40\text{ cal/cm}^2 8 − 40 cal/cm 2 ); Class 1 gloves
High-Voltage Battery Storage (BESS) Per voltage table Per voltage table High incident energy (often > 40 cal/cm 2 >40\text{ cal/cm}^2 > 40 cal/cm 2 ) ASTM F1505 rated 1 , 500 V d c 1,500\text{ V}_{dc} 1 , 500 V d c Category 4 suit or non-arc-in-excess controls; Class 0/1 gloves