6.3 Building Envelope & Fenestration
NATE Core Knowledge Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Introduction & Exam Overview
1.1 About the NATE Core Knowledge Exam 1.2 Study Strategy & Blueprint Navigation 1.3 HVAC Fundamentals & Math Review
2 Chapter 2: Safety Regulations & Jobsite Practices
2.1 Government & Environmental Regulations 2.2 Personal Safety, PPE & Jobsite Practices 2.3 Moving Machinery & Rotating Equipment Safety
3 Chapter 3: Hazardous Materials, Cylinders & Brazing Safety
3.1 Confined Spaces & Refrigerant Exposure Safety 3.2 Safe Brazing, Soldering & Nitrogen Purging 3.3 Compressed Gas Cylinders, Hazmat & Fire Safety
4 Chapter 4: Hand, Power & Fabrication Tools
4.1 Measurement & Layout Tools 4.2 Fastening & Mechanical Hand Tools 4.3 Sheet Metal Fabrication & Cutting Tools
5 Chapter 5: Copper Tubing Tools & Piping Practices
5.1 Copper Tubing Cutting & Reaming 5.2 Flaring Tools & Mechanical Joints 5.3 Swaging & Tubing Bending
6 Chapter 6: Basic Construction & Building Systems
6.1 Architectural Plans, Specifications & Blueprints 6.2 Structural Framing, Trusses & Clearances 6.3 Building Envelope & Fenestration 6.4 Mechanical Routing, Firestopping & Venting
7 Chapter 7: Basic Science & Thermodynamics
7.1 Matter, Chemistry & Combustion Principles 7.2 Pressure Fundamentals & Gas Laws 7.3 Applied HVAC Physics & Mathematics
8 Chapter 8: Achieving Desired Conditions & Comfort
8.1 Human Thermal Comfort & ASHRAE Standard 55 8.2 Humidity Control & System Psychrometrics 8.3 Ventilation Standards & ASHRAE Standard 62.2
9 Chapter 9: Indoor Air Quality & Acoustic Control
9.1 Air Filtration & MERV Ratings 9.2 Air Cleaning, Odor Control & UVGI 9.3 Sound & Vibration Attenuation
10 Chapter 10: Temperature & Heat Science
10.1 Sensible Heat, Latent Heat & BTU Fundamentals 10.2 Methods of Heat Transfer 10.3 Temperature Measurement Instruments & Calibration
11 Chapter 11: Humidity Measurements & Psychrometrics
11.1 Dry-Bulb, Wet-Bulb & Temperature Splits 11.2 Sling Psychrometers & Humidity Instruments 11.3 Psychrometric Chart Analysis & Enthalpy
12 Chapter 12: Electrical Fundamentals & Schematics
12.1 Electrical Concepts, Ohm's Law & Power 12.2 AC Power, Magnetism & Control Transformers 12.3 Electrical Loads & Power Factor 12.4 Electrical Symbols & Ladder Diagrams
13 Chapter 13: Electric Motors & Field Controls
13.1 Single-Phase Electric Motors & Capacitors 13.2 Three-Phase Motors & Commercial Power 13.3 Variable-Speed ECM Motors & Actuators 13.4 Field Wiring, Contactors & Control Devices
14 Chapter 14: Digital Meters & Electrical Diagnostics
14.1 Digital Multimeters & Safety Ratings 14.2 Voltage Drop, Amperage & Resistance Testing 14.3 Specialized Electrical Diagnostics: Megohmmeter, Capacitance & Micro-Signals
6.3 Building Envelope & Fenestration
Key Takeaways Explain This Topic AI
The building thermal envelope consists of the continuous thermal boundary (insulation layer) and the continuous air barrier, which must be installed in full physical alignment to prevent convective looping.
Thermal resistance (R-value) measures resistance to conductive heat flow (R = ΔT / Heat Flux); overall assembly R-values sum material layers in series, but thermal bridging through framing members drastically reduces effective whole-wall performance.
Fenestration performance is certified by the NFRC: U-factor measures overall heat conduction (lower U-factor means superior insulating ability; U = 1 / R), while Solar Heat Gain Coefficient (SHGC) measures solar heat transmission (low SHGC < 0.25 desired in cooling climates; higher SHGC desired in heating climates).
Air infiltration is driven by stack effect, wind forces, and duct leakage imbalances; whole-building airtightness is quantified via blower door testing at 50 Pascals (ACH50).
HVAC technicians must thoroughly air-seal all mechanical envelope penetrations, including duct boots, refrigerant lines, and plumbing chases, to prevent massive conditioned air loss.
Last updated: September 2026
- 6.3 Building Envelope & Fenestration
- The Building Thermal Envelope and Air Barrier Alignment
An HVAC system does not condition a vacuum; it conditions an enclosed architectural volume bounded by the building thermal envelope . The building envelope encompasses all exterior building assemblies—exterior walls, foundations, slabs, windows, exterior doors, and roof/ceiling assemblies—that separate conditioned indoor living space from unconditioned outdoor air, ventilated attics, or vented crawl spaces.
The Two Pillars: Thermal Boundary and Air Barrier
For a building envelope to perform effectively, two distinct components must function in unison:
The Thermal Boundary (Insulation Layer) : Retards the conductive and radiant transfer of heat between conditioned and unconditioned spaces.
The Continuous Air Barrier : A continuous plane of materials (such as taped exterior sheathing, sealed drywall, polyethylene membranes, or closed-cell spray foam) that blocks the convective infiltration and exfiltration of air through the assembly. Critical Thermal Alignment Principle:
- [ Outdoor Unconditioned Air ]
- |
- +------+-----------------------------------------------------+
- | AIR BARRIER (Taped Sheathing / Housewrap) |
- +------------------------------------------------------------+
- | THERMAL BOUNDARY (Insulation Layer) |
- | * Must be in continuous 100% direct contact with the |
- | air barrier to prevent convective looping and bypasses! |
- +------------------------------------------------------------+
- | INTERIOR AIR BARRIER (Sealed Drywall / Polyethylene) |
- +------+-----------------------------------------------------+
- |
- [ Indoor Conditioned Air ]
- The Alignment Mandate
A foundational rule of building science is that the thermal boundary and the air barrier must be installed in continuous, intimate contact with each other . When gaps exist between the insulation and the air barrier (for example, fiberglass batts drooping away from floor subflooring over an unconditioned crawl space, or unsealed vertical drywall chases behind bathtubs), air circulates freely behind the insulation in a process known as convective looping . Convective looping bypasses the thermal resistance of the insulation entirely, reducing effective R-value by 30 % 30\% 30% to 50 % 50\% 50% and leading to severe winter condensation, mold growth, and high HVAC energy bills.
Insulation Types and Thermal Resistance (R-Value)
Heat transfers spontaneously from regions of higher temperature to regions of lower temperature via conduction, convection, and radiation. In building assemblies, thermal resistance to conductive heat flow is quantified by the R-value .
The Physics of R-Value and Conductive Heat Transfer
Mathematically, R-value is defined as the temperature difference across an assembly divided by the heat flux passing through it: R = Δ T Heat Flux = Δ T ⋅ A ⋅ t Q R = \frac{\Delta T}{\text{Heat Flux}} = \frac{\Delta T \cdot A \cdot t}{Q} R = Heat Flux Δ T = Q Δ T ⋅ A ⋅ t
Where:
R R R = Thermal resistance in h ⋅ ft 2 ⋅ ∘ F / BTU \text{h}\cdot\text{ft}^2\cdot^\circ\text{F}/\text{BTU} h ⋅ ft 2 ⋅ ∘ F / BTU
- Δ T \Delta T Δ T = Temperature difference between interior and exterior surfaces in ∘ F ^\circ\text{F} ∘ F
- A A A = Surface area in ft 2 \text{ft}^2 ft 2
- t t t = Time duration in hours ( h \text{h} h )
- Q Q Q = Total heat transfer in BTU \text{BTU} BTU
Conductive heat transfer rate ( q q q in BTU/hr \text{BTU/hr} BTU/hr ) through any homogeneous building assembly is calculated using the steady-state heat conduction equation: q = A ⋅ Δ T R total = U ⋅ A ⋅ Δ T q = \frac{A \cdot \Delta T}{R_{\text{total}}} = U \cdot A \cdot \Delta T q = R total A ⋅ Δ T = U ⋅ A ⋅ Δ T
Series R-Value Calculation
Building assemblies consist of multiple material layers arranged in series (exterior siding, sheathing, insulation cavity, interior gypsum board, and interior/exterior air surface films). The total thermal resistance of layers in series is the direct arithmetic sum of their individual R-values: R total = R outside air film + R siding + R sheathing + R cavity + R drywall + R inside air film R_{\text{total}} = R_{\text{outside air film}} + R_{\text{siding}} + R_{\text{sheathing}} + R_{\text{cavity}} + R_{\text{drywall}} + R_{\text{inside air film}} R total = R outside air film + R siding + R sheathing + R cavity + R drywall + R inside air film
Comparative Analysis of Insulation Materials
Insulation Material Nominal R-Value per Inch Vapor Permeability Strengths & Best Applications Field Traps & Limitations
Fiberglass Batts R - 3.1 R\text{-}3.1 R - 3.1 to R - 3.7 R\text{-}3.7 R - 3.7 High (Permeable) Non-combustible, inexpensive, standard residential stud cavities. Air-permeable; compressing a batt reduces overall R-value; poor performance if air gaps exist.
Blown Loose-Fill Cellulose R - 3.2 R\text{-}3.2 R - 3.2 to R - 3.8 R\text{-}3.8 R - 3.8 Moderate Recycled paper treated with borates for fire/pest resistance; fills attic joists and irregular cavities well. Settles over time ( 10 % 10\% 10% to 20 % 20\% 20% ); can absorb moisture if roof leaks develop; requires attic baffles at soffits.
Mineral Wool (Rockwool) R - 3.3 R\text{-}3.3 R - 3.3 to R - 4.2 R\text{-}4.2 R - 4.2 High (Permeable) Extreme fire resistance (melting point > 2 , 150 ∘ F >2,150^\circ\text{F} > 2 , 15 0 ∘ F ), hydrophobic, excellent acoustic sound dampening. Denser and heavier than fiberglass; more abrasive to handle; higher material cost.
Expanded Polystyrene (EPS) R - 3.6 R\text{-}3.6 R - 3.6 to R - 4.0 R\text{-}4.0 R - 4.0 Moderate Inexpensive rigid white beadboard; continuous exterior insulation, foundation walls. Lower R-value per inch than XPS; susceptible to insect boring without insecticide treatment.
Extruded Polystyrene (XPS) R - 5.0 R\text{-}5.0 R - 5.0 Low / Semi-impermeable Blue/pink rigid board; high compressive strength, excellent moisture resistance for below-grade slabs. Degrades under direct UV solar exposure; requires thermal barrier (drywall) indoors due to flammability.
Open-Cell Spray Foam (ocSPF) R - 3.6 R\text{-}3.6 R - 3.6 to R - 3.8 R\text{-}3.8 R - 3.8 High ( 0.5 lb/ft 3 0.5\text{ lb/ft}^3 0.5 lb/ft 3 density) Expands 100 × 100\times 100 × to fill complex voids; creates excellent air seal; economical air barrier. Permeable to vapor (requires separate vapor retarder in cold climates); cannot be used in contact with liquid water.
Closed-Cell Spray Foam (ccSPF) R - 6.5 R\text{-}6.5 R - 6.5 to R - 7.0 R\text{-}7.0 R - 7.0 Class II Vapor Retarder ( 2.0 lb/ft 3 2.0\text{ lb/ft}^3 2.0 lb/ft 3 ) Maximum R-value per inch; impermeable to air and bulk water; adds structural racking strength to walls. High cost; requires strict chemical ratio mixing and thermal cure monitoring; requires ignition barrier.
Thermal Bridging Across Structural Framing
Technicians often assume that installing R - 13 R\text{-}13 R - 13 fiberglass batts into a 2 × 4 2\times4 2 × 4 exterior wall delivers an R - 13 R\text{-}13 R - 13 wall. It does not. Wood framing has an R-value of only approximately R - 1.25 R\text{-}1.25 R - 1.25 per inch of thickness (delivering R - 4.38 R\text{-}4.38 R - 4.38 for a 3.5 inch 3.5\text{ inch} 3.5 inch deep 2 × 4 2\times4 2 × 4 ). Structural framing members (studs, plates, headers, sills) act as thermal bridges—high-conductivity bypasses through which heat flows freely around cavity insulation.
In standard 16 inch 16\text{ inch} 16 inch on-center framing, wood framing represents 20 % 20\% 20% to 25 % 25\% 25% of the total wall surface area. To calculate the true effective whole-wall U-factor ( U wall U_{\text{wall}} U wall ) , parallel-path heat flow calculations are applied: U wall = ( f framing × U framing ) + ( f cavity × U cavity ) U_{\text{wall}} = (f_{\text{framing}} \times U_{\text{framing}}) + (f_{\text{cavity}} \times U_{\text{cavity}}) U wall = ( f framing × U framing ) + ( f cavity × U cavity )
Where f framing = 0.25 f_{\text{framing}} = 0.25 f framing = 0.25 and f cavity = 0.75 f_{\text{cavity}} = 0.75 f cavity = 0.75 : U framing = 1 R wood + R sheathing + R drywall = 1 4.38 + 0.62 + 0.45 = 1 5.45 = 0.183 U_{\text{framing}} = \frac{1}{R_{\text{wood}} + R_{\text{sheathing}} + R_{\text{drywall}}} = \frac{1}{4.38 + 0.62 + 0.45} = \frac{1}{5.45} = 0.183 U framing = R wood + R sheathing + R drywall 1 = 4.38 + 0.62 + 0.45 1 = 5.45 1 = 0.183 U cavity = 1 R insul + R sheathing + R drywall = 1 13.0 + 0.62 + 0.45 = 1 14.07 = 0.071 U_{\text{cavity}} = \frac{1}{R_{\text{insul}} + R_{\text{sheathing}} + R_{\text{drywall}}} = \frac{1}{13.0 + 0.62 + 0.45} = \frac{1}{14.07} = 0.071 U cavity = R insul + R sheathing + R drywall 1 = 13.0 + 0.62 + 0.45 1 = 14.07 1 = 0.071 U wall = ( 0.25 × 0.183 ) + ( 0.75 × 0.071 ) = 0.0458 + 0.0533 = 0.0991 U_{\text{wall}} = (0.25 \times 0.183) + (0.75 \times 0.071) = 0.0458 + 0.0533 = 0.0991 U wall = ( 0.25 × 0.183 ) + ( 0.75 × 0.071 ) = 0.0458 + 0.0533 = 0.0991 R effective = 1 U wall = 1 0.0991 ≈ R - 10.1 R_{\text{effective}} = \frac{1}{U_{\text{wall}}} = \frac{1}{0.0991} \approx R\text{-}10.1 R effective = U wall 1 = 0.0991 1 ≈ R - 10.1
Thermal bridging reduces the nominal R - 13 R\text{-}13 R - 13 cavity batt wall to an effective whole-wall performance of roughly R - 10.1 R\text{-}10.1 R - 10.1 (a 22 % 22\% 22% loss in thermal efficiency). With steel stud framing (where steel thermal conductivity is over 300 × 300\times 300 × greater than wood), cavity insulation performance drops by upwards of 50 % 50\% 50% unless continuous rigid foam insulation ( R ci R_{\text{ci}} R ci ) is installed over the exterior sheathing.
Fenestration Performance: National Fenestration Rating Council (NFRC)
Fenestration refers to all glazed assemblies in a building envelope, including windows, exterior glass doors, glazed curtain walls, and skylights. Windows represent the most thermally vulnerable component of the building envelope, accounting for a disproportionate share of both heating conduction losses and summer solar heat gains. NFRC Certified Rating Label:
- +-------------------------------------------------------------------------+
- | National Fenestration Rating Council |
- | CERTIFIED |
- +------------------------------------+------------------------------------+
- | U-Factor | Solar Heat Gain Coefficient |
- | 0.28 | 0.22 |
- +------------------------------------+------------------------------------+
- | Visible Transmittance | Air Leakage |
- | 0.54 | <= 0.3 |
- +------------------------------------+------------------------------------+
The National Fenestration Rating Council (NFRC) establishes standardized testing protocols and certifies window performance labels across four primary metrics:
1. U-Factor (Conduction Rate)
Definition : The rate of non-solar heat transfer through the entire window assembly (including glass, frame, edge spacers, and seals). Expressed in BTU / ( h ⋅ ft 2 ⋅ ∘ F ) \text{BTU}/(\text{h}\cdot\text{ft}^2\cdot^\circ\text{F}) BTU / ( h ⋅ ft 2 ⋅ ∘ F ) .
Relationship to R-Value : U-factor is the exact mathematical inverse of R-value ( U = 1 / R U = 1 / R U = 1/ R , and R = 1 / U R = 1 / U R = 1/ U ).
Scale & Interpretation : Typical values range from 0.15 0.15 0.15 to 1.20 1.20 1.20 . A LOWER U-factor indicates superior thermal insulating ability.
Single-pane clear glass with aluminum frame: U - 1.10 U\text{-}1.10 U - 1.10 to U - 1.20 U\text{-}1.20 U - 1.20 ( R - 0.85 R\text{-}0.85 R - 0.85 to R - 0.90 R\text{-}0.90 R - 0.90 )
Standard double-pane clear glass with vinyl frame: U - 0.45 U\text{-}0.45 U - 0.45 to U - 0.50 U\text{-}0.50 U - 0.50 ( R - 2.0 R\text{-}2.0 R - 2.0 to R - 2.2 R\text{-}2.2 R - 2.2 )
High-performance double-pane with Low-E coating and Argon gas fill: U - 0.25 U\text{-}0.25 U - 0.25 to U - 0.30 U\text{-}0.30 U - 0.30 ( R - 3.3 R\text{-}3.3 R - 3.3 to R - 4.0 R\text{-}4.0 R - 4.0 )
Premium triple-pane with two Low-E coatings and Krypton gas fill: U - 0.15 U\text{-}0.15 U - 0.15 to U - 0.20 U\text{-}0.20 U - 0.20 ( R - 5.0 R\text{-}5.0 R - 5.0 to R - 6.7 R\text{-}6.7 R - 6.7 )
2. Solar Heat Gain Coefficient (SHGC)
Definition : The fraction of incident solar radiation admitted through a window, both directly transmitted and absorbed/reradiated indoors.
Scale & Interpretation : Expressed as a dimensionless decimal number between 0.00 0.00 0.00 and 1.00 1.00 1.00 .
Low SHGC ( < 0.25 < 0.25 < 0.25 ) : Highly desirable in cooling-dominated climates (IECC Climate Zones 1, 2, and 3) . Spectrally selective Low-Emissivity (Low-E) coatings reflect the invisible infrared spectrum of sunlight, blocking up to 75 % 75\% 75% of solar radiant heat while allowing visible light through, drastically reducing air conditioning cooling loads.
High SHGC ( > 0.40 > 0.40 > 0.40 ) : Highly desirable on south-facing windows in heating-dominated climates (IECC Climate Zones 5, 6, 7, and 8) . It permits free passive solar heat gain to enter the home during winter sunny days, cutting heating fuel consumption.
3. Visible Transmittance (VT)
Definition : The fraction of visible spectrum light ( 380 to 740 nanometers 380\text{ to } 740\text{ nanometers} 380 to 740 nanometers ) that passes through the glazing assembly.
Scale : Expressed as a number between 0.00 0.00 0.00 and 1.00 1.00 1.00 , typically ranging from 0.30 0.30 0.30 to 0.70 0.70 0.70 for residential windows. Higher VT provides brighter natural daylighting, reducing interior electric lighting needs without necessarily adding solar heat gain.
4. Air Leakage (AL)
Definition : The volumetric rate of air infiltration leaking through cracks around window sashes, weatherstripping, and frame joints under a standardized 25 mph 25\text{ mph} 25 mph wind pressure differential ( 75 Pascals 75\text{ Pascals} 75 Pascals or 1.57 psf 1.57\text{ psf} 1.57 psf ). Expressed in cubic feet per minute per square foot of window area ( CFM/ft 2 \text{CFM/ft}^2 CFM/ft 2 ).
Threshold : Industry building codes mandate an AL rating of ≤ 0.30 CFM/ft 2 \le 0.30\text{ CFM/ft}^2 ≤ 0.30 CFM/ft 2 . High-performance airtight windows achieve AL ratings of ≤ 0.10 CFM/ft 2 \le 0.10\text{ CFM/ft}^2 ≤ 0.10 CFM/ft 2 .
Building Air Infiltration, Stack Effect & Blower Door Testing
Uncontrolled air leakage (infiltration of outdoor air and exfiltration of indoor conditioned air) accounts for 25 % 25\% 25% to 40 % 40\% 40% of residential heating and cooling energy loss, while introducing outdoor humidity, dust, and allergens.
Natural Driving Forces: Stack Effect and Wind Effect
The Stack Effect (Thermal Buoyancy) : Driven by the density differential between indoor air and outdoor air.
Winter Stack Effect : Warm indoor air is less dense than cold outdoor air, creating positive buoyant pressure that rises to the upper levels of the home. This warm air exfiltrates through unsealed ceiling penetrations, attic hatches, recessed lighting cans, and top plates. This exfiltration creates a negative pressure zone at the bottom of the building, which pulls freezing outdoor air inward through crawl spaces, sill plates, and lower-floor wall penetrations.
Summer (Reverse) Stack Effect : In air-conditioned buildings during hot weather, cool indoor air sinks, creating positive pressure leaking out of lower levels while drawing hot, humid outdoor air into the attic and upper floor penetrations.
Wind Effect : Wind striking the windward side of a building creates positive pressure pushing air inward, while generating negative suction on the leeward and sidewall surfaces pulling air outward.
Blower Door Testing and ACH50
Building airtightness is measured using a Blower Door System , consisting of a calibrated variable-speed fan mounted in an expandable temporary frame in an exterior doorway, paired with a dual-channel digital manometer.
The fan depressurizes the entire conditioned space to a standardized pressure difference of − 50 Pascals -50\text{ Pascals} − 50 Pascals ( − 0.20 in. w.g. -0.20\text{ in. w.g.} − 0.20 in. w.g. ) relative to outdoors.
The manometer measures the airflow rate in cubic feet per minute required to maintain this pressure differential, denoted as CFM50 .
To calculate Air Changes per Hour at 50 Pascals (ACH50) : ACH50 = CFM50 × 60 Conditioned Building Volume ( ft 3 ) \text{ACH50} = \frac{\text{CFM50} \times 60}{\text{Conditioned Building Volume (}\text{ft}^3\text{)}} ACH50 = Conditioned Building Volume ( ft 3 ) CFM50 × 60
Worked Calculation: Determining ACH50 Compliance
A two-story residential home with a total conditioned floor area of 2 , 400 ft 2 2,400\text{ ft}^2 2 , 400 ft 2 and an average ceiling height of 9.0 feet 9.0\text{ feet} 9.0 feet is subjected to a blower door test. The digital manometer records an airflow rate of 1 , 440 CFM50 1,440\text{ CFM50} 1 , 440 CFM50 .
Calculate Conditioned Building Volume : Volume = 2 , 400 ft 2 × 9.0 ft = 21 , 600 ft 3 \text{Volume} = 2,400\text{ ft}^2 \times 9.0\text{ ft} = 21,600\text{ ft}^3 Volume = 2 , 400 ft 2 × 9.0 ft = 21 , 600 ft 3
Calculate ACH50 : ACH50 = 1 , 440 CFM50 × 60 min/hr 21 , 600 ft 3 = 86 , 400 21 , 600 = 4.0 ACH50 \text{ACH50} = \frac{1,440\text{ CFM50} \times 60\text{ min/hr}}{21,600\text{ ft}^3} = \frac{86,400}{21,600} = 4.0\text{ ACH50} ACH50 = 21 , 600 ft 3 1 , 440 CFM50 × 60 min/hr = 21 , 600 86 , 400 = 4.0 ACH50
Code Compliance Check : The International Energy Conservation Code (IECC) mandates:
Climate Zones 3 through 8 : Maximum allowable leakage is 3.0 ACH50 3.0\text{ ACH50} 3.0 ACH50 .
Climate Zones 1 and 2 : Maximum allowable leakage is 5.0 ACH50 5.0\text{ ACH50} 5.0 ACH50 .
At 4.0 ACH50 4.0\text{ ACH50} 4.0 ACH50 , this building passes code in Climate Zones 1–2 (deep south), but fails in Climate Zones 3–8 (requiring further air-sealing).
Critical HVAC Air Sealing Priorities
HVAC installers are responsible for sealing some of the largest envelope bypasses in residential construction:
Duct Boots : The interface between sheet metal duct boots and drywall ceiling or floor cutouts must be sealed airtight using mastic or approved foil tape. Unsealed boot perimeters pull dirty, unconditioned attic air directly into living spaces when room doors close.
Top Plate Penetrations : All holes drilled through double top plates for refrigerant line sets, wiring, and condensate drains must be sealed with fire-rated expanding polyurethane foam.
Mechanical Chases : Vertical wall chases housing duct drops or flue pipes must be capped at the ceiling level with solid sheet goods and sealed with fire-rated sealant.