Study guide

9.2 Air Cleaning, Odor Control & UVGI

NATE Core Knowledge Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction & Exam Overview

1.1 About the NATE Core Knowledge Exam 1.2 Study Strategy & Blueprint Navigation 1.3 HVAC Fundamentals & Math Review

2 Chapter 2: Safety Regulations & Jobsite Practices

2.1 Government & Environmental Regulations 2.2 Personal Safety, PPE & Jobsite Practices 2.3 Moving Machinery & Rotating Equipment Safety

3 Chapter 3: Hazardous Materials, Cylinders & Brazing Safety

3.1 Confined Spaces & Refrigerant Exposure Safety 3.2 Safe Brazing, Soldering & Nitrogen Purging 3.3 Compressed Gas Cylinders, Hazmat & Fire Safety

4 Chapter 4: Hand, Power & Fabrication Tools

4.1 Measurement & Layout Tools 4.2 Fastening & Mechanical Hand Tools 4.3 Sheet Metal Fabrication & Cutting Tools

5 Chapter 5: Copper Tubing Tools & Piping Practices

5.1 Copper Tubing Cutting & Reaming 5.2 Flaring Tools & Mechanical Joints 5.3 Swaging & Tubing Bending

6 Chapter 6: Basic Construction & Building Systems

6.1 Architectural Plans, Specifications & Blueprints 6.2 Structural Framing, Trusses & Clearances 6.3 Building Envelope & Fenestration 6.4 Mechanical Routing, Firestopping & Venting

7 Chapter 7: Basic Science & Thermodynamics

7.1 Matter, Chemistry & Combustion Principles 7.2 Pressure Fundamentals & Gas Laws 7.3 Applied HVAC Physics & Mathematics

8 Chapter 8: Achieving Desired Conditions & Comfort

8.1 Human Thermal Comfort & ASHRAE Standard 55 8.2 Humidity Control & System Psychrometrics 8.3 Ventilation Standards & ASHRAE Standard 62.2

9 Chapter 9: Indoor Air Quality & Acoustic Control

9.1 Air Filtration & MERV Ratings 9.2 Air Cleaning, Odor Control & UVGI 9.3 Sound & Vibration Attenuation

10 Chapter 10: Temperature & Heat Science

10.1 Sensible Heat, Latent Heat & BTU Fundamentals 10.2 Methods of Heat Transfer 10.3 Temperature Measurement Instruments & Calibration

11 Chapter 11: Humidity Measurements & Psychrometrics

11.1 Dry-Bulb, Wet-Bulb & Temperature Splits 11.2 Sling Psychrometers & Humidity Instruments 11.3 Psychrometric Chart Analysis & Enthalpy

12 Chapter 12: Electrical Fundamentals & Schematics

12.1 Electrical Concepts, Ohm's Law & Power 12.2 AC Power, Magnetism & Control Transformers 12.3 Electrical Loads & Power Factor 12.4 Electrical Symbols & Ladder Diagrams

13 Chapter 13: Electric Motors & Field Controls

13.1 Single-Phase Electric Motors & Capacitors 13.2 Three-Phase Motors & Commercial Power 13.3 Variable-Speed ECM Motors & Actuators 13.4 Field Wiring, Contactors & Control Devices

14 Chapter 14: Digital Meters & Electrical Diagnostics

14.1 Digital Multimeters & Safety Ratings 14.2 Voltage Drop, Amperage & Resistance Testing 14.3 Specialized Electrical Diagnostics: Megohmmeter, Capacitance & Micro-Signals

9.2 Air Cleaning, Odor Control & UVGI

Key Takeaways Explain This Topic AI

Two-stage electronic air cleaners (EACs) charge airborne particulates positive with a 5,000–6,000 VDC ionizing section and collect them on alternating grounded and high-voltage plates with virtually zero static pressure penalty.

Mechanical particulate filters cannot capture gases, vapors, or odors; gas-phase filtration requires physical adsorption via activated carbon (surface area >1,000 m²/g) or chemisorption via potassium permanganate.

Ultraviolet Germicidal Irradiation (UVGI) operates in the UV-C electromagnetic band, with the peak microbial DNA/RNA inactivation occurring at 253.7 nanometers (commonly referenced as 254 nm).

Coil surface irradiation provides continuous, low-intensity exposure with infinite dwell time to prevent mold and bacterial biofilm on wet fins and drain pans, whereas in-duct airstream disinfection requires massive UV intensity to inactivate fast-moving pathogens during brief dwell times (<0.5 seconds).

UV-C radiation poses severe eye (photokeratitis) and skin hazards to technicians; safety interlocks must instantly de-energize lamps upon door access, and non-UV-rated electrical wiring, sensors, and plastic drain pans must be shielded with aluminum foil tape or sheet metal.

Last updated: September 2026

  • 9.2 Air Cleaning, Odor Control & UVGI
  • Electronic Air Cleaners (EACs) & Electrostatic Precipitators

While mechanical fibrous filters trap particles by physical contact and impaction, Electronic Air Cleaners (EACs) —also termed electrostatic precipitators—use high-voltage electrical fields to remove airborne particulates without imposing high static pressure resistance on the HVAC blower. EACs are installed in the return air duct directly upstream of the indoor cooling coil or furnace.

The Two-Stage Precipitator Principle

Residential and light commercial EACs operate almost universally on a two-stage electrostatic precipitation process powered by an internal high-voltage DC power supply pack: Airflow Direction ──►

[ Stage 1: Ionizer ] ──► Fine tungsten wires at +5,000 to +6,000 VDC generate corona discharge;

airborne particles collide with ions and receive a strong positive charge.

[ Stage 2: Collector] ──► Alternating parallel aluminum plates:

• Charged Plates (+2,500 to +3,000 VDC) repel positive particles.

• Grounded Plates (0 VDC) attract and trap positive particles.

Stage 1: The Ionizing Section (Charging) :

Incoming air first passes through a coarse aluminum pre-filter screen that strains out large hair and lint.

The air then enters the ionizing section, which consists of fine tungsten wires strung parallel between grounded aluminum support frames.

The power supply energizes these ionizing wires with +5,000 to +6,000 Volts DC (VDC) .

This immense voltage gradient creates a localized electrical breakdown of surrounding air molecules known as a corona discharge . As dust, smoke, and pollen particles pass through this intense electrostatic field, free positive ions collide with them, imparting a strong positive electrostatic charge to virtually every particle.

Stage 2: The Collector Section (Precipitation) :

Positively charged particles immediately enter the collector cell, which consists of a dense bank of closely spaced parallel aluminum plates.

These plates are arranged in an alternating electrical sequence: every other plate is energized with +2,500 to +3,000 VDC , while the intervening plates are solidly connected to electrical ground ( 0 VDC ).

According to Coulomb's Law of electrostatics, like charges repel and opposite charges attract. As the positively charged dust particles travel between the plates, the +3,000 VDC plates repel them forcefully, driving them directly toward the adjacent grounded plates.

The particles impact the grounded plates and adhere. An optional adhesive spray or natural molecular cohesion holds the dust until the cell is manually washed.

Engineering Advantages and Operational Limitations

Static Pressure Advantage : Unlike high-MERV mechanical filters that create 0.35 to 0.50 in. w.c. resistance, an EAC collector cell has large open air channels between its parallel plates. The static pressure drop across an EAC is exceptionally low—typically 0.05 to 0.15 in. w.c. —and remains relatively constant even as dust accumulates.

Sub-Micron Efficiency : EACs are highly effective against sub-micron particles, including tobacco smoke, cooking oils, and fine atmospheric soot (down to 0.01 µm), which easily slip through MERV 6–8 pleated filters.

Washable Media : No replacement media cartridges are required; collector cells are removed and washed periodically in detergent.

Maintenance Protocols and Ozone Generation Concerns

Nuisance Arcing and Snapping : As dust accumulates on collector plates, or if large lint strands bridge the gap between high-voltage and grounded plates, an electrical spark jumps across the gap. This produces an audible snapping or popping noise. While an occasional snap is normal, constant rapid snapping indicates either heavily loaded plates, broken/slack ionizing wires touching ground, or bent collector plates.

Washing and Drying Procedure : Technicians must emphasize that after soaking collector cells in non-caustic degreasing detergent and rinsing thoroughly, the cells must be allowed to dry completely (typically 12–24 hours) before re-energizing. Re-installing damp cells creates an instant short circuit that trips the solid-state power pack or causes violent arcing.

Ozone ( O 3 O_3 O 3 ​ ) Production : High-voltage electrical corona discharges naturally dissociate oxygen molecules ( O 2 O_2 O 2 ​ ), generating ozone ( O 3 O_3 O 3 ​ ) as a chemical byproduct. Ozone is a known pulmonary irritant that exacerbates asthma and damages lung tissue. Modern EACs must meet strict standards (such as UL 867 and UL 2998 ) limiting indoor ozone emissions to less than 0.005 parts per million (5 ppb) .

Odor and Gaseous Contaminant Control: Adsorption vs. Chemisorption

Standard particulate filters and electronic air cleaners are completely ineffective against gases, volatile organic compounds (VOCs), and odors. Gas molecules (such as formaldehyde, benzene, toluene, ammonia, and hydrogen sulfide) have diameters measured in fractions of a nanometer ( 0.0003 to 0.005 μ m 0.0003\text{ to }0.005\,\mu\text{m} 0.0003 to 0.005 μ m )—thousands of times smaller than the spaces between mechanical filter fibers or collector plates.

Controlling gaseous indoor contaminants requires gas-phase air filtration , utilizing adsorption and chemisorption . GAS-PHASE FILTRATION MECHANISMS

  • ┌────────────────────────────────────────┬────────────────────────────────────────┐
  • │ PHYSICAL ADSORPTION (Carbon) │ CHEMISORPTION (Permanganate) │
  • ├────────────────────────────────────────┼────────────────────────────────────────┤
  • │ • Van der Waals physical surface bond │ • Irreversible chemical covalent bond │
  • │ • Millions of internal micropores │ • Potassium permanganate on alumina │
  • │ • High affinity for heavy VOCs & fuels │ • Neutralizes formaldehyde, H2S, SO2 │
  • │ • Reversible if heated (desorption) │ • Non-reversible; changes color when spent│
  • └────────────────────────────────────────┴────────────────────────────────────────┘
  • 1. Physical Adsorption via Activated Carbon

Material Physics : Activated carbon (charcoal) is produced by heating carbon-rich materials (such as coconut shells, bituminous coal, or wood) to extreme temperatures in an oxygen-free furnace, followed by chemical activation with high-temperature steam. This thermal etching process blows millions of microscopic cavities, fissures, and sub-nanometer pores throughout the internal carbon matrix.

Vast Surface Area : The internal surface area of activated carbon is staggering: one single gram of activated carbon possesses an internal surface area exceeding 1,000 to 1,500 square meters (equivalent to three full-sized basketball courts packed inside one gram!).

Adsorption Mechanism : As gas molecules drift into these microscopic pores, they are captured on the carbon's internal walls by physical Van der Waals intermolecular attraction . The gas molecules condense from the vapor phase and are physically held on the solid carbon surface without changing their chemical structure.

Target Compounds : Activated carbon has an exceptional affinity for non-polar, high-molecular-weight organic gases: gasoline/diesel vapors, paint solvents, benzene, toluene, cooking grease odors, and tobacco smoke odors.

Limitation : Pure activated carbon has poor affinity for low-molecular-weight, polar gases such as formaldehyde ( C H 2 O CH_2O C H 2 ​ O ), ammonia ( N H 3 NH_3 N H 3 ​ ), carbon monoxide ( C O CO CO ), sulfur dioxide ( S O 2 SO_2 S O 2 ​ ), and hydrogen sulfide ( H 2 S H_2S H 2 ​ S ) .

2. Chemisorption via Impregnated Media

To eliminate low-molecular-weight toxic gases and pungent chemical odors that slip through pure carbon, technicians use chemisorption media :

Composition : Porous activated alumina ( A l 2 O 3 Al_2O_3 A l 2 ​ O 3 ​ ) spheres impregnated with active chemical oxidizing agents, most commonly potassium permanganate ( K M n O 4 KMnO_4 K M n O 4 ​ ) or sodium permanganate at 4% to 8% concentration.

Mechanism : Chemisorption is not merely physical trapping; it is an irreversible chemical reaction . As gas molecules touch the impregnated pellet, they undergo oxidation, forming stable, odorless, non-volatile chemical compounds (such as carbon dioxide, water, and inorganic salts) that remain permanently bonded within the substrate.

Target Contaminants : Formaldehyde (outgassed from new building materials, laminates, and carpets), sewage odors ( H 2 S H_2S H 2 ​ S ), combustion byproducts, and industrial acid gases.

Field Replacement Cycles and Media Saturation

Unlike particulate filters, gas-phase filters do NOT increase in static pressure drop as they become fully loaded . A fully saturated carbon bed offers the exact same resistance to airflow as a brand-new bed. Therefore, filter change-outs cannot be scheduled using a differential pressure manometer.

Technicians must monitor gas-phase filters by:

Operating Hours : Standard residential carbon inserts typically saturate within 3 to 6 months depending on VOC levels.

Pellet Color Change : Potassium permanganate pellets start with a vibrant deep purple color . As they chemically oxidize contaminants, they turn to brown , and finally to pale beige/white when completely spent.

Breakthrough Detection : The reappearance of persistent household odors indicates the carbon has reached its adsorption saturation threshold and is beginning to release desorbed contaminants back into the supply air.

Ultraviolet Germicidal Irradiation (UVGI)

Ultraviolet Germicidal Irradiation (UVGI) uses shortwave electromagnetic radiation to neutralize biological contaminants—including mold spores, bacteria, and viruses—circulating through or colonizing HVAC systems.

The Ultraviolet Electromagnetic Spectrum

The UV spectrum spans wavelengths from 100 to 400 nanometers (nm), situated between visible violet light and X-rays. It is subdivided into four bands:

UV Band Wavelength Range Natural / Practical Characteristics

UV-A 315 to 400 nm "Black light"; longest UV wavelength; causes skin tanning; minimal germicidal effect.

UV-B 280 to 315 nm Penetrating solar radiation; causes sunburn and skin cancer; minimal biological HVAC usage.

UV-C 100 to 280 nm Germicidal Band ; fully absorbed by Earth's atmosphere; lethal to single-celled microorganisms.

Vacuum UV 100 to 200 nm Generates ozone ( O 3 O_3 O 3 ​ ) by breaking oxygen molecules; hazardous; banned in standard IAQ systems.

The 253.7 nm (254 nm) Germicidal Sweet Spot

The peak germicidal effectiveness across all biological organisms occurs between 250 and 265 nm , with commercial low-pressure mercury-vapor lamps engineered to emit their maximum radiant output at exactly 253.7 nm (conventionally rounded to 254 nm ). MECHANISM OF UV-C INACTIVATION

  • Normal DNA Strand: ───[Thymine]═════════[Adenine]───
  • ▲
  • UV-C Photon (254 nm) Strikes
  • ▼
  • Damaged DNA Strand: ───[Thymine]─┐
  • ├─ Dimer Formed! (Replication Blocked)
  • ───[Thymine]─┘

When a microorganism is exposed to 254 nm photons, the light penetrates the cellular membrane and is absorbed by the nucleic acids of the cell's DNA (deoxyribonucleic acid) or RNA (ribonucleic acid) . The high-energy photon breaks the molecular hydrogen bonds between adjacent thymine (in DNA) or uracil (in RNA) base pairs, causing them to fuse together into thymine dimers .

This molecular fusion distorts the DNA helix, rendering the microorganism incapable of replicating . While the microbe may not die instantaneously, it is biologically inactivated and rendered completely non-infectious, unable to cause disease or colonize surfaces.

UVGI Applications: Coil Surface Irradiation vs. In-Duct Airstream Disinfection

In HVAC engineering, UVGI systems are applied in two distinct operational configurations with radically different design parameters: SURFACE VS. AIRSTREAM DISINFECTION

  • ┌────────────────────────────────────────┬────────────────────────────────────────┐
  • │ COIL SURFACE IRRADIATION (Static) │ IN-DUCT AIRSTREAM KILL (Dynamic) │
  • ├────────────────────────────────────────┼────────────────────────────────────────┤
  • │ • Target: Mold, slime, fungal biofilm │ • Target: Moving airborne virus/bacteria│
  • │ • Airflow speed: Irrelevant (stationary│ • Airflow speed: 400–600 FPM │
  • │ • Dwell time: Infinite (24/7 exposure) │ • Dwell time: < 0.3 seconds! │
  • │ • Intensity: Moderate (50–150 µW/cm²) │ • Intensity: Extreme (>1,000 µW/cm²) │
  • │ • Benefits: Heat transfer, clean pan │ • Benefits: Disease transmission check │
  • └────────────────────────────────────────┴────────────────────────────────────────┘
  • 1. Coil Surface Irradiation (Stationary Target)

Installation : Lamps are mounted 12 to 18 inches away from the downstream (or upstream) face of the indoor cooling coil, directly aimed at the fin surfaces and the wet condensate drain pan.

Primary Target : Mold spores ( Aspergillus , Penicillium ), fungal colonies, and bacterial biofilms that thrive in the dark, damp, 45°F–55°F evaporator environment.

Operating Dynamic : Because the coil fins and drain pan do not move, the biological target is stationary. The dwell time is effectively infinite (24 hours per day, 365 days per year). Consequently, a relatively modest UV intensity ( 50 to 150 µW/cm² ) delivers a massive cumulative lethal dosage over time.

HVAC Performance Benefits :

Eliminates the foul volatile organic odors known as "Dirty Sock Syndrome."

Prevents fungal biofilm from choking the narrow spaces between aluminum fins, maintaining design static pressure across the coil.

Prevents biological slime from clogging the condensate drain line, avoiding secondary pan overflows.

Keeps the coil's overall heat transfer coefficient ( U U U -value) at factory design levels, preserving system SEER2 efficiency.

2. In-Duct Airstream Disinfection (Moving Target)

Installation : High-intensity lamp arrays installed inside the supply or return ductwork designed to kill airborne microorganisms as they fly past.

Primary Target : Airborne viruses (influenza, coronaviruses), bacteria ( Streptococcus , Legionella ), and active fungal spores in circulation.

The Dwell Time Challenge : Microorganisms move at the speed of the duct airflow (typically 400 to 600 FPM). Consider the mathematical dwell time ( t t t ) in a 2-foot UV irradiation zone: Air Velocity in ft/sec = 500 FPM 60 sec/min = 8.33 ft/sec \text{Air Velocity in ft/sec} = \frac{500\text{ FPM}}{60\text{ sec/min}} = 8.33\text{ ft/sec} Air Velocity in ft/sec = 60 sec/min 500 FPM ​ = 8.33 ft/sec Dwell Time ( t ) = 2 feet 8.33 ft/sec = 0.24 seconds \text{Dwell Time } (t) = \frac{2\text{ feet}}{8.33\text{ ft/sec}} = 0.24\text{ seconds} Dwell Time ( t ) = 8.33 ft/sec 2 feet ​ = 0.24 seconds

The UV Dosage Formula

The antimicrobial effectiveness of UVGI is governed by the UV Dosage ( D D D ) equation: Dosage ( D ) = UV Intensity ( I ) × Exposure Dwell Time ( t ) \text{Dosage } (D) = \text{UV Intensity } (I) \times \text{Exposure Dwell Time } (t) Dosage ( D ) = UV Intensity ( I ) × Exposure Dwell Time ( t )

D = Dosage measured in microwatt-seconds per square centimeter ( μ W ⋅ s/cm 2 ) D = \text{Dosage measured in microwatt-seconds per square centimeter } (\mu\text{W}\cdot\text{s/cm}^2) D = Dosage measured in microwatt-seconds per square centimeter ( μ W ⋅ s/cm 2 )

I = Radiant intensity measured in microwatts per square centimeter ( μ W/cm 2 ) I = \text{Radiant intensity measured in microwatts per square centimeter } (\mu\text{W/cm}^2) I = Radiant intensity measured in microwatts per square centimeter ( μ W/cm 2 )

t = Exposure dwell time measured in seconds ( s ) t = \text{Exposure dwell time measured in seconds } (\text{s}) t = Exposure dwell time measured in seconds ( s )

Because in-duct dwell time is a tiny fraction of a second ( 0.24 s 0.24\text{ s} 0.24 s ), delivering a lethal dose of 10 , 000 to 30 , 000 μ W ⋅ s/cm 2 10,000\text{ to }30,000\ \mu\text{W}\cdot\text{s/cm}^2 10 , 000 to 30 , 000 μ W ⋅ s/cm 2 (required to kill resilient fungal spores or hardy bacteria) requires massive radiant intensity ( I = D / t = 20 , 000 / 0.24 = 83 , 333 μ W/cm 2 I = D / t = 20,000 / 0.24 = 83,333\ \mu\text{W/cm}^2 I = D / t = 20 , 000/0.24 = 83 , 333 μ W/cm 2 ). This requires expensive multi-lamp arrays or high-output (HO) amalgam lamps, making true in-duct airstream disinfection far more costly and complex than static coil surface irradiation.

Advanced IAQ Technologies: PCO and Bipolar Ionization

Photocatalytic Oxidation (PCO) :

Uses a broad-spectrum UV-C/UV-A lamp focused directly on a honeycomb matrix coated with titanium dioxide ( T i O 2 TiO_2 T i O 2 ​ ) .

Photons striking the catalyst create highly reactive hydroxyl radicals ( O H ∙ OH^\bullet O H ∙ ) and superoxide ions on the honeycomb surface.

These radicals instantly attack volatile organic compounds, breaking complex hydrocarbons down into water vapor and carbon dioxide.

Field Caution : If air velocity is too high or the catalyst surface is dusty, PCO systems suffer from incomplete oxidation , producing toxic intermediate byproducts—such as formaldehyde and acetaldehyde —that are more hazardous than the original odors.

Bipolar Ionization / Needlepoint Bipolar Ionization (NPBI) :

Uses sharp carbon fiber emitter needles energized with alternating voltage to split ambient moisture molecules into positive hydrogen ( H + H^+ H + ) and negative oxygen ( O 2 − O_2^- O 2 − ​ ) ions.

The ions cause sub-micron airborne particulates to cluster together (agglomeration) so mechanical filters can catch them, while also disrupting the protein surface coats of airborne pathogens.

Systems must be verified under UL 2998 for zero ozone generation.

Occupational Safety and Material Degradation Hazards

UV-C light is an invisible, ionizing radiation hazard. Technicians working around UVGI systems must adhere to strict safety standards:

1. Personnel Health Hazards

Photokeratitis ("Welder's Flash" or Arc Eye) : Direct or reflected UV-C radiation destroys corneal epithelial cells. Symptoms—including excruciating eye pain, severe light sensitivity (photophobia), profuse tearing, and the distinct feeling of hot sand rubbed into the eyeballs—typically develop 4 to 12 hours after exposure. While the cornea regenerates in 24 to 48 hours, repeated exposure causes permanent cataracts and retinal damage.

Erythema (Skin Burns) : Short-term exposure causes rapid, intense ultraviolet burns and blistering identical to severe sunburn, accelerating long-term skin cancer risks.

  • Caution
  • Mandatory Safety Rule: Never Look at an Illuminated UV Lamp

Never view an energized UV lamp with the naked eye. Always turn off power at the dedicated disconnect or service switch before removing any equipment access panel. When testing or measuring lamp output, technicians must wear UV-blocking polycarbonate safety goggles or a full-face shield (standard clear polycarbonate blocks 99.9% of UV-C) and heavy long sleeves.

2. Electrical Interlocks and Viewports

Every HVAC unit equipped with UVGI must feature an electrical door interlock switch wired in series with the ballast line voltage. When an access panel is removed, the switch mechanically opens, instantly killing power to the lamps.

Cabinet inspection ports must be constructed from UV-absorbing glass or specialized polycarbonate , allowing technicians to confirm lamp operation visually without exposure.

3. Material Photodegradation (The Plastic/Wire Shielding Mandate)

High-energy 254 nm photons break molecular carbon-carbon bonds in synthetic organic polymers. When retrofitting a UV lamp into an existing air handler, the technician must inspect all materials within direct line-of-sight of the lamp:

Standard Wire Insulation : Thermoplastic wiring insulation (such as PVC, nylon, or polyethylene) rapidly oxidizes, turning chalky, brittle, and cracked within 6 to 18 months, leading to dead short circuits and electrical fires.

Plastic Condensate Drain Pans : Non-UV-stabilized ABS or polystyrene drain pans become severely embrittled, cracking under water weight and flooding ceilings.

Flex Duct and Rubber Dampeners : Synthetic inner liners of flexible ductwork and rubber vibration isolators crumble into dust.

Corrective Field Action : All wiring harnesses within line-of-sight must be routed through flexible metallic conduit (liquidtight metal conduit) or wrapped completely in heavy-duty aluminum foil tape . Plastic drain pans must be shielded with sheet metal flashing or covered with UV-resistant aluminum foil tape.