Study guide

1.3 HVAC Fundamentals & Math Review

NATE Core Knowledge Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Introduction & Exam Overview

1.1 About the NATE Core Knowledge Exam 1.2 Study Strategy & Blueprint Navigation 1.3 HVAC Fundamentals & Math Review

2 Chapter 2: Safety Regulations & Jobsite Practices

2.1 Government & Environmental Regulations 2.2 Personal Safety, PPE & Jobsite Practices 2.3 Moving Machinery & Rotating Equipment Safety

3 Chapter 3: Hazardous Materials, Cylinders & Brazing Safety

3.1 Confined Spaces & Refrigerant Exposure Safety 3.2 Safe Brazing, Soldering & Nitrogen Purging 3.3 Compressed Gas Cylinders, Hazmat & Fire Safety

4 Chapter 4: Hand, Power & Fabrication Tools

4.1 Measurement & Layout Tools 4.2 Fastening & Mechanical Hand Tools 4.3 Sheet Metal Fabrication & Cutting Tools

5 Chapter 5: Copper Tubing Tools & Piping Practices

5.1 Copper Tubing Cutting & Reaming 5.2 Flaring Tools & Mechanical Joints 5.3 Swaging & Tubing Bending

6 Chapter 6: Basic Construction & Building Systems

6.1 Architectural Plans, Specifications & Blueprints 6.2 Structural Framing, Trusses & Clearances 6.3 Building Envelope & Fenestration 6.4 Mechanical Routing, Firestopping & Venting

7 Chapter 7: Basic Science & Thermodynamics

7.1 Matter, Chemistry & Combustion Principles 7.2 Pressure Fundamentals & Gas Laws 7.3 Applied HVAC Physics & Mathematics

8 Chapter 8: Achieving Desired Conditions & Comfort

8.1 Human Thermal Comfort & ASHRAE Standard 55 8.2 Humidity Control & System Psychrometrics 8.3 Ventilation Standards & ASHRAE Standard 62.2

9 Chapter 9: Indoor Air Quality & Acoustic Control

9.1 Air Filtration & MERV Ratings 9.2 Air Cleaning, Odor Control & UVGI 9.3 Sound & Vibration Attenuation

10 Chapter 10: Temperature & Heat Science

10.1 Sensible Heat, Latent Heat & BTU Fundamentals 10.2 Methods of Heat Transfer 10.3 Temperature Measurement Instruments & Calibration

11 Chapter 11: Humidity Measurements & Psychrometrics

11.1 Dry-Bulb, Wet-Bulb & Temperature Splits 11.2 Sling Psychrometers & Humidity Instruments 11.3 Psychrometric Chart Analysis & Enthalpy

12 Chapter 12: Electrical Fundamentals & Schematics

12.1 Electrical Concepts, Ohm's Law & Power 12.2 AC Power, Magnetism & Control Transformers 12.3 Electrical Loads & Power Factor 12.4 Electrical Symbols & Ladder Diagrams

13 Chapter 13: Electric Motors & Field Controls

13.1 Single-Phase Electric Motors & Capacitors 13.2 Three-Phase Motors & Commercial Power 13.3 Variable-Speed ECM Motors & Actuators 13.4 Field Wiring, Contactors & Control Devices

14 Chapter 14: Digital Meters & Electrical Diagnostics

14.1 Digital Multimeters & Safety Ratings 14.2 Voltage Drop, Amperage & Resistance Testing 14.3 Specialized Electrical Diagnostics: Megohmmeter, Capacitance & Micro-Signals

1.3 HVAC Fundamentals & Math Review

Key Takeaways Explain This Topic AI

Temperature conversions between Fahrenheit and Celsius require standard linear formulas, while thermodynamic gas law calculations require absolute temperature scales: Rankine (°R = °F + 460) and Kelvin (K = °C + 273).

Pressure is expressed as gauge pressure (psig), absolute pressure (psia = psig + 14.7 at sea level), or inches of water column (in. w.c., where 1 psi = 27.7 in. w.c. and 1 in. Hg = 13.6 in. w.c.).

Ohm's law (E = I × R) and the electric power formula (P = E × I) govern all electrical troubleshooting and circuit analysis on the Core exam.

The sensible heat formula (Q = 1.08 × CFM × ΔT) and total heat formula (Q = 4.5 × CFM × Δh) represent the foundational equations for evaluating airflow and thermal capacity in air distribution systems.

Converting between units (such as Watts to Btu/hr via the multiplier 3.412) enables field verification of electric furnace heating output and system operating CFM.

Last updated: September 2026

  • 1.3 HVAC Fundamentals & Math Review
  • Temperature Scales and Absolute Temperature Conversions

Temperature is the measurement of the average molecular kinetic energy of a substance. In HVAC/R work, technicians must routinely convert between temperature scales and understand when absolute temperature scales are mandatory.

The Four Standard Scales

Fahrenheit (°F) : The primary imperial scale used in North American HVAC/R. At standard sea-level atmospheric pressure (14.696 psia), pure water freezes at 32 ∘ F 32^\circ\text{F} 3 2 ∘ F and boils at 212 ∘ F 212^\circ\text{F} 21 2 ∘ F (a span of 180 degrees).

Celsius (°C) : The metric scale. Pure water freezes at 0 ∘ C 0^\circ\text{C} 0 ∘ C and boils at 100 ∘ C 100^\circ\text{C} 10 0 ∘ C (a span of 100 degrees). The ratio between Fahrenheit and Celsius degree increments is 180 100 = 9 5 = 1.8 \frac{180}{100} = \frac{9}{5} = 1.8 100 180 ​ = 5 9 ​ = 1.8 .

Rankine (°R) : The imperial absolute temperature scale. Absolute zero—the theoretical point where all molecular motion ceases—is 0 ∘ R 0^\circ\text{R} 0 ∘ R , corresponding to − 459.67 ∘ F -459.67^\circ\text{F} − 459.6 7 ∘ F . In field calculations, this is rounded to 460 460 460 .

Kelvin (K) : The metric absolute temperature scale. Absolute zero is 0 K 0\text{ K} 0 K , corresponding to − 273.15 ∘ C -273.15^\circ\text{C} − 273.1 5 ∘ C (rounded to 273 273 273 ).

Conversion Formulas ∘ F = ( ∘ C × 1.8 ) + 32 or ∘ F = ( ∘ C × 9 5 ) + 32 \mathbf{^\circ F = (^\circ C \times 1.8) + 32} \quad \text{or} \quad ^\circ\text{F} = \left(^\circ\text{C} \times \frac{9}{5}\right) + 32 ∘ F = ( ∘ C × 1.8 ) + 32 or ∘ F = ( ∘ C × 5 9 ​ ) + 32 ∘ C = ∘ F − 32 1.8 or ∘ C = ( ∘ F − 32 ) × 5 9 \mathbf{^\circ C = \frac{^\circ F - 32}{1.8}} \quad \text{or} \quad ^\circ\text{C} = (^\circ\text{F} - 32) \times \frac{5}{9} ∘ C = 1.8 ∘ F − 32 ​ or ∘ C = ( ∘ F − 32 ) × 9 5 ​ ∘ R = ∘ F + 460 ( exact: 459.67 ) \mathbf{^\circ R = ^\circ F + 460} \quad (\text{exact: } 459.67) ∘ R = ∘ F + 460 ( exact: 459.67 ) K = ∘ C + 273 ( exact: 273.15 ) \mathbf{K = ^\circ C + 273} \quad (\text{exact: } 273.15) K = ∘ C + 273 ( exact: 273.15 )

CRITICAL EXAM RULE : Whenever you apply the ideal gas laws (Boyle's Law, Charles's Law, Gay-Lussac's Law, or P 1 V 1 T 1 = P 2 V 2 T 2 \frac{P_1 V_1}{T_1} = \frac{P_2 V_2}{T_2} T 1 ​ P 1 ​ V 1 ​ ​ = T 2 ​ P 2 ​ V 2 ​ ​ ), temperature MUST ALWAYS be converted to an absolute scale ( Rankine in imperial units, Kelvin in metric units). Inserting Fahrenheit or Celsius directly into gas law equations results in fatal mathematical errors.

Worked Example: Temperature Conversion to Absolute

A cylinder of nitrogen gas sits in an unconditioned service van overnight at 40 ∘ F 40^\circ\text{F} 4 0 ∘ F . During the afternoon, the van temperature rises to 95 ∘ F 95^\circ\text{F} 9 5 ∘ F . What are the initial and final temperatures in degrees Rankine?

Initial Temperature: T 1 = 40 ∘ F + 460 = 500 ∘ R T_1 = 40^\circ\text{F} + 460 = 500^\circ\text{R} T 1 ​ = 4 0 ∘ F + 460 = 50 0 ∘ R

Final Temperature: T 2 = 95 ∘ F + 460 = 555 ∘ R T_2 = 95^\circ\text{F} + 460 = 555^\circ\text{R} T 2 ​ = 9 5 ∘ F + 460 = 55 5 ∘ R

Pressure Fundamentals: Atmospheric, Gauge, Absolute, and Water Column

Pressure is defined as force per unit area: P = Force Area ( e.g., pounds per square inch, or psi ) P = \frac{\text{Force}}{\text{Area}} \quad \left(\text{e.g., pounds per square inch, or psi}\right) P = Area Force ​ ( e.g., pounds per square inch, or psi )

1. Atmospheric Pressure

The earth's atmosphere exerts pressure due to the weight of air molecules. At sea level under standard conditions ( 59 ∘ F / 15 ∘ C 59^\circ\text{F} / 15^\circ\text{C} 5 9 ∘ F /1 5 ∘ C ), standard atmospheric pressure equals:

  • 14.696 psia 14.696\text{ psia} 14.696 psia (commonly rounded to 14.7 psia 14.7\text{ psia} 14.7 psia )
  • 29.92 in. Hg 29.92\text{ in. Hg} 29.92 in. Hg (inches of mercury)
  • 760 mm Hg 760\text{ mm Hg} 760 mm Hg (millimeters of mercury or Torr)
  • 101.325 kPa 101.325\text{ kPa} 101.325 kPa (kilopascals)
  • 407 in. w.c. 407\text{ in. w.c.} 407 in. w.c. (inches of water column)

As altitude increases, atmospheric pressure decreases because there is less atmospheric air mass above the measurement point. For example, at Denver, Colorado (~5,280 feet), atmospheric pressure drops to approximately 12.1 psia 12.1\text{ psia} 12.1 psia ( 24.6 in. Hg 24.6\text{ in. Hg} 24.6 in. Hg ).

2. Gauge Pressure (psig) vs. Absolute Pressure (psia)

Gauge Pressure ( psig \text{psig} psig ) : Calibrated to read 0 psig 0\text{ psig} 0 psig in open atmospheric air. A standard refrigeration manifold gauge measures pressure relative to the surrounding atmosphere.

Absolute Pressure ( psia \text{psia} psia ) : Measures pressure relative to a perfect, complete vacuum ( 0 psia 0\text{ psia} 0 psia ).

The Mathematical Bridge : P psia = P psig + P atmospheric ⟶ P psia = P psig + 14.7 ( at sea level ) \mathbf{P_{\text{psia}} = P_{\text{psig}} + P_{\text{atmospheric}}} \quad \longrightarrow \quad \mathbf{P_{\text{psia}} = P_{\text{psig}} + 14.7} \quad (\text{at sea level}) P psia ​ = P psig ​ + P atmospheric ​ ⟶ P psia ​ = P psig ​ + 14.7 ( at sea level ) P psig = P psia − 14.7 \mathbf{P_{\text{psig}} = P_{\text{psia}} - 14.7} P psig ​ = P psia ​ − 14.7

If your refrigeration gauge reads 118.3 psig 118.3\text{ psig} 118.3 psig on an R-410A system at sea level, the absolute pressure inside the circuit is: P psia = 118.3 + 14.7 = 133.0 psia P_{\text{psia}} = 118.3 + 14.7 = 133.0\text{ psia} P psia ​ = 118.3 + 14.7 = 133.0 psia

3. Vacuum Measurements: Inches of Mercury and Microns

When measuring pressures below atmospheric pressure (deep evacuation), standard positive gauge scales lack adequate resolution. Technicians use two specialized scales:

Inches of Mercury Vacuum ( in. Hg vac \text{in. Hg vac} in. Hg vac ) : Ranges from 0 in. Hg 0\text{ in. Hg} 0 in. Hg (atmospheric pressure) to 29.92 in. Hg 29.92\text{ in. Hg} 29.92 in. Hg (perfect vacuum). Compound gauges display this scale on the retard side.

Microns : The definitive scientific unit for deep vacuum measurement. A micron is one-millionth of a meter of mercury column ( 0.001 mm Hg 0.001\text{ mm Hg} 0.001 mm Hg ).

Standard atmospheric pressure = 760 , 000 microns 760,000\text{ microns} 760 , 000 microns .

1 in. Hg ≈ 25 , 400 microns 1\text{ in. Hg} \approx 25,400\text{ microns} 1 in. Hg ≈ 25 , 400 microns .

Target system evacuation (EPA standard / NATE best practice) = below 500 microns 500\text{ microns} 500 microns (with an isolated vacuum rise test not exceeding 1 , 000 microns 1,000\text{ microns} 1 , 000 microns ).

4. Inches of Water Column (in. w.c.)

In residential and light commercial HVAC, many critical pressures are far too subtle to be measured in pounds per square inch (psi). These include:

Gas manifold pressures on natural gas and propane furnaces.

Air handler external static pressure (ESP) across blower coils and ductwork.

Flue gas draft pressures in venting systems.

Technicians measure these using a digital manometer or inclined liquid manometer in inches of water column ( in. w.c. \text{in. w.c.} in. w.c. ) —the pressure required to support a column of water one inch high.

Pressure Conversion Constants Mathematical Value

1 psi 1\text{ psi} 1 psi in Inches of Water Column 27.7 in. w.c. 27.7\text{ in. w.c.} 27.7 in. w.c. (exact: 27.71 in. w.c. 27.71\text{ in. w.c.} 27.71 in. w.c. )

1 in. Hg 1\text{ in. Hg} 1 in. Hg in Inches of Water Column 13.6 in. w.c. 13.6\text{ in. w.c.} 13.6 in. w.c. (mercury is 13.6 times denser than water)

1 in. w.c. 1\text{ in. w.c.} 1 in. w.c. in psi 0.0361 psi 0.0361\text{ psi} 0.0361 psi

Standard HVAC Field Pressure Applications:

Natural Gas Furnace Manifold Pressure : Typically 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. (equivalent to 3.5 27.7 ≈ 0.126 psi \frac{3.5}{27.7} \approx 0.126\text{ psi} 27.7 3.5 ​ ≈ 0.126 psi ).

Liquefied Petroleum (LP/Propane) Manifold Pressure : Typically 10.5 to 11.0 in. w.c. 10.5\text{ to } 11.0\text{ in. w.c.} 10.5 to 11.0 in. w.c. (approx. 0.38 to 0.40 psi 0.38\text{ to } 0.40\text{ psi} 0.38 to 0.40 psi ).

External Static Pressure (ESP) : Total external static pressure across an air handler typically targets 0.50 in. w.c. 0.50\text{ in. w.c.} 0.50 in. w.c. for standard residential blowers.

Natural Draft Chimney Draft : Typically − 0.02 to − 0.04 in. w.c. -0.02\text{ to } -0.04\text{ in. w.c.} − 0.02 to − 0.04 in. w.c. (negative draft pulling combustion gases upward).

Fundamental Electrical Formulas: Ohm's Law and Electric Power

Electrical diagnostics represents 26% of the Core exam. Technicians must be thoroughly fluent in the mathematical relationships governing voltage, current, resistance, and power.

Ohm's Law

Ohm's law defines the relationship between electromotive force (Voltage, E E E ), intensity of current (Amperage, I I I ), and opposition to current flow (Resistance, R R R ): E = I × R I = E R R = E I \mathbf{E = I \times R} \qquad \mathbf{I = \frac{E}{R}} \qquad \mathbf{R = \frac{E}{I}} E = I × R I = R E ​ R = I E ​

E E E (Voltage) : Measured in Volts ( V \text{V} V ). The electrical pressure driving charge through a conductor.

I I I (Current) : Measured in Amperes or Amps ( A \text{A} A ). The rate of electron flow ( 1 Ampere = 1 Coulomb/second 1\text{ Ampere} = 1\text{ Coulomb/second} 1 Ampere = 1 Coulomb/second ).

R R R (Resistance) : Measured in Ohms ( Ω \Omega Ω ). The opposition to current flow.

Electric Power (Watt's Law)

Power is the rate at which electrical energy is converted into work or heat. In direct current (DC) circuits and single-phase alternating current (AC) pure resistive circuits (such as electric heating elements), power is given by: P = E × I P = I 2 × R P = E 2 R \mathbf{P = E \times I} \qquad \mathbf{P = I^2 \times R} \qquad \mathbf{P = \frac{E^2}{R}} P = E × I P = I 2 × R P = R E 2 ​

P P P (Power) : Measured in Watts ( W \text{W} W ) or Kilowatts ( 1 kW = 1 , 000 W 1\text{ kW} = 1,000\text{ W} 1 kW = 1 , 000 W ).

Power Conversion to Thermal Energy

In HVAC calculations, technicians must frequently bridge the gap between electrical input and thermal output: 1 Watt = 3.412 Btu/hr 1 kW = 3 , 412 Btu/hr \mathbf{1\text{ Watt} = 3.412\text{ Btu/hr}} \qquad \mathbf{1\text{ kW} = 3,412\text{ Btu/hr}} 1 Watt = 3.412 Btu/hr 1 kW = 3 , 412 Btu/hr

A 5 kW 5\text{ kW} 5 kW electric heating element produces: 5 kW × 3 , 412 Btu/kW = 17 , 060 Btu/hr 5\text{ kW} \times 3,412\text{ Btu/kW} = 17,060\text{ Btu/hr} 5 kW × 3 , 412 Btu/kW = 17 , 060 Btu/hr

A 10 kW 10\text{ kW} 10 kW heating package produces: 10 kW × 3 , 412 Btu/kW = 34 , 120 Btu/hr 10\text{ kW} \times 3,412\text{ Btu/kW} = 34,120\text{ Btu/hr} 10 kW × 3 , 412 Btu/kW = 34 , 120 Btu/hr

The Fundamental Airflow Equations: Sensible and Total Heat

Air distribution is the vehicle through which conditioning is delivered to the space. The two most critical equations tested on the NATE Core exam are the sensible heat equation and the total heat equation .

1. The Sensible Heat Equation

Sensible heat is heat that causes a measurable change in dry-bulb temperature without changing the moisture content (humidity ratio) of the air. Q sensible = 1.08 × CFM × Δ T \mathbf{Q_{\text{sensible}} = 1.08 \times \text{CFM} \times \Delta T} Q sensible ​ = 1.08 × CFM × ΔT

Where:

Q sensible Q_{\text{sensible}} Q sensible ​ : Sensible heat transfer rate in Btu/hr \text{Btu/hr} Btu/hr .

CFM \text{CFM} CFM : Airflow volume in Cubic Feet per Minute .

Δ T \Delta T Δ T : Temperature difference between entering and leaving air in ∘ F ^\circ\text{F} ∘ F ( Δ T = T supply − T return \Delta T = T_{\text{supply}} - T_{\text{return}} Δ T = T supply ​ − T return ​ or T return − T supply T_{\text{return}} - T_{\text{supply}} T return ​ − T supply ​ ).

1.08 1.08 1.08 : The sensible heat constant for standard air at sea level ( 70 ∘ F 70^\circ\text{F} 7 0 ∘ F , 29.92 in. Hg 29.92\text{ in. Hg} 29.92 in. Hg , density ρ = 0.075 lb/ft 3 \rho = 0.075\text{ lb/ft}^3 ρ = 0.075 lb/ft 3 , specific heat c p = 0.24 Btu/lb ⋅ ∘ F c_p = 0.24\text{ Btu/lb}\cdot^\circ\text{F} c p ​ = 0.24 Btu/lb ⋅ ∘ F ): Constant = 60 min hr × 0.075 lb ft 3 × 0.24 Btu lb ⋅ ∘ F = 1.08 Btu ⋅ min ft 3 ⋅ hr ⋅ ∘ F \text{Constant} = 60\frac{\text{min}}{\text{hr}} \times 0.075\frac{\text{lb}}{\text{ft}^3} \times 0.24\frac{\text{Btu}}{\text{lb}\cdot^\circ\text{F}} = 1.08\frac{\text{Btu}\cdot\text{min}}{\text{ft}^3\cdot\text{hr}\cdot^\circ\text{F}} Constant = 60 hr min ​ × 0.075 ft 3 lb ​ × 0.24 lb ⋅ ∘ F Btu ​ = 1.08 ft 3 ⋅ hr ⋅ ∘ F Btu ⋅ min ​

Algebraic Variations of the Sensible Heat Formula:

Solving for Airflow ( CFM \text{CFM} CFM ) : CFM = Q sensible 1.08 × Δ T \mathbf{\text{CFM} = \frac{Q_{\text{sensible}}}{1.08 \times \Delta T}} CFM = 1.08 × ΔT Q sensible ​ ​

Solving for Temperature Difference ( Δ T \Delta T Δ T ) : Δ T = Q sensible 1.08 × CFM \mathbf{\Delta T = \frac{Q_{\text{sensible}}}{1.08 \times \text{CFM}}} ΔT = 1.08 × CFM Q sensible ​ ​

2. The Total Heat Equation (Enthalpy Equation)

In cooling and dehumidification, air undergoes both a dry-bulb temperature drop (sensible cooling) and moisture condensation (latent cooling). Total cooling capacity must therefore account for both sensible and latent heat removal using specific enthalpy ( h h h ) , measured in Btu per pound of dry air \text{Btu per pound of dry air} Btu per pound of dry air : Q total = 4.5 × CFM × Δ h \mathbf{Q_{\text{total}} = 4.5 \times \text{CFM} \times \Delta h} Q total ​ = 4.5 × CFM × Δh

Where:

Q total Q_{\text{total}} Q total ​ : Total heat transfer rate in Btu/hr \text{Btu/hr} Btu/hr .

Δ h \Delta h Δ h : Change in specific enthalpy between entering and leaving air ( h entering − h leaving h_{\text{entering}} - h_{\text{leaving}} h entering ​ − h leaving ​ ) in Btu/lb \text{Btu/lb} Btu/lb .

4.5 4.5 4.5 : The total heat air constant for standard air: Constant = 60 min hr × 0.075 lb ft 3 = 4.5 lb ⋅ min ft 3 ⋅ hr \text{Constant} = 60\frac{\text{min}}{\text{hr}} \times 0.075\frac{\text{lb}}{\text{ft}^3} = 4.5\frac{\text{lb}\cdot\text{min}}{\text{ft}^3\cdot\text{hr}} Constant = 60 hr min ​ × 0.075 ft 3 lb ​ = 4.5 ft 3 ⋅ hr lb ⋅ min ​

3. Cooling Tonnage Equivalents

Technicians must remember standard cooling capacity ratings: 1 Ton of Refrigeration = 12 , 000 Btu/hr = 200 Btu/min \mathbf{1\text{ Ton of Refrigeration} = 12,000\text{ Btu/hr} = 200\text{ Btu/min}} 1 Ton of Refrigeration = 12 , 000 Btu/hr = 200 Btu/min

A nominal residential system operates at approximately 400 CFM per ton 400\text{ CFM per ton} 400 CFM per ton of cooling under standard humid climate design conditions (varying between 350 CFM/ton 350\text{ CFM/ton} 350 CFM/ton for high latent removal and 450 CFM/ton 450\text{ CFM/ton} 450 CFM/ton for dry, arid climates).

A 3-ton system typically requires: 3 tons × 400 CFM/ton = 1 , 200 CFM 3\text{ tons} \times 400\text{ CFM/ton} = 1,200\text{ CFM} 3 tons × 400 CFM/ton = 1 , 200 CFM .

  • Worked Engineering & Diagnostic Calculations
  • Calculation 1: Determining Airflow via Electric Heat Strip Testing

Scenario : A technician is commissioning a residential air handler with an electric heat strip. The technician measures:

Line Voltage: E = 240 V E = 240\text{ V} E = 240 V

Total Current Draw of Heaters: I = 40 A I = 40\text{ A} I = 40 A (blower motor amperage is isolated and excluded)

Return Air Dry-Bulb Temperature: T return = 68 ∘ F T_{\text{return}} = 68^\circ\text{F} T return ​ = 6 8 ∘ F

Supply Air Dry-Bulb Temperature: T supply = 104 ∘ F T_{\text{supply}} = 104^\circ\text{F} T supply ​ = 10 4 ∘ F

Step 1: Calculate electrical heat output in Watts and Btu/hr P = E × I = 240 V × 40 A = 9 , 600 W = 9.6 kW P = E \times I = 240\text{ V} \times 40\text{ A} = 9,600\text{ W} = 9.6\text{ kW} P = E × I = 240 V × 40 A = 9 , 600 W = 9.6 kW Q sensible = 9 , 600 W × 3.412 Btu/hr W = 32 , 755.2 Btu/hr Q_{\text{sensible}} = 9,600\text{ W} \times 3.412\frac{\text{Btu/hr}}{\text{W}} = 32,755.2\text{ Btu/hr} Q sensible ​ = 9 , 600 W × 3.412 W Btu/hr ​ = 32 , 755.2 Btu/hr

Step 2: Calculate temperature rise ( Δ T \Delta T Δ T ) Δ T = 104 ∘ F − 68 ∘ F = 36 ∘ F \Delta T = 104^\circ\text{F} - 68^\circ\text{F} = 36^\circ\text{F} Δ T = 10 4 ∘ F − 6 8 ∘ F = 3 6 ∘ F

Step 3: Solve for CFM using the sensible heat formula CFM = Q sensible 1.08 × Δ T = 32 , 755.2 1.08 × 36 = 32 , 755.2 38.88 ≈ 842.5 CFM \text{CFM} = \frac{Q_{\text{sensible}}}{1.08 \times \Delta T} = \frac{32,755.2}{1.08 \times 36} = \frac{32,755.2}{38.88} \approx 842.5\text{ CFM} CFM = 1.08 × Δ T Q sensible ​ ​ = 1.08 × 36 32 , 755.2 ​ = 38.88 32 , 755.2 ​ ≈ 842.5 CFM

The blower is delivering approximately 843 CFM 843\text{ CFM} 843 CFM .

Calculation 2: Determining Gas Furnace Temperature Rise

Scenario : A technician services an 80 % 80\% 80% AFUE gas furnace with an input rating of 80 , 000 Btu/hr 80,000\text{ Btu/hr} 80 , 000 Btu/hr . The system is delivering a measured airflow of 1 , 200 CFM 1,200\text{ CFM} 1 , 200 CFM . What is the expected temperature rise ( Δ T \Delta T Δ T ) across the heat exchanger?

Step 1: Calculate furnace heating output capacity ( Q Q Q ) Q = Input Rating × Efficiency = 80 , 000 Btu/hr × 0.80 = 64 , 000 Btu/hr Q = \text{Input Rating} \times \text{Efficiency} = 80,000\text{ Btu/hr} \times 0.80 = 64,000\text{ Btu/hr} Q = Input Rating × Efficiency = 80 , 000 Btu/hr × 0.80 = 64 , 000 Btu/hr

Step 2: Solve for Δ T \Delta T Δ T Δ T = Q 1.08 × CFM = 64 , 000 1.08 × 1 , 200 = 64 , 000 1 , 296 ≈ 49.38 ∘ F \Delta T = \frac{Q}{1.08 \times \text{CFM}} = \frac{64,000}{1.08 \times 1,200} = \frac{64,000}{1,296} \approx 49.38^\circ\text{F} Δ T = 1.08 × CFM Q ​ = 1.08 × 1 , 200 64 , 000 ​ = 1 , 296 64 , 000 ​ ≈ 49.3 8 ∘ F

The expected temperature rise across the furnace heat exchanger is approximately 49.4 ∘ F 49.4^\circ\text{F} 49. 4 ∘ F . If the furnace nameplate lists an allowable rise of 40 ∘ F to 70 ∘ F 40^\circ\text{F} \text{ to } 70^\circ\text{F} 4 0 ∘ F to 7 0 ∘ F , this operating condition falls perfectly within manufacturer specifications.

Calculation 3: Manifold Gas Pressure Conversion

Scenario : A field technician measures a natural gas manifold pressure of 3.5 in. w.c. 3.5\text{ in. w.c.} 3.5 in. w.c. using a digital manometer. The customer's industrial engineering manager asks for this pressure in pounds per square inch (psi).

Calculation :

Since 1 psi = 27.7 in. w.c. 1\text{ psi} = 27.7\text{ in. w.c.} 1 psi = 27.7 in. w.c. : P psi = 3.5 in. w.c. 27.7 in. w.c./psi ≈ 0.126 psi P_{\text{psi}} = \frac{3.5\text{ in. w.c.}}{27.7\text{ in. w.c./psi}} \approx 0.126\text{ psi} P psi ​ = 27.7 in. w.c./psi 3.5 in. w.c. ​ ≈ 0.126 psi

This calculation highlights why manometers are indispensable in HVAC work: a pressure difference of 0.126 psi 0.126\text{ psi} 0.126 psi would barely register off the pin of a standard 0 – 100 psig 0\text{–}100\text{ psig} 0 – 100 psig gauge.

Comprehensive HVAC Formula & Constant Reference Sheet

Formula Name Equation Units & Key Constants

Fahrenheit to Celsius ∘ C = ( ∘ F − 32 ) ÷ 1.8 ^\circ\text{C} = (^\circ\text{F} - 32) \div 1.8 ∘ C = ( ∘ F − 32 ) ÷ 1.8 ∘ F ^\circ\text{F} ∘ F , ∘ C ^\circ\text{C} ∘ C

Celsius to Fahrenheit ∘ F = ( ∘ C × 1.8 ) + 32 ^\circ\text{F} = (^\circ\text{C} \times 1.8) + 32 ∘ F = ( ∘ C × 1.8 ) + 32 ∘ F ^\circ\text{F} ∘ F , ∘ C ^\circ\text{C} ∘ C

Absolute Temperature (Rankine) ∘ R = ∘ F + 460 ^\circ\text{R} = ^\circ\text{F} + 460 ∘ R = ∘ F + 460 Mandatory for imperial gas laws

Absolute Temperature (Kelvin) K = ∘ C + 273 \text{K} = ^\circ\text{C} + 273 K = ∘ C + 273 Mandatory for metric gas laws

Absolute Pressure (psia) P psia = P psig + 14.7 P_{\text{psia}} = P_{\text{psig}} + 14.7 P psia ​ = P psig ​ + 14.7 At standard sea level

Water Column to psi psi = in. w.c. ÷ 27.7 \text{psi} = \text{in. w.c.} \div 27.7 psi = in. w.c. ÷ 27.7 1 psi = 27.7 in. w.c. 1\text{ psi} = 27.7\text{ in. w.c.} 1 psi = 27.7 in. w.c.

Mercury to Water Column in. w.c. = in. Hg × 13.6 \text{in. w.c.} = \text{in. Hg} \times 13.6 in. w.c. = in. Hg × 13.6 Mercury density ratio = 13.6

  • Ohm's Law (Voltage) E = I × R E = I \times R E = I × R Volts, Amperes, Ohms
  • Electric Power (Watts) P = E × I P = E \times I P = E × I Pure resistive / DC loads

Electrical Thermal Equivalent Q = Watts × 3.412 Q = \text{Watts} \times 3.412 Q = Watts × 3.412 1 kW = 3 , 412 Btu/hr 1\text{ kW} = 3,412\text{ Btu/hr} 1 kW = 3 , 412 Btu/hr

Sensible Heat Equation Q sensible = 1.08 × CFM × Δ T Q_{\text{sensible}} = 1.08 \times \text{CFM} \times \Delta T Q sensible ​ = 1.08 × CFM × Δ T Standard air constant = 1.08

Total Heat Equation Q total = 4.5 × CFM × Δ h Q_{\text{total}} = 4.5 \times \text{CFM} \times \Delta h Q total ​ = 4.5 × CFM × Δ h Standard air constant = 4.5

Cooling Tonnage Equivalent 1 Ton = 12 , 000 Btu/hr 1\text{ Ton} = 12,000\text{ Btu/hr} 1 Ton = 12 , 000 Btu/hr Nominal airflow ≈ 400 CFM/ton \approx 400\text{ CFM/ton} ≈ 400 CFM/ton

Common Math Traps on the NATE Core Exam

Forgetting to convert Watts to Btu/hr : When evaluating electric heat strip temperature rise, remember that multiplying Amps by Volts yields Watts, not Btu/hr. You must multiply Watts by 3.412 3.412 3.412 before inserting into Q = 1.08 × CFM × Δ T Q = 1.08 \times \text{CFM} \times \Delta T Q = 1.08 × CFM × Δ T .

Using Input Rating instead of Output Capacity : On gas or oil heating calculations, furnaces are rated by input Btu/hr. The heat transferred to the air stream is the output ( Q output = Input × AFUE Efficiency Q_{\text{output}} = \text{Input} \times \text{AFUE Efficiency} Q output ​ = Input × AFUE Efficiency ). Using the gross input rating will overstate calculated airflow or temperature rise by 10% to 20%.

Plugging Gauge Pressure into Gas Law Formulas : In any formula evaluating pressure changes due to temperature (e.g., P 1 / T 1 = P 2 / T 2 P_1/T_1 = P_2/T_2 P 1 ​ / T 1 ​ = P 2 ​ / T 2 ​ ), both pressure and temperature must be absolute ( P P P in psia, T T T in °R).

Confusing Water Column (in. w.c.) with Inches of Mercury (in. Hg) : Remember that water is much lighter than mercury. 1 in. Hg 1\text{ in. Hg} 1 in. Hg equals 13.6 in. w.c. 13.6\text{ in. w.c.} 13.6 in. w.c. , and 1 psi 1\text{ psi} 1 psi equals 27.7 in. w.c. 27.7\text{ in. w.c.} 27.7 in. w.c. , whereas 1 psi 1\text{ psi} 1 psi equals only 2.036 in. Hg 2.036\text{ in. Hg} 2.036 in. Hg .